Plan Review Details - Permit 14091093
Plan Review Stops For Permit 14091093
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-22 Cont ID  
Sent By skennedy Date 2014-10-22 Time 15:28 Rev Time 0.00
Received By skennedy Date 2014-10-22 Time 15:28 Sent To  
Notes
2014-10-22 15:30:102ND REVIEW: FBC 2010
  
 PROVISO: SUBMIT A REVISION FOR THE INFORMATION BELOW:
 FBC 107.3.5 STRUCTURAL PLAN REVIEW CRITERIA SHALL
 INCLUDE WALL SYSTEMS. SPECIFY THE SPACING OR CLARIFY
 THE QUANTITY AND TYPE OF THE "TITEN" ANCHORS IN THE TOP
 AND BOTTOM PLATES IN WALL SECTION A. ADDITIONALLY,
 SPECIFY ANY CONNECTION AT THE ENDS/SIDES OF EACH WALL
 TO THE EXISTING STRUCTURE. PLEASE NOTE THE EXISTING
 FOUNDATION ON SECTIONS A APPREARS TO BE LARGER AND TO
 HAVE MORE RE-INFORCING THAN THE SECTION ON THE ORIGINAL
 CONSTRUCTION PLANS ON FILE. THAT PLAN SHOW THE FOOTING
 TO BE 8X8 W/1#5.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-01 Cont ID  
Sent By skennedy Date 2014-10-01 Time 17:06 Rev Time 0.00
Received By skennedy Date 2014-10-01 Time 17:06 Sent To  
Notes
2014-10-01 17:17:341ST REVIEW: FBC 2010
  
 FBC 107.3.5 STRUCTURAL PLAN REVIEW CRITERIA SHALL
 INCLUDE WALL SYSTEMS. SPECIFY THE SPACING OR CLARIFY
 THE QUANTITY AND TYPE OF THE "TITEN" ANCHORS IN THE TOP
 AND BOTTOM PLATES IN WALL SECTION A. ADDITIONALLY,
 SPECIFY ANY CONNECTION AT THE ENDS/SIDES OF EACH WALL
 TO THE EXISTING STRUCTURE. PLEASE NOTE THE EXISTING
 FOUNDATION ON SECTIONS A APPREARS TO BE LARGER AND TO
 HAVE MORE RE-INFORCING THAN THE SECTION ON THE ORIGINAL
 CONSTRUCTION PLANS ON FILE. THAT PLAN SHOW THE FOOTING
 TO BE 8X8 W/1#5.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-10-01 Cont ID  
Sent By skennedy Date 2014-10-01 Time 17:06 Rev Time 0.00
Received By skennedy Date 2014-10-01 Time 17:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-10-02 Cont ID  
Sent By pleduc Date 2014-10-02 Time   Rev Time 0.00
Received By pleduc Date 2014-10-02 Time 12:38 Sent To PC
Notes
2014-10-02 12:43:27THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-02 Cont ID  
Sent By pleduc Date 2014-10-02 Time   Rev Time  
Received By pleduc Date 2014-09-30 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-10-01 Cont ID  
Sent By skennedy Date 2014-10-01 Time 16:55 Rev Time 0.00
Received By skennedy Date 2014-10-01 Time 16:55 Sent To FIRE
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-10-01 Cont ID  
Sent By skennedy Date 2014-10-01 Time 17:17 Rev Time 0.00
Received By skennedy Date 2014-10-01 Time 17:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-30 Cont ID  
Sent By sgraham Date 2014-09-30 Time 15:47 Rev Time 0.00
Received By sgraham Date 2014-09-30 Time 15:47 Sent To B1
Notes
***NONE***