Plan Review Stops For Permit 14090425 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2014-09-24 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-09-24 |
Time |
17:44 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-09-24 |
Time |
17:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-09-12 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-09-12 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-09-12 |
Time |
16:29 |
Sent To |
|
|
Notes |
2014-09-12 16:30:57 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. THE ASSEMBLY SELECTED FOR THE FLAT ROOF HAS A DESIGN | | PRESSURE LIMITATION OF -60. THIS DOES NOT MEET THE | | DESIGN PRESSURE REQUIREMENT OF THE CORNER ZONES. SEE | | GENERAL LIMITATION #7 ON THE LAST PAGE OF THE NOA; RAS | | 117 CALCULATIONS REQUIRED TO BE PERFORMED BY AN | | ARCHITECT OR ENGINEER. FBC1609, PROVIDE ENGINEERING | | REQUIRED FOR THE FLAT DECK. |
|
|
|