Plan Review Details - Permit 14090549
Plan Review Stops For Permit 14090549
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-09-19 Cont ID  
Sent By jwitmer Date 2014-09-19 Time 09:55 Rev Time 0.00
Received By jwitmer Date 2014-09-19 Time 07:05 Sent To  
Notes
2014-09-19 07:46:36ROOFING PRODUCT APPROVALS:
 BORAL ROOFING BARCELONA 900 CONCRETE TILE
 NOA 12-0222.02
 #-M 2-COMPONENT FOAM ROOF TILE ADHESIVE AH-160
 NOA 12-02228.18
 BORAL ROOFING TILE SEAL
 NOA 12-1219.01

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-01-10 Cont ID  
Sent By dhayes Date 2015-01-10 Time 14:43 Rev Time 0.00
Received By dhayes Date 2015-01-10 Time 14:23 Sent To  
Notes
2015-01-10 14:43:46DATE: 01/10/15
 PROJECT: BUS SHELTER
 PERMIT#: 14090549
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) PROVIDE EQUIPMENT GROUND WITH BRANCH CIRCUIT
 CONDUCTORS NEC 250.119, 250.120, 250.122
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-12-01 Cont ID  
Sent By dhayes Date 2014-12-01 Time 13:13 Rev Time 0.00
Received By dhayes Date 2014-12-01 Time 13:13 Sent To  
Notes
2014-12-01 14:54:07DATE: 12/01/2014
 PROJECT: BUS SHELTER
 PERMIT#: 14090549
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING IT IS REQUIRED TO INSERT THE
 CORRECTED PAGES INTO THE DENIED SUBMITTAL PACKAGE, VOID
 THE PREVIOUSLY REVIEWED SHEETS AND LEAVE THEM FOR
 COMPARATIVE REVIEW. PLEASE INSERT REVISED SHEETS FOR
 NEXT RESUBMITTAL.
  
 2) CLARIFICATION IS REQUIRED BETWEEN THE "FLOOR PLAN"
 AND THE "ELECTRICAL PLAN" THE FLOOR PLAN INDICATES ONE
 LIGHT FIXTURE IN WHAT APPEARS TO BE THE MIDDLE OF THE
 FLOOR AND CALLS FOR CONTROL BY A TIME CLOCK. THE
 ELECTRICAL PLAN INDICATES TWO LIGHT FIXTURES IN WHAT
 APPEARS TO BE THE CEILING STRUCTURE AND TO BE CONTROLED
 BY A PHOTO CELL. PLEASE CLARIFY AND INDICATE THE
 LOCATION OF THE PHOTOCELL.
 B) PROVIDE A LIGHT FIXTURE SCHEDULE TO INDICATE THE
 TYPE AND APPROVED USE FOR THE PROPOSED LIGHT FIXTURES.
  
 3) PROVIDE A SITE PLAN INDICATING THE BUS SHELTER, THE
 LOCATION OF THE ELECTRICAL SERVICE AND THE ELECTRICAL
 PANEL RELATIVE TO THE LOCATION OF THE BUS SHELTER. THE
 ELECTRICAL PANEL ON THE RISER DIAGRAM IS INDICATED AS A
 NEMA 1 ENCLOSURE. PLEASE CLARIFY THE PANEL IS IN A NEMA
 1 LOCATION OR REVISE TO APPROVED TYPE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-16 Cont ID  
Sent By dhayes Date 2014-09-16 Time 16:37 Rev Time 0.00
Received By dhayes Date 2014-09-16 Time 16:37 Sent To  
Notes
2014-09-16 16:50:55DATE: 9/16/2014
 PROJECT: BUS SHELTER
 PERMIT#: 14090549
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE THE MINIMUM PLAN REVIEW CRITERIA, RISER
 DIAGRAM, PANEL SCHEDULE, LOAD CALCULATION.
  
 2) INDICATE HOW THE DESIGN IS PROPOSED TO COMPLY WITH
 THE FBC-E 505 LIGHTING FOR ALL EXTERIOR APPLICATIONS
 NOT EXEMPTED IN SECTION 505.1 SHALL HAVE AUTOMATIC
 CONTROLS CAPABLE OF TURNING OFF EXTERIOR LIGHTING WHEN
 SUFFICIENT DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING
 IS NOT REQUIRED DURING NIGHTTIME HOURS. LIGHTING NOT
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND
 A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2014-09-17 Cont ID  
Sent By cranford Date 2014-09-17 Time 15:26 Rev Time 0.00
Received By cranford Date 2014-09-17 Time 15:25 Sent To  
Notes
2014-09-17 15:26:15REVIEW NOT REQUIRED. LOCATION SHOWN ON PLANS APPROVED
 UNDER E14020004.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-01-10 Cont ID  
Sent By dhayes Date 2015-01-10 Time 14:43 Rev Time 0.00
Received By dhayes Date 2014-12-23 Time 16:38 Sent To  
Notes
2014-12-23 16:39:16SENT TO DAVID HAYES,S DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-01 Cont ID  
Sent By dhayes Date 2014-12-01 Time 14:54 Rev Time 0.00
Received By dhayes Date 2014-11-25 Time   Sent To  
Notes
2014-11-26 10:42:10INCOMING SENT TO D. HAYES'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-25 Cont ID  
Sent By skennedy Date 2014-09-25 Time 16:04 Rev Time 0.00
Received By skennedy Date 2014-09-16 Time 16:37 Sent To  
Notes
2014-09-16 16:53:41B11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-09-19 Cont ID  
Sent By jwitmer Date 2014-09-19 Time 09:55 Rev Time 0.00
Received By jwitmer Date 2014-09-19 Time 09:55 Sent To  
Notes
2014-09-19 09:56:15BUS STOP IMPACT FEES NOT REQUIRED. CALLED MICHELLE AT P
 B C.

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-25 Cont ID  
Sent By ajones Date 2014-09-25 Time 15:51 Rev Time 0.00
Received By ajones Date 2014-09-25 Time 15:51 Sent To  
Notes
***NONE***