2014-09-21 12:30:08 | TO TL'S DESK |
| |
| |
| |
2014-09-21 12:27:01 | DATE: 9/21/2014 |
| PROJECT: 5335 N. MILITARY TR. |
| PERMIT#: 14060910 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE REVISED PLANS TO INDICATE A FLOOR PLAN THAT |
| MATCHES THE RISER DIAGRAM. THERE ARE 5 ELECTRICAL |
| PANELS INDICATED ON THE FLOOR PLAN SUBMITTED AND ONLY 2 |
| PANELS ON THE RISER SUBMITTED. LABEL AND IDENTIFY THE |
| MAINS AT THE SERVICE RISER AND ALSO AT THE |
| CORRESPONDING PANEL ON THE FLOOR PLAN. WPB AMENDMENTS |
| TO FBC 1107.3.2 |
| |
| 2) REVISE RISER DIGRAM TO INDICATE A GROUNDING |
| ELECTRODE SYSTEM DETAIL THAT INCLUDES THE MAIN BONDING |
| JUMPER ATTACHMENT DETAIL AT THE NEUTRAL TERMINAL. THE |
| RISER SHOWN ON THE PLAN SUBMITTED INCLUDES A # 6 GROUND |
| WIRE IN THE NIPPLE WITH GROUNDED NEUTRAL CONDUCTOR. |
| PLEASE REMOVE OR CLAIRIFY. WPB AMENDMENTS TO FBC |
| 1107.3.2 |
| |
| 3) INCLUDE THE LOCATION OF THE ELECTRICAL SERVICE AND |
| MAINS ON THE PLAN. IF A SITE PLAN IS REQUIRED TO |
| INDICATE THE LOCATION OF THE ELECTRCAL SERVICE PLEASE |
| PROVIDE TO INDICATE THE LOACTION OF THE ELECTRICAL |
| SERVICE IN RELATION TO THE SERVICE. WPB AMENDMENTS TO |
| FBC 1107.3.2 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |