Plan Review Details - Permit 14090410
Plan Review Stops For Permit 14090410
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-09-24 Cont ID  
Sent By rmcdouga Date 2014-09-24 Time 15:36 Rev Time 0.00
Received By rmcdouga Date 2014-09-24 Time 15:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-12 Cont ID  
Sent By rmcdouga Date 2014-09-12 Time 11:44 Rev Time 0.00
Received By rmcdouga Date 2014-09-12 Time 11:44 Sent To E
Notes
2014-09-12 16:26:17 
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) FBC 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2) FBC 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 SHOW THAT THE SOUND UNDERLAYMENT COMPLIES WITH THE
 FOLLOWING:
  
 3) SECTION 603 COMBUSTIBLE MATERIAL IN TYPE I AND II
 CONSTRUCTION
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM
 PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN
 25.
 EXCEPTIONS:
 1. INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
 3. FOAM PLASTICS IN ACCORDANCE WITH CHAPTER 26.
  
 4) SECTION 2603 FOAM PLASTIC INSULATION
 2603.3 SURFACE-BURNING CHARACTERISTICS.
 UNLESS OTHERWISE INDICATED IN THIS SECTION, FOAM
 PLASTIC INSULATION AND FOAM PLASTIC CORES OF
 MANUFACTURED ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 75 AND A SMOKE-DEVELOPED INDEX OF NOT
 MORE THAN 450 WHERE TESTED IN THE MAXIMUM THICKNESS
 INTENDED FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL
 723. LOOSE FILL-TYPE FOAM PLASTIC INSULATION SHALL BE
 TESTED AS BOARD STOCK FOR THE FLAME SPREAD AND
 SMOKE-DEVELOPED INDEXES.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-13 Cont ID  
Sent By dhayes Date 2014-09-13 Time 13:06 Rev Time 0.00
Received By dhayes Date 2014-09-13 Time 12:50 Sent To  
Notes
2014-09-13 13:11:57DATE: 9/13/2014
 PROJECT: GOLDBERG BATHROOM RENNOVATION
 PERMIT#: 14090410
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) NEC 210.11(C)(3)
 BATHROOM BRANCH CIRCUITS. IN ADDITION TO THE NUMBER OF
 BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS
 SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. VERFY EXISTING
 RECEPTACLE OUTLET CIRCUIT IS 20 AMP OR UPDATE TO FOR
 NEC COMPLIANCE
  
 2) FBC-RESIDENTIAL 314 AND 315.
 WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. VERIFY DUAL
 VOLTAGE SMOKE DETECTORS ARE EXISTING OR UPDATE FOR FBC
 COMPLIANCE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-24 Cont ID  
Sent By rmcdouga Date 2014-09-24 Time 15:36 Rev Time 0.00
Received By rmcdouga Date 2014-09-24 Time 15:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-13 Cont ID  
Sent By dhayes Date 2014-09-13 Time 13:12 Rev Time 0.00
Received By dhayes Date 2014-09-11 Time 17:15 Sent To  
Notes
2014-09-12 17:15:54SENT TO ELECTRICAL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-09-12 Cont ID  
Sent By rmcdouga Date 2014-09-12 Time 11:44 Rev Time 0.00
Received By rmcdouga Date 2014-09-12 Time 11:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-09-12 Cont ID  
Sent By rmcdouga Date 2014-09-12 Time 11:43 Rev Time 0.00
Received By rmcdouga Date 2014-09-12 Time 11:43 Sent To  
Notes
***NONE***