Plan Review Details - Permit 14090441
Plan Review Stops For Permit 14090441
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-11 Cont ID  
Sent By shill Date 2014-10-11 Time 14:39 Rev Time 0.00
Received By shill Date 2014-10-11 Time 14:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-30 Cont ID  
Sent By shill Date 2014-09-30 Time 18:10 Rev Time 0.00
Received By shill Date 2014-09-30 Time 18:10 Sent To  
Notes
2014-09-30 18:12:17****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE FLOOR PLAN TO SHOW ROOM DESIGNATIONS.
  
 2. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND
 OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. THE
 CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%.
  
 TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION
 NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT:
  
 STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS
 - AWNING, CASEMENT, SINGLE HUNG?
  
 STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE.
 CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE
 WINDOW IS FULLY OPEN.
  
 STATE WHAT THE PROPOSED CLEAR OPENING DIMENSIONS ARE.
 THIS CAN BE OBTAINED FROM THE MANUFACTURER.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-11 Cont ID  
Sent By shill Date 2014-10-11 Time 14:40 Rev Time 0.00
Received By shill Date 2014-10-02 Time 07:39 Sent To  
Notes
2014-10-03 07:39:47TO SHILL DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-30 Cont ID  
Sent By shill Date 2014-09-30 Time 18:12 Rev Time 0.00
Received By shill Date 2014-09-30 Time 18:12 Sent To  
Notes
2014-09-12 14:27:23ROUTED TO MISC 1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved