Plan Review Details - Permit 14091005
Plan Review Stops For Permit 14091005
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-12-27 Cont ID  
Sent By rmcdouga Date 2014-12-27 Time 08:32 Rev Time 0.00
Received By rmcdouga Date 2014-12-24 Time 08:49 Sent To  
Notes
2014-12-27 07:34:14APPROVED WITH EXCEPTIONS.
 -SUBMIT TWO COPIES OF THE CURRENT PRODUCT APPROVAL FOR
 THE CAST-CRETE 8 INCH LINTELS THAT HAVE BEEN REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. FBC
 107.3.4

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-22 Cont ID  
Sent By rmcdouga Date 2014-10-22 Time 11:08 Rev Time 0.00
Received By rmcdouga Date 2014-10-20 Time 08:40 Sent To  
Notes
2014-10-22 10:16:10PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 BUILDING DENIED
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOTE 2 ON SHEETS A-1 AND A-2 INCORRECTLY REFERENCES
 THE FBC 2007 / 2009 AMENDMENTS. THE CORRECT EDITION IS
 THE FBC 2010.
  
 2) IN THE DOOR SCHEDULE ON SHEETS A-1 AND A-2, FOR DOOR
 #2 THE DESIGN OPENING PRESSURES ARE MORE THAN THE NOA
 PRESSURES OF +/- 50 PSF. THE PRODUCT APPROVAL, FL#
 14665.1 HAS PRESSURES OF +/- 55 PSF. FBC-R 301.2.1
  
 3) THE WINDOW SCHEDULE APPEARS TO BE MISSING FROM THE
 PLANS. FBC 107.2.1 AND FBC-R 301.2.1
  
 4) DESIGNATE THE EGRESS WINDOW IN THE MASTER BEDROOM OF
 THE RIGHT UNIT. FBC-R310.1
  
 5) THE FOLLOWING MIAMI-DADE NOAS HAVE BEEN SUPERSEDED:
 BORAL TILESEAL (NOA NO. 12-0417.06) AND CASTCRETE 8"
 LINTELS (NOA NO. 12-0209.13). SUBMIT THE CURRENT NOAS.
 DCA RULE 9N-3
  
 6) THE FLORIDA PRODUCT APPROVAL ( FL# 7170 )THAT WAS
 SUBMITTED FOR THE AMARR SECTIONAL GARAGE DOOR IS FOR
 THE 2007 FBC. SUBMIT THE PRODUCT APPROVAL THAT
 REFERENCES THE 2010 FBC EDITION.
  
 7) THE PRODUCT APPROVAL NUMBERS THAT ARE SPECIFIED IN
 THE DOOR SCHEDULE ON THE PLANS FOR THE FIBERGLASS ENTRY
 DOOR AND THE SLIDING GLASS DOOR DO NOT MATCH THE ONES
 THAT WERE SUBMITTED. FBC 107.2.1
  
 8) THE NOA OPENING PRESSURE FOR THE SLIDING GLASS DOOR
 IS +/- 80.0 PSF IN THE DOOR SCHEDULE AND +/- 60 PSF IN
 THE PRODUCT APPROVAL THAT WAS SUBMITTED. FBC 107.2.1
  
 7) SPECIFY THE ROOF TILE (PROFILE), SIZE AND NUMBER OF
 SCREWS THAT WILL BE USED TO PROVIDE WINDLOAD RESISTANCE
 PER FRSA/TRI 07320/8-05. FBC-R 301.2.1
  
 8) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-12-24 Cont ID  
Sent By rmcdouga Date 2014-12-24 Time 13:08 Rev Time 0.00
Received By rmcdouga Date 2014-12-24 Time 13:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-22 Cont ID  
Sent By rmcdouga Date 2014-10-22 Time 16:04 Rev Time 0.00
Received By rmcdouga Date 2014-10-22 Time 16:04 Sent To  
Notes
2014-10-22 16:04:28PLAN REVIEW COMMENTS
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 ELECTRIC DENIED
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 REQUIRED BY THE BUILDING OFFICIAL, AND MAY REQUIRE ONLY
 ONE SET OF SUBMITTALS. ONLY ONE SET OF PLANS WAS
 SUBMITTED FOR THE TWO UNIT TOWNHOUSE.
  
