2014-10-27 07:14:27 | 10/27/2014 |
| PROJECT: THE ALCHEMIST SIGN |
| PERMIT#: 14090734 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: PASS WITH EXCEPTION. |
| |
| 1) PLEASE PROVIDE THE FOLLOWING FOR VERIFICATION BY |
| ELECTRICAL INSPECTOR IN THE FIELD. |
| A) FBC-E 505.2.4 |
| ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL |
| HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN |
| NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME |
| CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES |
| SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS |
| OF POWER FOR A MINIMUM OF 10 HOURS. |
| B) NEC 600.3 |
| ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING ? |
| FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND |
| INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS |
| OTHERWISE APPROVED BY SPECIAL PERMISSION. |
| C) NEC 110.3(B) |
| LISTED OR LABELED EQUIPMENT SHALL BE INSTALLED AND USED |
| IN ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE |
| LISTING OR LABELING. |
| D) NEC 600.5 |
| EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY |
| A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT |
| SUPPLIES NO OTHER LOAD. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |