|
 |
 |
 |
 |
 |
Plan Review Details - Permit 14090408
Plan Review Stops For Permit 14090408 |
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2014-10-17 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2014-10-17 |
Time |
13:21 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2014-10-17 |
Time |
13:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2014-09-20 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2014-09-20 |
Time |
05:32 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2014-09-20 |
Time |
05:32 |
Sent To |
|
|
Notes |
2014-09-20 05:42:57 | CITY OF WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1. | | 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE | | GAS RANGE. | | 2) THE GAS TABLE REFERENCED ON YOUR DRAWING SHOWS THE | | CSST TUBING SIZES IN EHD (EQUIVALENT HYDRAULIC | | DIAMETER). INDICATE THE CORRELATING EHD FOR THE NOMINAL | | PIPE SIZES SHOWN ON THE GAS PIPING RISER. | | 3)THE GAS PLAN INDICATES PIPING WILL BE RUN UNDER THE | | HOUSE. GAS PIPING INSTALLED BENEATH FLOORS SHALL COMPLY | | WITH SEC.404.12 OF THE 2010 FGC. SUBMIT A DETAIL FOR | | THE TYPE OF CONDUIT TO BE INSTALLED, THE SIZE, THE | | LOCATION, ETC. THE CONDUIT SHALL ORIGINATE AND | | TERMINATE IN AN OCCUPIABLE/ACCESSIBLE PORTION OF THE | | BUILDING. | | 4) THE GAS RISER SHOWS CSST TUBING TO THE TANKLESS | | WATER HEATER BUT THE PLAN SHOWS GALVANIZED PIPING. | | CLARIFY. | | 5) INDICATE THE TYPE OF VENT/CHIMNEY FOR THE TANKLESS | | WATER HEATER. THE LOCATION OF THE VENT SHALL COMPLY | | W/SEC. 503 OF THE 2010 FGC. | | 6) IDENTIFY THE TANKLESS WATER HEATER OUTLET ON THE GAS | | RISER. | | 7) PLANS DRAWN IN PENCIL ARE NOT ACCEPTABLE. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-10-17 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2014-10-17 |
Time |
13:22 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2014-10-16 |
Time |
07:48 |
Sent To |
|
|
Notes |
2014-10-17 07:48:48 | TO T.L'S DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-09-20 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2014-09-20 |
Time |
05:44 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2014-09-11 |
Time |
|
Sent To |
|
|
Notes |
2014-09-20 05:43:58 | 9/20/14- -DENIED/E-MAILED CONTR./PLACED IN SMALL | | "A".TKL. | 2014-09-11 16:28:54 | <5000 GAS/PLUMB |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |