Plan Review Details - Permit 14090944
Plan Review Stops For Permit 14090944
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-12-06 Cont ID  
Sent By shill Date 2014-12-06 Time 12:47 Rev Time 0.00
Received By shill Date 2014-12-06 Time 12:47 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-12-04 Cont ID  
Sent By shill Date 2014-12-04 Time 17:03 Rev Time 0.00
Received By shill Date 2014-12-04 Time 17:00 Sent To E
Notes
2014-12-04 17:23:53****CORRECTIONS****
 ****COURTESY REVIEW - CONTRACTOR REQUESTED THAT PERMIT
 BE ISSUED, NO PERMIT REQUIRED FOR KITCHEN (STATED THAT
 KITCHEN TO BE REPLACED SAME CONFIGURATION, NEW CABINETS
 AND APPLICANCES ONLY)***
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. PLANS PROVIDED ARE NOT CONSISTENT WITH THE SCOPE OF
 THE APPLICATION, FBC 107.2.1.
  
 APPLICATION IS TO "ENCLOSE DEN AREA WITH A SET OF
 FRENCH DOORS" BUT PLANS ALSO SHOW A KITCHEN RENOVATION,
 NEW CABINETS, ELECTRICAL WORK. EITHER REVISE PLAN TO
 INCLUDE ONLY WORK PROPOSED OR REVISE VALUE AND
 DESCRIPTION TO INCLUDE ALL WORK SHOWN ON THE PLANS.
  
 NEW COMMENT PURSUANT TO CONTRACTOR'S EMAIL 12/4:
  
 2. AS KITCHEN IS BEING CONFIGURED AND THE ELECTRICAL
 WORK AFFECTS THE KITCHEN CABINETS, AS DISCUSSED WITH
 THE ARCHITECT, PROVIDE PLANS WHICH INCLUDE SCOPE OF
 WORK UNDER THIS PERMIT - ACCORDING TO CONTRACTOR, THE
 DEN. AS KITCHEN IS BEING DONE SEPARATELY BUT YOUR
 ELECTRICAL SUBCONTRACTOR IS DOING THE ELECTRICAL, THE
 ENTIRE KITCHEN (INCLUDING ELECTRICAL WORK IN THE
 KITCHEN) SHOULD BE ON A SEPARATE PERMIT WITH SEPARATE
 PLANS AS CONTRACTOR STATES THAT "OTHERS" ARE DOING THIS
 SCOPE OF WORK.
  
 MY UNDERSTANDING IS THAT THE KITCHEN CABINET INSTALLER
 HAS STATED THAT THE CABINET INSTALLATION IS "LIKE
 MAKING FURNITURE" AND DOES NOT NEED A PERMIT. A PERMIT
 AND CONTRACTING LICENSE ARE REQUIRED FOR THIS
 INSTALLATION. SEE THE FOLLOWING WEBSITE:
  
 HTTP://WWW.PBCGOV.COM/PZB/CONTRACTORS/
  
 AND SEE "STANDARDS FOR CERTIFIED CATEGORIES"
  
 HTTP://WWW.PBCGOV.COM/PZB/CONTRACTORS/STANDARDS.PDF
  
 INSTALLATION OF CABINETRY IS REGULATED BY PALM BEACH
 COUNTY. THEREFORE, A CONTRACTOR LICENSE IS REQUIRED TO
 INSTALL CABINETS. A PERMIT IS ALSO REQUIRED.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-12-01 Cont ID  
Sent By shill Date 2014-12-01 Time 09:35 Rev Time 0.00
Received By shill Date 2014-12-01 Time 09:35 Sent To E
Notes
2014-12-01 09:37:18****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLANS PROVIDED ARE NOT CONSISTENT WITH THE SCOPE OF
 THE APPLICATION, FBC 107.2.1.
  
