Plan Review Details - Permit 14090658
Plan Review Stops For Permit 14090658
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-04-16 Cont ID  
Sent By cranford Date 2015-04-15 Time 07:58 Rev Time 0.00
Received By shill Date 2015-04-16 Time 07:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-11 Cont ID  
Sent By shill Date 2014-10-11 Time 14:25 Rev Time 0.00
Received By shill Date 2014-10-11 Time 14:25 Sent To E
Notes
2014-10-11 14:27:13****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. REVISE PLAN TO PROVIDE THE FOLLOWING INFORMATION:
  
 TOTAL NUMBER OF PARKING SPACES
 NUMBER OF ACCESSIBLE SPACES
 LOCATION OF ACCESSIBLE ENTRANCES
 ACCESSIBLE ROUTE FROM ACCESSIBLE SPACE TO ACCESSIBLE
 ENTRANCE
  
 SEE FBC 2010 ACCESSIBLITY 202.3 (ALTERATIONS), 208.2
 (PARKING SPACES), 502 (PARKING SPACES), 206 (ACCESSIBLE
 ROUTE).
  
 YOU MAY FIND THE FOLLOWING DOCUMENT USEFUL,
 PARTICULARLY THE INTRODUCTION: "WHEN A BUSINESS
 RESTRIPES A PARKING LOT, IT MUST PROVIDE ACCESSIBLE
 PARKING SPACES AS REQUIRED BY THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN."
  
 HTTP://WWW.ADA.GOV/RESTRIPE.HTM
  
 2. FBC 2010 ACCESSIBILITY ADVISORY 502.3, WHERE THE
 ACCESSIBLE ROUTE MUST CROSS VEHICULAR TRAFFIC LANES,
 MARKED CROSSINGS ENHANCE PEDESTRIAN SAFETY; PLEASE
 INDICATE LOCATION ON PLAN.
  
 3. TWO COMPLETE SETS OF PLANS REQUIRED FOR PERMIT
 ISSUANCE.
  
 4. DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS481.
  
 5. THE PRINTED NAME AND LICENSE NUMBER OF THE
 INDIVIDUAL SIGNING AND SEALING THE PLAN IS TO BE
 INCLUDED IN THE TITLE BLOCK, FS481.
  
 6. SCOPE ON APPLICATION INCLUDES SOLAR PAY STATIONS,
 BUT NO INFORMATION PROVIDED FOR PROPOSED INSTALLATION
 (ELECTRICAL, STRUCTURAL) FBC 107.
  
 7. VALUE IS TO INCLUDE THE VALUE OF ALL LABOR,
 MATERIALS, OVERHEAD, PROFIT, ARCHITECTURE, FBC 109.
 VALUE IS TOO LOW, PLEASE REVISE TO BE A REASONABLE
 VALUE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-04-13 Cont ID  
Sent By shill Date 2015-04-13 Time 10:38 Rev Time 0.00
Received By dhayes Date 2015-04-13 Time 08:43 Sent To B
Notes
2015-04-13 10:38:404/13/2015
 PROJECT: DIXIE/MANGO PARKING LOT UPGRADES
 PERMIT#: 14090658
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) PROVIDE MANUFACTURER PRODUCT SPECIFICATIONS
 INDICATING THE SOLAR PAY STATIONS ARE LISTED AND LABLED
 BY A NATIONALLY RECOGNIZED TESTING LAB. THE "CE" MARK
 IS NOT RECOGNIZED IN THE US. SEE THE NEC 690.4(D), NEC
 110.3(B)
  
 2) THE MANUFACTURER'S DOCUMENTATION SHALL ALSO INCLUDE
 THE DETAILS REQUIRED FOR THE INSTALLATION INDICATING
 COMPLIANCE WITH THE NEC ARTICLE 690
  
 3) VERIFY VALUATION OF IMPROVEMENTS INCLUDING ALL
 LABOR, MATERIALS, EQUIPMENT AND SUB-CONTRACTS.THE
 STATED VALUE OF THE PROJECT IS NOT REALISTIC. PROVIDE
 SUPPORTING DOCUMENTATION OF IT'S VALIDITY OR THE ALUE
 WILL BE ALTERRED BY THE BUILDING OFFICIAL. FBC WPB
 AMENDMENTS. SECTION 109.3.
  
 4) IF THE DESIGN CAN BE APPROVED BY MEETING THE ABOVE
 NOTED DEFICIENCIES AN ELECTRICAL APPLICATION FROM A
 REGISTERED ELECTRICAL CONTRACTOR WILL BE REQUIRED TO
 VERIFY THE INSTALLATION MEETS OR EXCEEDS THE MINIMUM
 CRITERIA NOTED ABOVE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-18 Cont ID  
Sent By dhayes Date 2014-10-18 Time 13:30 Rev Time 0.00
Received By dhayes Date 2014-10-18 Time 13:30 Sent To  
Notes
2014-10-18 13:44:5910/18/2014
 PROJECT: DIXIE/MANGO PARKING LOT UPGRADES
 PERMIT#: 14090658
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE MANUFACTURER PRODUCT SPECIFICATIONS
 INDICATING POWER SOURCE AS SOLAR ONLY AND THAT IT IS
 LISTED AND LABELED.
  
 2) VERIFY VALUATION OF IMPROVEMENTS INCLUDING ALL
 LABOR, MATERIALS, EQUIPMENT AND SUB-CONTRACTS. FBC WPB
 AMENDMENTS. SECTION 109.3
  
 3) TWO COPIES OF ALL PLANS AND SPECIFICATIONS ARE
 REQUIRED FOR SUBMITTAL WITH AN APPLICATION FOR PERMIT.
 ONCE REVIEWED AND READY FOR ISSUANCE, ONE SET TO BE
 RETAINED BY THE BUILDING OFFICIAL FOR THE PURPOSE OF
 RECORD KEEPING AND THE OTHER TO BE RETURNED TO THE
 APPLICANT UPON ISSUANCE OF THE PERMIT. WPB AMENDMENTS
 TO THE FBC 107.3.1
  
 4) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-04-15 Cont ID  
Sent By cranford Date 2015-04-09 Time 12:21 Rev Time 0.00
Received By cranford Date 2015-04-09 Time 10:54 Sent To B
Notes
2015-04-09 11:20:452ND REVIEW
  
 BOTH THE EXISTING (UNPERMITTED) AND PROPOSED SURFACE
 PARKING LOT CONFIGURATION ARE IN DIMENSIONAL
 NONCONFORMITY WITH THE DISTANCE OF THE PARKING LOT
 ENTRANCE TO THE CORNER (SECTION 94-313 OF THE CODE OF
 ORDINANCES), MAXIMUM PARKING ENTRANCE WIDTH OF 25 FT
 AND MINIMUM CAR QUEUING LENGTH OF 20 FT [SECTION
 94-111(4)].
  
 PLANNING DEPT. HAS AGREED TO USING RAILROAD TIES IN
 LIEU OF CONCRETE CURBING TO PROTECT THE LANDSCAPING IN
 THE SOUTHERN ISLAND.
  
 PLANNING DEPT. ALSO AGREED TO THE USE OF PLASTIC/RUBBER
 WHEEL STOPS WITHIN THE PRIVATE PARKING LOT.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 ENGINEERING & PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2014-10-01 Cont ID  
Sent By cranford Date 2014-10-01 Time 14:07 Rev Time 0.00
Received By cranford Date 2014-10-01 Time 11:57 Sent To B
Notes
2014-10-01 12:55:181. THE SUBMITTED DESIGN PLANS WERE NOT SIGNED OR SEALED
 BY A LICENSED PROFESSIONAL (ARCHITECT, CIVIL ENGINEER,
 AND/OR LANDSCAPE ARCHITECT). PLEASE SUBMIT SIGNED AND
 SEALED PLANS. (FAC 61G15-23.002, FS 481.221 AND
 481.321)
  
 2. PLEASE SUBMIT AN APPLICATION FOR A DEVELOPMENT
 PERMIT FROM THE ENGINEERING DEPARTMENT. ANY WORK WITHIN
 THE RIGHT-OF-WAY WILL ALSO REQUIRED A RIGHT-OF-WAY
 PERMIT. APPLICATION FORMS CAN BE FOUND AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
 (SECTIONS 2-421 AND 78-432, CODE OF ORDINANCES)
  
 3. THE SITE WAS PREVIOUSLY PAVED WITHOUT OBTAINING THE
 NECESSARY AUTHORIZATIONS FROM THE CITY. DEMONSTRATE
 THAT THE PROJECT, CONVERTING A VACANT LOT INTO A PAVED
 PARKING LOT, PROVIDES ADEQUATE STORMWATER MANAGEMENT,
 INCLUDING NOT MODIFYING THE VELOCITY OR VOLUME OF
 OFF-SITE STORMWATER DISCHARGE.. COMPLIANCE WITH CHAPTER
 40E-4 FAC WILL DEMONSTRATE COMPLIANCE WITH THIS
 PROVISION. [CODE OF ORDINANCES SECTIONS 90-201, 94-35(C
 )(11), 94-307, AND 94-580]
  
 4. THE NORTHERN KIOSK IS SHOWN WITHIN THE PROPOSED
 SWALE. HOW KIOSK BE ACCESSES BY CUSTOMERS OF THE
 PARKING FACILITY? DEMONSTRATE THAT THE KIOSK WILL NOT
 REDUCE THE CALCULATED DETENTION CAPACITY OF THE SWALE.
  
 5. DIMENSION THE "LANDSCAPE PAVERS" AREA AND INDICATE
 THE TYPE OF PAVER TO BE USED AND SUBGRADE REQUIREMENTS.
 THE PAVER BACK-UP AREA WILL NEED TO MEET THE STRIPING
 AND DIMENSIONAL REQUIREMENTS OF SECTION 94-111(C)(2) OF
 THE CODE OF ORDINANCES.
  
 6. DEMONSTRATE THAT THE PARKING LOT ENTRANCE MEETS THE
 REQUIREMENTS OF SECTION 94-313 OF THE CODE OF
 ORDINANCES, INCLUDING THE CORNER CLEAR DISTANCE.
  
 7. REVISE THE PARKING LOT ENTRANCE TO MEET CITY
 STANDARD DETAIL GC-7. THE DETAIL CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 8. THE FOLLOWING CONDITIONS OF THE HISTORICAL
 PRESERVATION BOARD APPROVAL WERE NOT MET BY THIS
 APPLICATION.
  
 - PROVIDE A STRIPING DETAIL ON THE PLANS THAT IS
 COMPLAINCE WITH CITY STANDARDS. (CITY OF WEST PALM
 BEACH CODE OF ORDINANCES, SECTION 94-485)
  
 - PROVIDE PROPER SIGNAGE AND STIPING AT THE SITE EXIT.
 (SECTION 86-73)
  
 - DEMONSTRATE ACCESS TO PAY KIOSKS IS INCOMPLIANCE WITH
 ADA REQUIREMENTS (PUBLIC OPEN SPACE DEFINITION, SECTION
 94-109)
  
 - INDICATE ON THE PLANS THAT THE "LANDSCAPE PAVERS"
 WILL BE A GRASS PERMEABLE PAVER
  
 - PROVIDE PROPER SIGNAGE FOR THE HANDICAP ACCESSIBLE
 PARKING SPACE.
  
 - REVISE THE SWALE DETAIL SO THAT THE TOP DIMENSION
 FITS INTO THE SPACE SHOWN ON THE AVAILABLE GREEN SPACE
 SHOWN ON PLANS.
  
 - SHOW THE SWALE CENTER LINE LOCATION ON THE PLANS AND
 INDICATE HOW THE SWALE WILL BE CONSTRUCTED WITHOUT
 DAMAGING THE EXISTING TREES.
  
 - EVAULATE THE GRADING ON THE SOUTHEAST CORNER OF THE
 SITE TO ENSURE THAT THE STORM RUNOFF WILL REACH THE
 PROPOSED SWALE.
  
 - VERIFY THAT THE PROPOSED LANDSCAPING WILL NOT
 INTERFERE WITH THE FUNCTION OF THE SWALE, WHICH IS TO
 STORE STORMWATER RUNOFF FOR WATER QUALITY TREATMENT
 THROUGH PERCOLATION AND ATTENUATE PEAK RUNOFF FROM THE
 DESIGN STORM.
  
 - PROVIDE DRAINAGE AND WATER QUALITY TRERATMENT
 CALCULATIONS SIGNED AND SEALED BY A PROFESSIONAL
 ENGINEER.
  
 - PROVIDE SPOT GRADES AT THE PROPERTY LINE TO VERIFY
 THAT THE SITE WILL PROVIDE WATER QUALITY TREATMENT
 PRIOR TO DISCHARGING OFF-SITE AND THAT THE RUNOFF WILL
 NOT DISCHARGE ONTO THE PROPERTY TO THE EAST.
  
 - REVISE THE PLAN DIMENSIONS TO INCLUDE THE FOUR FEET
 OF PAVEMENT REMOVAL. THE 16-FT STALL DEPTH DOES NOT
 APPEAR TO TAKE THIS INTO ACCOUNT
  
 - PROVIDE THE VERTICAL DATUM REFERENCE (NGVD 1929).
  
 - DIMENSION THE DRIVE AISLE AND CURB CUT WIDTHS. THEY
 SHOULD BE NO LESS THAN 24 FEET.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 ENGINEERING & PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-04-03 Cont ID  
Sent By dkittred Date 2015-04-03 Time 10:52 Rev Time 0.00
Received By dkittred Date 2015-04-03 Time 10:52 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2014-09-29 Cont ID  
Sent By dkittred Date 2014-09-29 Time 11:01 Rev Time 0.00
Received By dkittred Date 2014-09-19 Time 08:24 Sent To  
Notes
2014-09-29 11:03:409/29/14 - SEE ZONING COMMENTS/NOTES.
  
