Plan Review Details - Permit 14090408
Plan Review Stops For Permit 14090408
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-10-17 Cont ID  
Sent By tklarge Date 2014-10-17 Time 13:21 Rev Time 0.00
Received By tklarge Date 2014-10-17 Time 13:21 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-09-20 Cont ID  
Sent By tklarge Date 2014-09-20 Time 05:32 Rev Time 0.00
Received By tklarge Date 2014-09-20 Time 05:32 Sent To  
Notes
2014-09-20 05:42:57CITY OF WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1.
 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 GAS RANGE.
 2) THE GAS TABLE REFERENCED ON YOUR DRAWING SHOWS THE
 CSST TUBING SIZES IN EHD (EQUIVALENT HYDRAULIC
 DIAMETER). INDICATE THE CORRELATING EHD FOR THE NOMINAL
 PIPE SIZES SHOWN ON THE GAS PIPING RISER.
 3)THE GAS PLAN INDICATES PIPING WILL BE RUN UNDER THE
 HOUSE. GAS PIPING INSTALLED BENEATH FLOORS SHALL COMPLY
 WITH SEC.404.12 OF THE 2010 FGC. SUBMIT A DETAIL FOR
 THE TYPE OF CONDUIT TO BE INSTALLED, THE SIZE, THE
 LOCATION, ETC. THE CONDUIT SHALL ORIGINATE AND
 TERMINATE IN AN OCCUPIABLE/ACCESSIBLE PORTION OF THE
 BUILDING.
 4) THE GAS RISER SHOWS CSST TUBING TO THE TANKLESS
 WATER HEATER BUT THE PLAN SHOWS GALVANIZED PIPING.
 CLARIFY.
 5) INDICATE THE TYPE OF VENT/CHIMNEY FOR THE TANKLESS
 WATER HEATER. THE LOCATION OF THE VENT SHALL COMPLY
 W/SEC. 503 OF THE 2010 FGC.
 6) IDENTIFY THE TANKLESS WATER HEATER OUTLET ON THE GAS
 RISER.
 7) PLANS DRAWN IN PENCIL ARE NOT ACCEPTABLE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-17 Cont ID  
Sent By tklarge Date 2014-10-17 Time 13:22 Rev Time 0.00
Received By tklarge Date 2014-10-16 Time 07:48 Sent To  
Notes
2014-10-17 07:48:48TO T.L'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-20 Cont ID  
Sent By tklarge Date 2014-09-20 Time 05:44 Rev Time 0.00
Received By tklarge Date 2014-09-11 Time   Sent To  
Notes
2014-09-20 05:43:589/20/14- -DENIED/E-MAILED CONTR./PLACED IN SMALL
 "A".TKL.
2014-09-11 16:28:54<5000 GAS/PLUMB