Plan Review Details - Permit 14090490
Plan Review Stops For Permit 14090490
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-11-06 Cont ID  
Sent By jgomez Date 2014-11-06 Time 14:05 Rev Time 0.00
Received By jgomez Date 2014-11-06 Time 14:05 Sent To  
Notes
2014-11-06 14:05:42ACCORDING TO AERIAL VIEW FROM THE PROPERTY APPRAISAL IT
 LOOKS LIKE THE EXISTING WINDOWS ARE AWNING TYPE
 WINDOWS. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date 2014-10-31 Cont ID  
Sent By jgomez Date 2014-10-31 Time 17:24 Rev Time 0.00
Received By jgomez Date 2014-10-31 Time 17:24 Sent To  
Notes
2014-10-31 17:28:00 
 ***REVIEW IN PROGRESS....
  
  
 1-SPECIFY ANCHOR TO BE USED.
  
 2- SPECIFY THE EXISTING BEDROOM WINDOWS TYPE AND SIZE
 TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF
 SEC. 604 OF 2010 FBC-EXISTING BUILDING CODE.
 REPEAT COMMENT. NOT ADDRESSED.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. THERE ARE NO 12 WINDOWS TO BE REPLACED AS STATED
 IN THE PERMIT APPLICATION. ACCORDING TO SKETCH
 SUBMITTED, THERE ARE 19 WINDOWS AND 7 WINDOW MULLIONS
 TO BE REPLACED. IN ADDITION, THERE WILL BE HURRICANE
 PANELS INSTALLED ALSO. VALUATION TO INCLUDE ALL LABOR,
 MATERIALS, AND CONTRACTOR'S OVERHEAD AND PROFIT AS
 REQUIRED BY SEC. 1069.3 CITY AMENDMENTS TO FBC. UPDATE
 VALUATION AS REQUIRED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-10-07 Cont ID  
Sent By jgomez Date 2014-10-07 Time 10:54 Rev Time 0.00
Received By jgomez Date 2014-10-07 Time 10:54 Sent To  
Notes
2014-10-07 10:56:46RESIDENTIAL (R3) WINDOW ALTERATION, SECOND BUILDING
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE SHUTTERS INSTALLATION SCHEDULE.
 INFORMATION SHOWN IN THE SHUTTERS INSTALLATION SCHEDULE
 SUBMITTED IS INCOMPLETE. IT DOESN'T PROVIDE ANY
 INFORMATION CONCERNING THE PROPOSED INSTALLATION. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- SKETCH SUBMITTED: CLEARLY SPECIFY THE EXISTING
 BEDROOM WINDOWS TYPE AND SIZE TO VERIFY COMPLIANCE WITH
 THE EGRESS REQUIREMENTS OF SEC. 604 OF 2010
 FBC-EXISTING BUILDING CODE.
 REPEAT COMMENT. NOT ADDRESSED.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. THERE ARE NO 12 WINDOWS TO BE REPLACED AS STATED
 IN THE PERMIT APPLICATION. ACCORDING TO SKETCH
 SUBMITTED, THERE ARE 19 WINDOWS AND 7 WINDOW MULLIONS
 TO BE REPLACED. IN ADDITION, THERE WILL BE HURRICANE
 PANELS INSTALLED ALSO. VALUATION TO INCLUDE ALL LABOR,
 MATERIALS, AND CONTRACTOR'S OVERHEAD AND PROFIT AS
 REQUIRED BY SEC. 1069.3 CITY AMENDMENTS TO FBC. UPDATE
 VALUATION AS REQUIRED.
 REPEAT COMMENT. NOT ADDRESSED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICE DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-17 Cont ID  
Sent By jgomez Date 2014-09-17 Time 08:50 Rev Time 0.00
Received By jgomez Date 2014-09-17 Time 08:44 Sent To  
Notes
2014-09-17 08:53:43RESIDENTIAL (R3) WINDOW ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE SHUTTERS INSTALLATION SCHEDULE.
 INFORMATION SUBMITTED IS INCOMPLETE. IT DOESN'T PROVIDE
 ANY INFORMATION CONCERNING THE PROPOSED INSTALLATION.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- SKETCH SUBMITTED: CLEARLY IDENTIFY ROOM DESIGNATIONS
 (FOR EXAMPLE BEDROOM, KITCHEN, LIVING ROOM, ETC). AND
 CLEARLY SPECIFY THE EXISTING BEDROOM WINDOWS TYPE AND
 SIZE TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS
 OF SEC. 604 OF 2010 FBC-EXISTING BUILDING CODE.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. THERE ARE NO 12 WINDOWS TO BE REPLACED AS STATED
 IN THE PERMIT APPLICATION. ACCORDING TO SKETCH
 SUBMITTED, THERE ARE 19 WINDOWS AND 7 WINDOW MULLIONS
 TO BE REPLACED. IN ADDITION, THERE WILL BE HURRICANE
 PANELS INSTALLED ALSO. VALUATION TO INCLUDE ALL LABOR,
 MATERIALS, AND CONTRACTOR'S OVERHEAD AND PROFIT AS
 REQUIRED BY SEC. 1069.3 CITY AMENDMENTS TO FBC. UPDATE
 VALUATION AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICE DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-11-06 Cont ID  
Sent By jgomez Date 2014-11-06 Time 14:01 Rev Time 0.00
Received By jgomez Date 2014-11-06 Time 14:01 Sent To  
Notes
2014-11-06 14:02:43MET W/ MIKE TO GO OVER COMMENTS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-10-31 Cont ID  
Sent By jgomez Date 2014-10-31 Time 17:25 Rev Time 0.00
Received By jgomez Date 2014-10-28 Time 13:50 Sent To  
Notes
2014-10-28 13:52:40INCOMING SENT TO J. GOMEZ. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-07 Cont ID  
Sent By jgomez Date 2014-10-07 Time 10:54 Rev Time 0.00
Received By jgomez Date 2014-10-03 Time 13:35 Sent To  
Notes
2014-10-03 13:35:56TO JG DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-17 Cont ID  
Sent By jgomez Date 2014-09-17 Time 08:44 Rev Time 0.00
Received By jgomez Date 2014-09-17 Time 08:44 Sent To  
Notes
2014-09-15 13:24:36ROUTED TO BLDG $5000 & UNDER