 APPLICANT OBTAINED CLASS B SPECIAL USE PERMIT (WITH
 CONDITIONS) FOR PARKING LOT AS A PRINCIPAL USE AT
 AUGUST 26, 2014 HPB MEETING. DK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-16 Cont ID  
Sent By shill Date 2015-04-16 Time 07:36 Rev Time 0.00
Received By shill Date 2015-03-31 Time 10:44 Sent To  
Notes
2015-04-01 10:45:44RE-SUBMITTAL SEN TO ZONING SHELF FOR DANIELLE KITTREDGE
 REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-18 Cont ID  
Sent By shill Date 2014-10-18 Time 13:45 Rev Time 0.00
Received By dhayes Date 2014-09-18 Time 08:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2015-04-10 Cont ID  
Sent By dkittred Date 2015-04-10 Time 15:30 Rev Time 0.00
Received By dkittred Date 2015-04-10 Time 15:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2015-04-10 Cont ID  
Sent By dkittred Date 2015-04-10 Time 08:52 Rev Time 0.00
Received By dkittred Date 2015-04-10 Time 08:20 Sent To  
Notes
2015-04-10 08:52:09PLANNING AND ZONING COMMENTS: ***FAILED***
  
 4/10/15 (REVIEW FROM 4/3/15 UPDATED)
  
 THE FOLLOWING ITEMS WERE MISSING FROM THE PLAN:
  
 1. CURBING DETAIL.
 2. WHEEL STOP DETAIL.
 3. STOP BAR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-04-03 Cont ID  
Sent By dkittred Date 2015-04-03 Time 10:52 Rev Time 0.00
Received By dkittred Date 2015-04-02 Time 16:25 Sent To ENG
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-09-29 Cont ID  
Sent By dkittred Date 2014-09-29 Time 11:38 Rev Time 0.00
Received By dkittred Date 2014-09-19 Time 08:24 Sent To ENG
Notes
2014-09-29 11:38:569/29/14 - SENT TO FRONT COUNTER TO MATCH WITH
 ORIGINALLY APPLICATION. DK
  
2014-09-29 11:38:11PLANNING AND ZONING COMMENTS: ***FAILED***
  
 9/29/14
  
 1. PROPER STOP SIGNAGE (STOP SIGN AND STOP BAR) IS
 REQUIRED FOR EXITING THE SITE. PLEASE REVISE PLANS.
  
 2. WILL THE PERMEABLE LANDSCAPE PAVERS BE INSTALLED AS
 PART OF THE RESTRIPING TO CREATE THE BACK-UP AREA? IF
 SO, PLEASE INDICATE THAT IN THE SCOPE OF WORK.
 OTHERWISE, WHEN WILL THE PAVERS BE INSTALLED?
  
 3. DIMENSIONS ON THE NORTH SIDE OF THE PROPERTY HAS
 OMITTED THE 4 FOOT SWALE AREA SO THE 41 FOOT BACKING UP
 DEPTH IS SHOWN LARGER THAN IT REALLY CAN BE.
  
 4. IT IS UNCLEAR WHAT THE DEPTH OF THE PARKING SPACES
 WILL BE. DEPTH OF ALL PARKING SPACES DIMENSION TO 18
 FEET IN LENGTH, HOWEVER, DIMENSIONS ON THE NORTH SIDE
 OF THE PROPERTY INDICATED THE SMALL PARKING SPACES WILL
 ALL BE 16 FEET IN DEPTH. PLEASE KEEP IN MIND THAT THE
 HANDICAP PARKING SPACE IS REQUIRED TO BE A MINIMUM OF
 18 FEET IN LENGTH. PLEASE REVIEW ALL DIMENSIONS
 PROVIDED ON THE PLAN AND REVISE OR CLARIFY ACCORDINGLY.
  
  
 ADDITIONAL COMMENTS:
  
 5. STANDARD STRIPING DETAIL HAS BEEN ATTACHED TO THE
 PLANS TO SHOW DOUBLE STRIP CONNECTED AT THE BOTTOMS AS
 WELL AS STRIPING WIDTH, STRIPING COLORS, AND REQUIRED
 SIGNAGE.
  
 6. IN CONJUNCTION WITH THE CLASS B SPECIAL USE PERMIT,
 ENGINEERING PLANS ADDRESSING STORMWATER ISSUES NEED TO
 BE SUBMITTED AND APPROVED PRIOR TO OR CONCURRENTLY WITH
 THE APPROVAL OF THE RESTRIPING FOR THE PARKING LOT TO
 MAKE SURE REVIEW OF THE ENGINEERING PLANS FOR
 STORMWATER DOES NOT AFFECT THE FINAL DESIGN OF THE
 PARKING LOT STRIPING.
  
 7. SEPARATE PERMIT WILL BE REQUIRED, AS DETERMINED BY
 THE BUILDING DIVISION, FOR INSTALLATION OF THE PAY
 METER KIOSKS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  