Plan Review Details - Permit 14090505
Plan Review Stops For Permit 14090505
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-10 Cont ID  
Sent By skennedy Date 2014-10-10 Time 12:40 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-03 Cont ID  
Sent By skennedy Date 2014-10-03 Time 16:44 Rev Time 0.00
Received By skennedy Date 2014-10-03 Time 16:44 Sent To  
Notes
2014-10-03 16:45:501ST REVIEW: FBC 2010
  
 FBC 107.3.5 STRUCTURAL PLAN REVIEW CRITERIS: SPECIFY
 ANCHOR DIAMETER.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-10-10 Cont ID  
Sent By skennedy Date 2014-10-10 Time 12:40 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-10-03 Cont ID  
Sent By skennedy Date 2014-10-03 Time 16:46 Rev Time 0.00
Received By skennedy Date 2014-10-03 Time 16:46 Sent To  
Notes
2014-10-03 16:46:551ST REVIEW: FBC 2010
  
 THE APPLICATION IS UNDER VALUED:
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-22 Cont ID  
Sent By dhayes Date 2014-09-22 Time 16:14 Rev Time 0.00
Received By dhayes Date 2014-09-22 Time 16:14 Sent To B
Notes
2014-09-22 16:17:59TO MISC. 2
  
  
2014-09-22 16:15:17DATE: 9/22/2014
 PROJECT: FOREVER 21 SIGN
 PERMIT#: 14090505
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) NEC 600.6(A)(1)DISCONNECTS.
 EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE
 LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL
 UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN OR
 OUTLINE LIGHTING SYSTEM THAT IT CONTROLS.
  
 2) FBC-E 505.2.4 ENERGY
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS.
  
 3) WPB AMENDMENTS TO THE FBC SECTION 109.3 VALUATION.
 THE CLAIMED VALUATION OF THE, ALTERATION, APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION.THE BUILDING OFFICIAL
 SHALL RESERVE THE RIGHT TO DENY THE PERMIT. THE
 APPLICANT HAS THE RIGHT TO SHOW DETAILED, QUANTITY
 ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS (EXCLUDING
 LAND VALUE) TO MEET THE APPROVAL OF THE BUILDING
 OFFICIAL.
 FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN
 FEES, MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST
 ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS
 PUBLISHED BY INTERNATIONAL CODE CONGRESS. FINAL
 BUILDING PERMIT VALUATION SHALL BE SET BY THE BUILDING
 OFFICIAL. FBC WPB AMENDMENTS. SECTION 109.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-03 Cont ID  
Sent By skennedy Date 2014-10-03 Time 16:44 Rev Time 0.00
Received By skennedy Date 2014-09-15 Time 16:43 Sent To  
Notes
2014-09-15 14:48:57ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-22 Cont ID  
Sent By ajones Date 2014-09-22 Time 13:33 Rev Time 0.00
Received By ajones Date 2014-09-22 Time 13:32 Sent To E
Notes
***NONE***