Plan Review Details - Permit 14090746
Plan Review Stops For Permit 14090746
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2014-09-25 Cont ID  
Sent By JWITMER Date 2014-09-25 Time 15:09 Rev Time 0.00
Received By spalmer Date 2014-09-25 Time 15:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2014-09-23 Cont ID  
Sent By dhayes Date 2014-09-23 Time   Rev Time 0.00
Received By dhayes Date 2014-09-23 Time 09:00 Sent To  
Notes
2014-09-23 09:17:54B12
  
  
2014-09-23 09:17:23DATE: 9/23/2014
 PROJECT: DXL
 PERMIT#: 14070136
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL REVISION PLAN REVIEW
 ACTION: PROVISO
  
 1) RISER ON REVISION INDICATES A 150AMP MAIN BREAKER IN
 PANEL B ON THE SECONDARY SIDE OF THE NEW 75KVA
 TRANSFORMER. THE PANEL SCHEDULE INDICATE S A 225AMP MLO
 PANEL IN PANEL B. REVISE PLANS FOR CLARIFICATION.
  
 2) NEC 210.4(B) EACH MULTIWIRE BRANCH CIRCUIT SHALL BE
 PROVIDED WITH A MEANS THAT WILL SIMULTANEOUSLY
 DISCONNECT ALL UNGROUNDED CONDUCTORS AT THE POINT WHERE
 THE BRANCH CIRCUIT ORIGINATES.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2014-09-25 Time   Rev Time 0.00
Received By jgomez Date 2014-09-22 Time 14:28 Sent To  
Notes
2014-09-22 14:29:06REVISION SENT TO B12 SHELF FOR REVIEW. JG.

Review Stop Z ZONING
Rev No 1 Status N Date 2014-09-25 Cont ID  
Sent By spalmer Date 2014-09-25 Time 15:10 Rev Time 0.00
Received By spalmer Date 2014-09-25 Time 15:10 Sent To  
Notes
2014-09-25 15:11:13USED A COMMERCIAL REVISION NUMBER THAT WE DIDN'T NEED
 AND USED IT AS A MECHANICAL CHANGEOUT