Plan Review Details - Permit 14090973
Plan Review Stops For Permit 14090973
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2014-10-03 Cont ID  
Sent By jgomez Date 2014-10-03 Time 17:15 Rev Time 0.00
Received By jgomez Date 2014-10-03 Time 17:15 Sent To  
Notes
2014-10-03 17:18:34ENERGY CALCULATIONS SUBMITTED WERE NOT REQUESTED OR
 REQUIRED FOR THIS JOB. IT MAY BE A SUBMITTAL TO ADDRESS
 MECHANICAL REVIEW PROVISO. NEVERTHELESS, IT WAS NOT
 WHAT IT WAS REQUESTED ON ROBERT MCDOUGAL'S PROVISO.
 SENT TO ROBERT'S DESK FOR REVIEW. JG.
  
 *** REMAINDER TO CONTRACTOR:
 THERE WAS A BUILDING PROVISO DATED 8/7/14. INFORMATION
 REQUESTED IN THIS PROVISO NEED TO BE ADDRESSED. SEE
 COPY OF PROVISO BELOW:
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF COVER. GENERAL NOTES ON COVER SHEET INDICATES
 NEW ROOF AS PART OF THE SCOPE OF WORK.
 B) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS, DETAILS AND SPECIFICATIONS.
 C) WINDOW MULLIONS. NOA 11-0922.01 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA.
 D) ROUND CASEMENT WINDOW AS SHOWN ON PLANS.
 E) NEW ALUMINUM CASEMENT NOA 12-0216.04 WAS SUBMITTED.
 NEED TO PROVIDE TWO COPIES.
 F) NEW FRENCH DOORS FLORIDA PRODUCT APPROVAL FL14504
 WAS SUBMITTED. NEED TO PROVIDE TWO COPIES.
 2- ARCHITECT TO REVIEW AND APPROVE ABOVE PRODUCT
 APPROVALS. SEC. 107.3.4.1 OF CITY AMENDMENTS.
 3- SHEET A-2: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR INTERIOR HANDRAIL TO BE REPLACED.
 TABLE R301.5 AND SEC. R311.7.7.
 4- SHEET A-4: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR NEW MASTER BATHROOM BALCONY. TABLE
 R301.5 AND SEC. R312.
 5- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR NEW ARCHED OPENINGS IN THE REBUILT DEN AREA ON
 FIRST FLOOR. SEC. R301.
 6- SHEET A-9: REVISE ALL THE DOOR STRUCTURAL BUCK
 DETAILS. BUCK NEED TO PROVIDE FULL SUPPORT TO THE DOOR
 FRAME. SEC. R612.10.2.1.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-03 Cont ID  
Sent By rmcdouga Date 2014-10-03 Time 16:07 Rev Time 0.00
Received By rmcdouga Date 2014-09-26 Time 16:34 Sent To  
Notes
2014-09-26 16:35:17INCOMING SENT TO D. HAYES DESK .JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-10-03 Cont ID  
Sent By rmcdouga Date 2014-10-03 Time 16:07 Rev Time 0.00
Received By rmcdouga Date 2014-10-03 Time 16:06 Sent To  
Notes
2014-10-03 16:09:40REVISION DENIED
  
 1) THE TWO SETS OF ENERGY CALCULATIONS THAT WERE
 SUBMITTED WERE NOT REQUESTED NOR REQUIRED. PLEASE
 REVIEW THE (4) ITEMS THAT WERE REQUESTED ON THE
 CONDITIONALLY APPROVED HVAC PLANS (SHEET H-1). THEY ARE
 LISTED BELOW. IF YOU HAVE ANY QUESTIONS PLEASE CALL.
 WHEN SUBMITTING THE REQUESTED INFORMATION, PLEASE
 SUBMIT ALL OF THE REQUESTED INFORMATION AT THE SAME
 TIME UNDER THIS REVISION NUMBER. THIS WAY IT WILL COST
 LESS AND BE LESS CONFUSING THAN SUBMITTING THE ITEMS
 SEPARATELY.
  
 ITEMS PREVIOUSLY REQUESTED
  
 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS FOR
 THE THE NEW A/C UNITS AS REQUIRED BY FBCR M1401.3.
 2) SUBMIT AHRI CERTIFICATIONS FOR THE NEW HEATING AND
 COOLING EQUIPMENT. FBC ENERGY CONSERVATION SECTION
 402.1.2.4.
 3) REVISE THE SIZE OF THE THROUGH THE WALL TRANSFER
 GRILL AT THE GUEST BEDROOM TO COMPLY WITH FBCR M1602.4
 FOR BALANCED RETURN AIR.
 TRANSFER GRILLS SHALL USE 50 SQUARE INCHES OF GRILL
 AREA TO 100 CFMS OF SUPPLY AIR.
 4) PROVIDE TWO SETS OF AN EQUIPMENT ANCHORING DETAIL
 FOR THE MECHANICAL EQUIPMENT THAT IS EXPOSED TO WIND
 LOADS. FBCR M1307.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]


Account Summary | Usage Policy | Privacy Policy