Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-23 Cont ID  
Sent By pleduc Date 2014-09-29 Time 12:51 Rev Time 0.00
Received By dhayes Date 2014-09-23 Time 10:37 Sent To FIRE
Notes
2014-09-23 10:38:36DATE: 9/23/2014
 PROJECT: COURTNY LAKES
 PERMIT#: 14090532
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) THE INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE
 CONSIDERED A WET LOCATION. ALL CONDUCTORS WITHIN THE
 RACEWAY SHALL BE LISTED ACCORDINGLY. SUITABILITY FOR
 INSTALLATION AND USE IN CONFORMITY WITH THE PROVISIONS
 OF THIS CODE. NEC 110.3(B)
  
 2) A SEPARATE ELECTRICAL PERMIT APPLICATION SHALL BE
 SUBMITTED ACCOMPANIED BY SHOP DRAWINGS, EQUIPMENT
 SUBMITTALS, PRODUCT APPROVALS FOR ALL OF THE FOLLOWING:
 NETWORK, DATA/COM, FIRE ALARM, SECURITY, CCTV, AND
 AUDIO/ VIDEO WORK.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-16 Cont ID  
Sent By pleduc Date 2014-09-17 Time 15:39 Rev Time 0.00
Received By dhayes Date 2014-09-16 Time 15:19 Sent To FIRE
Notes
2014-09-16 15:25:38DATE: 9/16/2014
 PROJECT: COURTNEY LAKES
 PERMIT#: 14090532
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-09-29 Cont ID  
Sent By pleduc Date 2014-09-29 Time   Rev Time 0.00
Received By pleduc Date 2014-09-29 Time 12:44 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-09-17 Cont ID  
Sent By pleduc Date 2014-09-17 Time   Rev Time 0.00
Received By pleduc Date 2014-09-17 Time 15:26 Sent To PC
Notes
2014-09-17 15:39:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES (?MAG-LOCKS?)
  
 7.2.1.6.2 (NFPA 101) DOOR ASSEMBLIES IN THE MEANS OF
 EGRESS SHALL BE PERMITTED TO BE EQUIPPED WITH AN
 APPROVED ENTRANCE AND EGRESS ACCESS CONTROL SYSTEM,
 PROVIDED THAT ALL THE FOLLOWING CRITERIA ARE MET:
  
 (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOOR LEAVES
 THAT ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS
 UPON DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF
 POWER TO THE SENSOR.
  
 (2) LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOOR LEAVES SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS.
  
 (3) DOOR LEAVES SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED 40 IN. TO 48 IN. VERTICALLY ABOVE THE FLOOR AND
 WITHIN 60 IN. OF THE SECURED DOOR OPENINGS.
  
 (4) THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 AS FOLLOWS: PUSH TO EXIT.
  
 (5) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS
 AND THE DOOR LEAVES SHALL REMAIN UNLOCKED FOR NOT LESS
 THAN 30 SECONDS.
  
 (6) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE
 SIGNALING SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND
 THEY SHALL REMAIN UNLOCKED UNTIL THE FIRE-PROTECTIVE
 SIGNALING SYSTEM HAS BEEN MANUALLY RESET.
  
 (7) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT
 ACTIVATE THE BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM
 SHALL NOT BE REQUIRED TO UNLOCK THE DOOR LEAVES. (8)
 ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR FIRE
 DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND
 THEY SHALL REMAIN UNLOCKED UNTIL THE FIRE-PROTECTIVE
 SIGNALING SYSTEM HAS BEEN MANUALLY RESET.
  
 ALL OF THESE REQUIRMENTS SHALL BE MET AND CLEARLY
 IDENTIFIED AND INDICATED ON THE PLAN AT EACH INTENDED
 INSTALLATION LOCATION.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-29 Cont ID  
Sent By pleduc Date 2014-09-29 Time   Rev Time 0.00
Received By pleduc Date 2014-09-23 Time 09:49 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-17 Cont ID  
Sent By pleduc Date 2014-09-17 Time   Rev Time 0.00
Received By pleduc Date 2014-09-16 Time 15:19 Sent To PC
Notes
2014-09-16 11:44:30ROUTED TO ELECTRICAL