Plan Review Details - Permit 14090987
Plan Review Stops For Permit 14090987
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-20 Cont ID  
Sent By rmcdouga Date 2014-10-20 Time 07:52 Rev Time 0.00
Received By rmcdouga Date 2014-10-20 Time 06:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-03 Cont ID  
Sent By rmcdouga Date 2014-10-03 Time 18:48 Rev Time 0.00
Received By rmcdouga Date 2014-10-03 Time 18:48 Sent To  
Notes
2014-10-03 18:50:58PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) CORRECT THE CODE EDITION AND THE WINDSPEED DATA ON
 SHEET N-1. THE APPLICABLE CODE IS THE 2010 FBC. THE
 WIND SPEED IS 170 MPH VULT AND THE EXPOSURE CATEGORY IS
 D. FBC - R 301.2.1
  
 2) SPECIFY WHICH OF THE BARRIER METHODS LISTED IN FBC -
 R4101.17 WILL BE USED TO PROTECT ACCESS FROM THE
 DWELLING TO THE POOL.
  
 3) THE VALUATION ON THE PERMIT APPLICATION OF
 $13,000.00 FOR THE POOL IS TOO LOW. PLEASE SUBMIT AN
 ADEQUATE VALUE FOR THE NEW POOL AND EQUIPMENT. IF THE
 DEMO AND REMOVAL OF THE EXISTING POOL IS INCLUDED IN
 THIS PERMIT, THEN INCLUDE THE VALUE OF THAT WORK.
  
 4) THE PERMIT CAN NOT BE ISSUED UNTIL THE POOL PLUMBING
 AND ELECTRICAL PERMIT APPLICATIONS ARE SUBMITTED.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-10-20 Cont ID  
Sent By rmcdouga Date 2014-10-20 Time 06:58 Rev Time 0.00
Received By rmcdouga Date 2014-10-20 Time 06:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-03 Cont ID  
Sent By rmcdouga Date 2014-10-03 Time 18:47 Rev Time 0.00
Received By rmcdouga Date 2014-10-03 Time 18:47 Sent To  
Notes
2014-10-03 18:56:10PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 ELECTRICAL
  
 1) ON SHEET P-2 UNDER EQUIPMENT SELECTION IS LISTED "
 HEATER (ELECTRIC): JANDY 400 BTU GAS " . PLEASE CLARIFY
 IF THE POOL HEATER WILL BE GAS OR ELECTRIC AND CORRECT
 THE NOTE ACCORDINGLY. FBC 107.2.1
  
 2) IF THE POOL HEATER IS ELECTRIC, SUBMIT LOAD
 CALCULATIONS TO SHOW THAT THE EXISTING SERVICE WILL
 ACCOMMODATE THE NEW HEAT PUMP. NEC 220.40
  
 3) IF THE POOL HEATER IS ELECTRIC, SUBMIT THE CUT
 SHEETS WITH THE ELECTRIC REQUIREMENTS FOR THE POOL
 HEATER. NEC 680.9
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2014-10-04 Cont ID  
Sent By rmcdouga Date 2014-10-04 Time 07:36 Rev Time 0.00
Received By rmcdouga Date 2014-10-04 Time 07:36 Sent To  
Notes
2014-10-04 07:38:01NO GAS RISER PLAN WAS SUBMITTED AND NO APPLICATION FOR
 GAS WAS SUBMITTED. A SEPARATE PERMIT, APPLICATION AND
 REVIEW IS REQUIRED FOR GAS.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-09-26 Cont ID  
Sent By fmittner Date 2014-09-26 Time 13:09 Rev Time 0.00
Received By fmittner Date 2014-09-26 Time 13:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-20 Cont ID  
Sent By rmcdouga Date 2014-10-20 Time 07:52 Rev Time 0.00
Received By rmcdouga Date 2014-10-14 Time 14:09 Sent To  
Notes
2014-10-15 14:09:47RE-SUBMITTAL SENT TO TIM LARGE FOR PLUMBING REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-04 Cont ID  
Sent By rmcdouga Date 2014-10-04 Time 08:04 Rev Time 0.00
Received By rmcdouga Date 2014-09-29 Time 07:00 Sent To  
Notes
2014-09-29 07:01:06INCOMING SENT TO POOL BOX. JW

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-10-16 Cont ID  
Sent By tklarge Date 2014-10-16 Time 05:27 Rev Time 0.00
Received By tklarge Date 2014-10-16 Time 05:27 Sent To  
Notes
2014-10-16 05:33:57****PROVISO****
 MANUF. SPEC SHEETS FOR POOL HEATER THAT SHOWS THE
 HEATER IS LISTED AND LABELED PER THE 2010 FLORIDA FUEL
 GAS CODE SEC. 301.3.SHALL BE ON THE JOBSITE FOR
 INSPECTOR. THE SPECS ATTACHED TO THE PLANS DO NOT SHOW
 THE HEATER IS LISTED & LABELED. INSPECTOR TO CHECK UNIT
 IN FIELD.

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-10-02 Cont ID  
Sent By tklarge Date 2014-10-02 Time 11:21 Rev Time 0.00
Received By tklarge Date 2014-10-02 Time 10:23 Sent To  
Notes
2014-10-02 11:32:151) SUBMIT 2 COPIES OF MANUF. SPECS FOR THE POOL HEATER
 THAT SHOW THE HEATER IS LISTED AND LABELED PER THE 2010
 FUEL GAS CODE SEC. 301.3 .
 2) INDICATE THE TYPE OF POOL BARRIER TO BE INSTALLED
 AROUND THE POOL. BARRIER TO COMPLY W/2010 FBCR,
 SEC.R4101.17.
 3) SHT. N-1 - POOL EQUIPMENT DETAILS - REFER TO THE
 2007 FBC AND 140 MPH WIND LOAD. REVISE NOTE TO READ 170
 MPH AND 2010 FBC.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-26 Cont ID  
Sent By fmittner Date 2014-09-26 Time 13:09 Rev Time 0.00
Received By fmittner Date 2014-09-26 Time 13:09 Sent To  
Notes
***NONE***