 2) THE PLANS REFERENCE THE 2009 NEC IN SEVERAL PLACES.
 THE 2008 NEC IS THE APPLICABLE CODE EDITION FOR THIS
 PROJECT.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-31 Cont ID  
Sent By rmcdouga Date 2014-12-31 Time 12:59 Rev Time 0.00
Received By rmcdouga Date 2014-12-19 Time 15:08 Sent To  
Notes
2014-12-19 15:08:36R29
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-19 Cont ID  
Sent By shill Date 2014-10-29 Time 15:14 Rev Time 0.00
Received By shill Date 2014-09-29 Time 07:06 Sent To  
Notes
2014-09-29 07:06:35INCOMING SENT TO R13. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-01-05 Cont ID  
Sent By rmcdouga Date 2015-01-05 Time 12:38 Rev Time 0.00
Received By rmcdouga Date 2015-01-05 Time 12:38 Sent To  
Notes
2015-01-05 12:41:15MU2014-2257, 2377

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-12-24 Cont ID  
Sent By rmcdouga Date 2014-12-24 Time 11:13 Rev Time 0.00
Received By rmcdouga Date 2014-12-24 Time 11:13 Sent To  
Notes
2014-12-24 11:13:47BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-10-20 Cont ID  
Sent By rmcdouga Date 2014-10-20 Time 08:40 Rev Time 0.00
Received By rmcdouga Date 2014-10-20 Time 08:40 Sent To  
Notes
2014-10-20 10:09:59BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-12-24 Cont ID  
Sent By rmcdouga Date 2014-12-24 Time 12:48 Rev Time 0.00
Received By rmcdouga Date 2014-12-24 Time 12:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-10-07 Cont ID  
Sent By rbergsma Date 2014-10-07 Time   Rev Time 1.00
Received By rbergsma Date   Time   Sent To  
Notes
2014-10-07 14:40:50DRAWINGS APPROVED AS NOTED, DRYER EXHAUST MUST BE 26
 GAUGE AS PER --FBC-M 504.6 ,
 DRAWINGS SPEC 30 GAUGE

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-12-24 Cont ID  
Sent By rmcdouga Date 2014-12-24 Time 12:46 Rev Time 0.00
Received By rmcdouga Date 2014-12-24 Time 12:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-10-20 Cont ID  
Sent By rmcdouga Date 2014-10-20 Time 18:41 Rev Time 0.00
Received By rmcdouga Date 2014-10-20 Time 18:41 Sent To  
Notes
2014-10-22 16:05:23APPROVED PENDING SUBMITTAL OF ONE ADDITIONAL SET OF
 PLANS.

Review Stop Z ZONING
Rev No 2 Status P Date 2014-12-31 Cont ID  
Sent By eschneid Date 2014-12-31 Time 10:38 Rev Time 0.25
Received By eschneid Date 2014-12-31 Time 10:38 Sent To PC
Notes
2014-12-31 10:38:591) A SEPARATE LANDSCAPE AND IRRIGATION PERMIT AND THEIR
 INSTALLATION IS REQUIRED PRIOR TO CO.
  
 2) SCREEN ENCLOSURE REQUIRES SEPARATE PERMIT.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-10-29 Cont ID  
Sent By eschneid Date 2014-10-29 Time 10:23 Rev Time 0.50
Received By eschneid Date 2014-10-29 Time 10:23 Sent To  
Notes
2014-10-29 10:49:52FAILED
  
 1) ONLY ONE SET OF PLANS WAS SUBMITTED WITH THIS
 APPLICATION. PLEASE PROVIDE THE SECOND SET OF PLANS.
  
 2) PLANS COMPLY WITH ZONING REQUIREMENTS.
  
 3) A SEPARATE LANDSCAPE AND IRRIGATION PERMIT AND THEIR
 INSTALLATION IS REQUIRED PRIOR TO CO.
  
 4) SCREEN ENCLOSURE REQUIRES SEPARATE PERMIT.
2014-10-09 14:57:5510/9/14