Plan Review Details - Permit 14090715
Plan Review Stops For Permit 14090715
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-05-04 Cont ID  
Sent By jwitmer Date 2015-05-04 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2015-05-02 Time 10:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-02 Cont ID  
Sent By jwitmer Date 2014-10-02 Time 14:13 Rev Time 0.00
Received By jwitmer Date 2014-10-02 Time 13:39 Sent To  
Notes
2014-10-02 14:13:18BUILDING PLAN REVIEW
 PERMIT:14090715
 ADD:325 EUCALYPTUS STREET
 CONT: KAST
 TEL: (561) 689-2910
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. OCT. 02/2014
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE TEMPORARY
 CONSTRUCTION TRAILERS ARE TEMPORARY, THAT MEANS 180
 DAYS OR LESS BY DEFINITON. PLEASE PROVIDE THE DATE THEY
 WILL BE INSTALLED AND THE DATE THEY WILL BE REMOVED.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE,
 CHAPTER 1, ADMINISTRATION, 2010 108.1 GENERAL. THE
 BUILDING OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR
 TEMPORARY STRUCTURES AND TEMPORARY USES. SUCH PERMITS
 SHALL BE LIMITED AS TO TIME OF SERVICE, BUT SHALL NOT
 BE PERMITTED FOR MORE THAN 6MONTHS. THE BUILDING
 OFFICIAL IS AUTHORIZED TO GRANT EXTENSIONS FOR
 DEMONSTRATED CAUSE.
  
 2) SHEET 1 OF 4 FROM THE STATE APPROVED PLANS INDICATE
 IN NOTE # 2 THEY WILL NEED TO PROVIDE STAIR, RAMP,
 LANDINGS, DECKS AND GAURDRAIL DETAILS, THEY ARE NOT
 INCLUDED IN THE STATE APPROVED PLANS.
 2A) 1009.6 STAIRWAY CONSTRUCTION. ALL STAIRWAYS SHALL
 BE BUILT OF MATERIALS CONSISTENT WITH THE TYPES
 PERMITTED FOR THE TYPE OF CONSTRUCTION OF THE BUILDING,
 EXCEPT THAT WOOD HANDRAILS SHALL BE PERMITTED FOR ALL
 TYPES OF CONSTRUCTION.
 2B) STAIR, RAMPS, LANDINGS & DECKS ARE TO BE DESIGN TO
 TABLE 1607 LIVE LOADS.
 2C) 1010.2 SLOPE. RAMPS USED AS PART OF A MEANS OF
 EGRESS SHALL HAVE A RUNNING SLOPE NOT STEEPER THAN ONE
 UNIT VERTICAL IN 12 UNITS HORIZONTAL (8.333-PERCENT
 SLOPE). THE SLOPE OF OTHER PEDESTRIAN RAMPS SHALL NOT
 BE STEEPER THAN ONE UNIT VERTICAL IN EIGHT UNITS
 HORIZONTAL (12.5-PERCENT SLOPE). ACC CODE 405,
 HANDRAILS 1012 & GUARDRAILS 1013.
  
 3) PROVIDE A SITE PLAN AND SHOW THE ACCESSIBLE ROUTE TO
 THE MANUFACTURERD BUILDINGS FROM THE ACCESSIBLE PARKINS
 SPOT AND ACCESS AISLE.
 2010 FBC- ACCESS 502.1.
  
 4) SHEET 1 OF 4 FROM THE STATE APPROVED PLANS INDICATE
 IN NOTE # 14 SITE INSTALLED ITEM GUTTERS. 1503.7
 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 5) SHEET 1 OF 4 FROM THE STATE APPROVED PLANS INDICATE
 IN NOTE # 16 STORM SHUTTERS. 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)((E) SHUTTERS.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2014-09-23 Cont ID  
Sent By rlecky Date 2014-09-23 Time 13:25 Rev Time 0.00
Received By rlecky Date 2014-09-23 Time 13:20 Sent To  
Notes
2014-09-23 13:27:28SEE PERMIT # 14061214 FOR TEMPORARY POWER

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-09-24 Cont ID  
Sent By wjolin Date 2014-09-24 Time 11:02 Rev Time 0.00
Received By wjolin Date 2014-09-24 Time 10:10 Sent To  
Notes
2014-09-24 10:15:47325 EUCALPYTUS STREET
 PERMIT #14090715
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ***NEED A #131 FINAL FIRE INSPECTION***
  
 SUBMIT INFORMATION FOR STAIRS, HANDRAILS, GUARDRAILS
 AND WOOD DECKING CONNECTING ONE TRAILER TO THE OTHER.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT
 THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE,
 ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN
 GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER
 SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR
 OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT
 OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH
 DIAMETER SPHERE.
  
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR.
 HANDRAILS SHALL BE LOCATED NOT LESS THAN 34-INCHES AND
 NOT MORE THAN 38-INCHES ABOVE THE SURFACE OF THE TREAD,
 MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE
 LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE
 RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES.
  
 STAIR RISERS SHALL BE BETWEEN 4 INCHES AND 7 INCHES IN
 HEIGHT. STAIRS SHALL BE SLIP RESISTANT AND HAVE A
 MINIMUM TREAD DEPTH OF 11 INCHES AND PREVENT THE
 ACCUMULATION OF WATER.
  
 PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING
 MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE RELEASING OPERATION. THE RELEASING
 MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
 THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING
 OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO
 OPERATE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-04 Cont ID  
Sent By jwitmer Date 2015-05-04 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2015-04-30 Time 17:48 Sent To  
Notes
2015-04-30 17:48:37TO JW DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-02 Cont ID  
Sent By jwitmer Date 2014-10-02 Time 14:13 Rev Time 0.00
Received By jwitmer Date 2014-09-20 Time 08:36 Sent To  
Notes
2014-09-20 08:36:36INCOMING SENT TO C02 . JW

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-29 Cont ID  
Sent By aaponte Date 2014-09-29 Time 13:49 Rev Time 0.00
Received By aaponte Date 2014-09-29 Time 13:49 Sent To  
Notes
2014-09-26 16:01:439/26/14