Plan Review Details - Permit 14090554
Plan Review Stops For Permit 14090554
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2014-10-02 Cont ID  
Sent By tklarge Date 2014-10-02 Time 14:59 Rev Time 0.00
Received By tklarge Date 2014-10-02 Time 14:59 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2014-10-02 Cont ID  
Sent By tklarge Date 2014-09-27 Time 05:55 Rev Time 0.00
Received By tklarge Date 2014-09-27 Time 05:55 Sent To  
Notes
2014-09-27 06:15:00WPB ADMIN. AMEND. TO 2010 FBC SEC. 107.2.1.
 1) THE REVISED DRAWING IS STILL VAGUE REGARDING THE
 SIZING AND TYPE OF PIPE BEING USED. IF YOU ARE USING
 THE LONGEST LENGTH METHOD I SUGGEST REFERRING TO SEC.
 402.4.1 OF THE 2010 FLORIDA FUEL GAS CODE AND ALSO THE
 DEFINITION OF "POINT OF DELIVERY."
 I CANNOT DO A PROPER REVIEW UNTIL THE FOLLOWING ISSUES
 ARE CLARIFIED:
 A) INDICATE THE TOTAL LENGTH OF THE PIPING FROM THE
 "POINT OF DELIVERY" TO THE MOST REMOTE OUTLET AND THE
 LOAD FOR THE SECTION.
 B) LABEL THE PIECES OF EQUIPMENT ON THE GAS RISER.
 C) YOU SUBMITTED A SIZING TABLE FOR PE PIPE YET THE GAS
 RISER SHOWS THE LETTER "G" WHICH I ASSUME TO BE IS
 GALVANIZED. CLEARLY INDICATE THE TYPE OF PIPE MATERIAL
 BEING INSTALLED.
 D) SUBMIT TWO COPIES OF THE APPROPRIATE SIZING TABLES
 AND HEATER SPEC. SHEETS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-09-20 Cont ID  
Sent By tklarge Date 2014-09-20 Time 04:49 Rev Time 0.00
Received By tklarge Date 2014-09-20 Time 04:49 Sent To  
Notes
2014-09-20 04:58:58WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 1) THE GAS PIPING FOR THE FIRE PIT IS NOT SHOWN ON THE
 GAS RISER. SHOW THE PIPNG FOR THE FIRE PIT & BTU LOAD
 ON THE DRAWING.
 2) SIZE ALL SECTIONS THE PIPING ON THE GAS RISER.
 3) SUBMIT A COPY OF THE APPLICABLE SIZING TABLE USED
 FOR THE GAS SYSTEM.
 4) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT. ALL EQUIPMENT SHALL BE LISTED AND
 LABELED PER THE 2010 FUEL GAS CODE SEC. 301.3.
 5) THERE ARE TWO LONGEST LENGTHS SHOWN ON THE PLANS. IT
 APPEARS THAT THE LONGEST LENGTH IS THE RUN TO THE
 WADING POOL HEATER. THIS LENGTH SHALL BE USED FOR THE
 SIZING OF THE ENTIRE SYSTEM PER THE 2010 FGC
 SEC.402.4.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-10-02 Cont ID  
Sent By tklarge Date 2014-10-02 Time 15:00 Rev Time 0.00
Received By tklarge Date 2014-10-02 Time 13:23 Sent To  
Notes
2014-10-02 13:23:57RE-SUBMITTAL SENT TO TIM LARGE'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-02 Cont ID  
Sent By jgomez Date 2014-09-27 Time 13:21 Rev Time 0.00
Received By jgomez Date 2014-09-26 Time 16:28 Sent To  
Notes
2014-10-02 13:22:08LAST REVIEW DONE 9/27/14. JG.
2014-09-26 16:28:44INCOMING SENT TO T. LARGE DESK .JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-20 Cont ID  
Sent By tklarge Date 2014-09-20 Time 05:00 Rev Time 0.00
Received By tklarge Date 2014-09-19 Time 06:54 Sent To  
Notes
2014-09-20 05:00:139/20/14 - DENIED/E-MAILED CONTRACTOR/PLACED IN SMALL "
 P".TKL
2014-09-16 14:32:32ROUTED TO PLUMBING LESS THAN $5000