Plan Review Details - Permit 14090789
Plan Review Stops For Permit 14090789
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-10-02 Cont ID  
Sent By sciard Date 2014-10-02 Time 12:28 Rev Time 0.00
Received By sciard Date 2014-10-02 Time 12:28 Sent To  
Notes
2014-10-02 12:31:2610/02/2014. SENT TO PLUMBING.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-27 Cont ID  
Sent By dhayes Date 2014-09-27 Time 15:13 Rev Time 0.00
Received By dhayes Date 2014-09-27 Time 15:04 Sent To  
Notes
2014-09-27 15:17:489/27/2014
 PROJECT: LAURA BUDD GENERATOR
 PERMIT#: 14090789
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION:
  
 1) PROVIDE A SITE PLAN INDICATING THE LOCATION OF
 ELECTRICAL SERVICE EQUIPMENT IN RELATION TO THE
 PROPOSED LLOCATION OF THE GENERATOR.
  
 2) PROVIDE A SITE PLAN WITH A DETAIL INDICATING THE
 LOCATION OF ANY WINDOWS, DOOR AND VENTS LEADING INTO OR
 OUT OF THE RESIDENCE IN RELATION TO THE PROPOSED
 LOCATION OF THE GENERATOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-10-02 Cont ID  
Sent By tklarge Date 2014-10-02 Time 13:44 Rev Time 0.00
Received By tklarge Date 2014-10-02 Time 13:44 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-09-27 Cont ID  
Sent By tklarge Date 2014-09-27 Time 07:28 Rev Time 0.00
Received By tklarge Date 2014-09-27 Time 07:28 Sent To  
Notes
2014-09-27 07:45:181) SECTION 616.1 OF THE 2010 FUEL GAS CODE MANDATES
 THAT THE GENERATOR SHALL BE INSTALLED IN ACCORDANCE
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AND
 NFPA 37. NFPA 37 REQUIRES THE GENERATOR TO BE A MIN. OF
 5 FT. FROM OPENINGS IN WALLS AND 5 FT. FROM STRUCTURES
 HAVING COMBUSTIBLE WALLS UNLESS THE WALL IS FIRE RATED
 WITH A RATING OF AT LEAST ONE HOUR OR THE WEATHERPROOF
 ENCLOSURE IS CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS,
 AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE MATERIALS OUTSIDE
 THE ENCLOSURE. THE GENERATOR IS SHOWN 18 INCHES FROM
 THE BUILDING WALLS.
 2) SHOW THAT THE GENERATOR IS A MIN. 5 FT. AWAY FROM
 ALL BUILDING OPENINGS.
 3) SUBMIT 2 COPIES OF THE MANUF. INSTALLATION
 INSTRUCTIONS FOR THE GENERATOR.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-02 Cont ID  
Sent By tklarge Date 2014-10-02 Time 13:45 Rev Time 0.00
Received By tklarge Date 2014-09-30 Time 14:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-27 Cont ID  
Sent By dhayes Date 2014-09-27 Time 15:18 Rev Time 0.00
Received By dhayes Date 2014-09-22 Time 17:15 Sent To  
Notes
2014-09-22 17:15:23SENT TO ZONNG SHELF FOR REVIEW. JG.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2014-09-27 Cont ID  
Sent By dhayes Date 2014-09-27 Time 14:53 Rev Time 0.00
Received By dhayes Date 2014-09-27 Time 14:53 Sent To  
Notes
2014-09-27 15:03:52REVIEWED FOR FLOOD ZONE. THIS PROPERTY IS NOT IN A
 FLOOD ZONE BY VERTUE OF THE FLOOD ZONE X500 THE
 PROPERTY RESIDES IN.

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-23 Cont ID  
Sent By sgraham Date 2014-09-23 Time 08:34 Rev Time 0.00
Received By sgraham Date 2014-09-23 Time 08:34 Sent To E
Notes
***NONE***