Plan Review Details - Permit 14090975
Plan Review Stops For Permit 14090975
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-29 Cont ID  
Sent By jwitmer Date 2014-10-29 Time 14:20 Rev Time 0.00
Received By jwitmer Date 2014-10-29 Time 13:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-01 Cont ID  
Sent By jwitmer Date 2014-10-01 Time 16:41 Rev Time 0.00
Received By jwitmer Date 2014-10-01 Time 15:38 Sent To  
Notes
2014-10-01 16:41:10BUILDING PLAN REVIEW
 PERMIT: 14090975
 ADD: 401 N DIXIE, 2ND FLOOR RENOVATION
 CONT: ROBLING ARCHITECTURE
 TEL: (561649-6705
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 01/ 2014
 ACTION: DENIED
  
 1) THE TRAINING ROOM IS APPROX. 1504 SQ. FT. WHEN YOU
 DIVIDE BY 20 THE OCCUPANT LOAD WOULD BE 76 OCCUPANTS.
 THIS WILL PUT THIS SPACE INTO A ASSEMBLY USAGE. SECTION
 508.2 PROVIDES THE CRITERIA TO DETERMINE IF THIS AREA
 IS TO BE CLASSIFIED AS A ACCESSORY OCCUPANCY OR IF THIS
 WILL BE CONSIDERED A MIXED OCCUPANCY. PLEASE REVIEW
 508.2.1 AREA LIMITATIONS. 508.2.1 AREA LIMITATIONS.
 AGGREGATE ACCESSORY OCCUPANCIES SHALL NOT OCCUPY MORE
 THAN 10 PERCENT OF THE BUILDING AREA OF THE STORY IN
 WHICH THEY ARE LOCATED AND SHALL NOT EXCEED THE TABULAR
 VALUES IN TABLE 503, WITHOUT BUILDING AREA INCREASES IN
 ACCORDANCE WITH SECTION 506 FOR SUCH ACCESSORY
 OCCUPANCIES.
 PLEASE PROVIDE ALL OF THE SQUARE FOOTAGE FOR ASSEMBLY
 USAGE ON THIS FLOOR, IF IT EXCEEDS 10 % OF THE FLOOR
 PLATE THEN THIS AREA WOULD BE CONSIDERED AN A3 ASSEMBLY
 OCCUPANCY AND REQUIRE RATED WALLS AS INDICATED IN TABLE
 508.4.
  
 THE OTHER OPTION THE DESIGN PROFESSIONAL HAS IS IN
 REVIEWING AND DECLARING NON-SEPARATED AND THE
 REQUIREMENTS FOUND IN 2010 FBC-B 508.3.
 (1-3).
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-10-29 Cont ID  
Sent By jwitmer Date 2014-10-29 Time 14:20 Rev Time 0.00
Received By dhayes Date 2014-10-29 Time 10:52 Sent To B
Notes
2014-10-29 10:52:58TO J.WITMER'S DESK.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-07 Cont ID  
Sent By dhayes Date 2014-10-07 Time 08:07 Rev Time 0.00
Received By dhayes Date 2014-10-07 Time 08:03 Sent To  
Notes
2014-10-07 08:12:0210/7/2014
 PROJECT: SA/PD ADMINISTRATION
 PERMIT#: 14090975
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION:
  
 1) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED
 MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND
 ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE
 REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL
 BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY
 INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF
 A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT
 REQUIRES EMERGENCY ILLUMINATION. NEC 700.16. THERE IS
 NOT ADAQUATE EMERGENCY ILLUMINATION AS DIRECTED BY THE
 NEC 700.16
  
 2) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT
 SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
 EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT
 EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL
 BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND
 BY ONE OF THE WIRING METHODS OF CHAPTER 3. NEC
 700.12(F)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-10-06 Cont ID  
Sent By pleduc Date 2014-10-06 Time   Rev Time 0.00
Received By pleduc Date 2014-10-06 Time 11:06 Sent To  
Notes
2014-10-06 11:17:50THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-29 Cont ID  
Sent By jwitmer Date 2014-10-29 Time 14:20 Rev Time 0.00
Received By jwitmer Date 2014-10-29 Time 10:52 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-07 Cont ID  
Sent By dhayes Date 2014-10-07 Time 08:12 Rev Time 0.00
Received By dhayes Date 2014-09-26 Time 13:19 Sent To  
Notes
2014-09-26 13:20:01INCOMING SENT TO B02 . JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-10-06 Cont ID  
Sent By rbergsma Date 2014-10-06 Time   Rev Time 0.50
Received By rbergsma Date   Time   Sent To  
Notes
***NONE***