Plan Review Details - Permit 14091093
Plan Review Stops For Permit 14091093 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2014-10-22 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-10-22 |
Time |
15:28 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-10-22 |
Time |
15:28 |
Sent To |
|
|
Notes |
2014-10-22 15:30:10 | 2ND REVIEW: FBC 2010 | | | | PROVISO: SUBMIT A REVISION FOR THE INFORMATION BELOW: | | FBC 107.3.5 STRUCTURAL PLAN REVIEW CRITERIA SHALL | | INCLUDE WALL SYSTEMS. SPECIFY THE SPACING OR CLARIFY | | THE QUANTITY AND TYPE OF THE "TITEN" ANCHORS IN THE TOP | | AND BOTTOM PLATES IN WALL SECTION A. ADDITIONALLY, | | SPECIFY ANY CONNECTION AT THE ENDS/SIDES OF EACH WALL | | TO THE EXISTING STRUCTURE. PLEASE NOTE THE EXISTING | | FOUNDATION ON SECTIONS A APPREARS TO BE LARGER AND TO | | HAVE MORE RE-INFORCING THAN THE SECTION ON THE ORIGINAL | | CONSTRUCTION PLANS ON FILE. THAT PLAN SHOW THE FOOTING | | TO BE 8X8 W/1#5. | | | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-10-01 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-10-01 |
Time |
17:06 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-10-01 |
Time |
17:06 |
Sent To |
|
|
Notes |
2014-10-01 17:17:34 | 1ST REVIEW: FBC 2010 | | | | FBC 107.3.5 STRUCTURAL PLAN REVIEW CRITERIA SHALL | | INCLUDE WALL SYSTEMS. SPECIFY THE SPACING OR CLARIFY | | THE QUANTITY AND TYPE OF THE "TITEN" ANCHORS IN THE TOP | | AND BOTTOM PLATES IN WALL SECTION A. ADDITIONALLY, | | SPECIFY ANY CONNECTION AT THE ENDS/SIDES OF EACH WALL | | TO THE EXISTING STRUCTURE. PLEASE NOTE THE EXISTING | | FOUNDATION ON SECTIONS A APPREARS TO BE LARGER AND TO | | HAVE MORE RE-INFORCING THAN THE SECTION ON THE ORIGINAL | | CONSTRUCTION PLANS ON FILE. THAT PLAN SHOW THE FOOTING | | TO BE 8X8 W/1#5. | | | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2014-10-01 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-10-01 |
Time |
17:06 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-10-01 |
Time |
17:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2014-10-02 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-10-02 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-10-02 |
Time |
12:38 |
Sent To |
PC |
|
Notes |
2014-10-02 12:43:27 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE | | FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND | | COMPLIANCE. | | | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | CONSTRUCTION PERIOD. | | | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | AND COMPLETE PROTECTION IS RETURNED. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-10-02 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-10-02 |
Time |
|
Rev Time |
|
Received By |
pleduc |
Date |
2014-09-30 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2014-10-01 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-10-01 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-10-01 |
Time |
16:55 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2014-10-01 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-10-01 |
Time |
17:17 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-10-01 |
Time |
17:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2014-09-30 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2014-09-30 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
sgraham |
Date |
2014-09-30 |
Time |
15:47 |
Sent To |
B1 |
|
Notes |
|
|
|