 APPLICATION IS TO "ENCLOSE DEN AREA WITH A SET OF
 FRENCH DOORS" BUT PLANS ALSO SHOW A KITCHEN RENOVATION,
 NEW CABINETS, ELECTRICAL WORK. EITHER REVISE PLAN TO
 INCLUDE ONLY WORK PROPOSED OR REVISE VALUE AND
 DESCRIPTION TO INCLUDE ALL WORK SHOWN ON THE PLANS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-14 Cont ID  
Sent By shill Date 2014-10-14 Time 17:51 Rev Time 0.00
Received By shill Date 2014-10-14 Time 17:51 Sent To  
Notes
2014-10-14 17:53:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 107, PROVIDE PLANS WHICH ARE A MINIMUM OF 1/8"
 SCALE AND LEGIBLE. PLANS TO SHOW SCOPE, LOCATION, OF
 PROPOSED WORK.
  
 PLANS SUBMITTED ARE TOO SMALL TO READ; UNABLE TO
 PROVIDE A COMPLETE CHECKLIST AT THIS TIME.
  
 2. FBC 107, PROVIDE SPECS FOR PROPOSED FRENCH DOOR.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-05 Cont ID  
Sent By dhayes Date 2014-12-05 Time 10:55 Rev Time 0.00
Received By dhayes Date 2014-12-05 Time 10:55 Sent To  
Notes
2014-12-05 10:59:5412/5/2014
 PROJECT: TWO CITY CONDO #816
 PERMIT#: 14090944
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION.
  
 1) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, THE INDIVIDUAL DWELLING UNIT SHALL BE
 EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW
 DWELLINGS. VERIFY OR PROVIDE INTERCONNECTED SMOKE
 DETECTORS AS NEEDED. FBC-R 314 AND 315.
  
 2) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-11-13 Cont ID  
Sent By shill Date 2014-12-01 Time 09:41 Rev Time 0.00
Received By pleduc Date 2014-11-13 Time 08:06 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-10-16 Cont ID  
Sent By pleduc Date 2014-10-16 Time   Rev Time 0.00
Received By pleduc Date 2014-10-16 Time 11:26 Sent To PC
Notes
2014-10-16 11:33:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PLANS WERE SMALL AND MANY OF THE DIMENSIONS WERE
 UNREADALBE. MUCH OF THE WORDING WAS A IN SMALL FONT AND
 UNREADABLE.
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE FOLLOWING MUST BE INDICATED ON THE SUBMITTAL.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-12-08 Cont ID  
Sent By pleduc Date 2014-12-08 Time   Rev Time 0.00
Received By pleduc Date 2014-12-05 Time 12:56 Sent To  
Notes
2014-12-06 12:58:01THE SET STAMPED "CONTRACTOR" IS THE ONLY SIGNED AND
 SEALED ORIGINAL. SENDING PLANS BACK TO ELECTRICAL TO
 CONFIRM THAT ALL REDLINES AND NOTES ARE ON THE OTHER
 SET WHICH WAS PREVIOUSLY STAMPED "FILE SET" (AND IS NOT
 SIGNED AND SEALED).
  
 ROUTED TO DAH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-05 Cont ID  
Sent By jwitmer Date 2014-12-05 Time 11:00 Rev Time  
Received By dhayes Date 2014-11-10 Time 16:07 Sent To  
Notes
2014-12-01 09:42:1712/1 TO ELEC
  
2014-11-19 08:29:30TO MISC 2 BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-16 Cont ID  
Sent By pleduc Date 2014-10-16 Time 11:28 Rev Time 0.00
Received By pleduc Date 2014-09-25 Time 07:43 Sent To  
Notes
2014-10-14 17:53:57TO FIRE
  
2014-09-26 07:43:32SENT TO MISC 1 BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2014-11-19 Cont ID  
Sent By aaponte Date 2014-11-19 Time 08:29 Rev Time 0.00
Received By aaponte Date 2014-11-19 Time 08:29 Sent To  
Notes
***NONE***