Plan Review Details - Permit 14090389
Plan Review Stops For Permit 14090389 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2014-11-25 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-11-25 |
Time |
16:27 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-11-25 |
Time |
16:27 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2014-11-17 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-11-17 |
Time |
11:15 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-11-08 |
Time |
10:04 |
Sent To |
FIRE |
|
Notes |
2014-11-08 10:45:20 | 11/08/14 NOTE: THE NEW PLANS APPEAR TO BE CODE | | COMPLIANT, THE PLANS ARE MISSING SHEET A-4 WHICH WAS | | NOT SUBMITTED IN THE LAST TWO RESUBMITTALS. THERE IS | | ONLY ONE ORIGINAL SET OF PLANS WITH A A4 SHEET. TODAY | | (SAT. NOV. 08/2014) I CALLED THE ARCHITECT OF RECORD | | KELLY YATES (653-8280) AND LEFT A VOICE MESSAGE THAT WE | | NEED (2) A4 SHEETS IF THERE IS A REVISION ON THIS SHEET | | OR ONE A4 SHEET IF NOTHING ON THIS SHEET WAS CHANGED. | | WILL HOLD UP THE REVIEW SO THIS SHEET CAN BE INSERTED | | INTO THE PLANS BEFORE CONTINEUING TO FIRE FOR REVIEW. | | J. W. | | | | 11/17/14 FAILED SEE COMMENT ABOVE. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2014-10-16 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-10-16 |
Time |
14:58 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-10-16 |
Time |
11:00 |
Sent To |
|
|
Notes |
2014-10-16 14:58:15 | BUILDING PLAN REVIEW | | PERMIT: 14090389 | | ADD: 309 CLEMATIS ST | | CONT: TBD | | TEL: (561)296-7699 SCOTT SMITH | | | | 2010 FLORIDA BUILDING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | | | 2ND REVIEW | | DATE: THURS. OCT. 16TH/ 2014 | | ACTION: DENIED | | | | 1) THE NEW SHEETS SHOW ON PAGE A-2.0 THE 2ND FLOOR | | FRONT STAIRWAY PROPOSED TO MOVE ITS LOCATION FORWARD | | FROM WHERE ITS LOCATION IS NOW. THERE IS A NEW ROOM | | LCREATED IN THE 2ND FLOOR LANDING THAT IS 19'-3" LONG. | | SHEET A-3.0 INDICATES THIS ROOM IS FOR ROOF ACCESS | | ONLY. THIS IS NOT PART OF A REQUIRED EXIT AND SHOULD | | NOT HAVE ACCESS INTO THE VERTICAL EXIT. | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | 2010 FBC-B 1022.4 PENETRATIONS. | | PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT | | ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT | | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT | | VENTILATION OR PRESSURIZATION, SPRINKLER PIPING, | | STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT | | COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING | | THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT | | EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH | | PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH | | SECTION 713. THERE SHALL BE NO PENETRATIONS OR | | COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT, | | BETWEEN ADJACENT EXIT ENCLOSURES. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-09-25 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-09-25 |
Time |
09:47 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-09-25 |
Time |
07:17 |
Sent To |
|
|
Notes |
2014-09-25 09:47:54 | BUILDING PLAN REVIEW | | PERMIT: 14090389 | | ADD: 309 CLEMATIS ST | | CONT: TBD | | TEL: (561)296-7699 SCOTT SMITH | | | | 2010 FLORIDA BUILDING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: THURS. SEPT. 25TH/ 2014 | | ACTION: DENIED | | | | 1) PLEASE PROVIDE A EXIT PLAN FOR THE WHOLE BUILDING. | | PLEASE NOTE THIS IS A THREE STORY BUILDING A-2 / A3 | | ASSEMBLY BUILDING WITH ONLY 2 ENCLOSED STAIRWELLS. | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | CODE, CHAPTER 1, ADMINISTRATION, | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE | | EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL | | SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND | | DOCUMENTS: A FLOOR PLAN; | | 107.3.5.1 COMMERCIAL BUILDINGS: | | 107.3.5.1.1 BUILDING | | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS | | SHALL BE DETERMINED. | | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE | | TABLE 503). | | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: | | OCCUPANCY LOAD | | GROSS | | NET | | MEANS OF EGRESS | | EXIT ACCESS | | EXIT | | EXIT DISCHARGE | | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION | | DOORS | | | | 2) 2010 FBC-B 1016.1 DOES ALLOW FOR UNENCLOSED | | STAIRWELLS FOR 50 % OF EXITS BUT EXCEPTION # 3 ONLY | | ALLOWS THE EXIT ACCESS TRAVEL DISTANCE TO A MAXIMUM OF | | 50 PERCENT OF THE EXITS IS PERMITTED TO BE MEASURED | | FROM THE MOST REMOTE POINT WITHIN A BUILDING TO AN EXIT | | USING UNENCLOSED EXIT ACCESS STAIRWAYS OR RAMPS WHEN | | CONNECTING A MAXIMUM OF TWO STORIES. THE TWO CONNECTED | | STORIES SHALL BE PROVIDED WITH AT LEAST TWO MEANS OF | | EGRESS. SUCH INTERCONNECTED STORIES SHALL NOT BE OPEN | | TO OTHER STORIES. THIS STAIR CONNECTS TO THE 3RD STORY | | A ROOF TOP ASSEMBLY FLOOR. | | | | 3) NOTE THERE IS ALSO AN OPEN EXPIRED PERMIT FOR THE | | 3RD STORY ROOFTOP ADDITION, NEVER ACHIEVED A | | CERTIFICATE OF OCUPANCY, PERMIT # 08060519. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | DEVELOPMENT SERVICES HOME PAGE | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2014-11-01 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-11-01 |
Time |
15:10 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-11-01 |
Time |
14:23 |
Sent To |
|
|
Notes |
2014-11-01 15:10:01 | 11/1/2014 | | PROJECT: SKY 309 | | PERMIT#: 14090389 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 2ND ELECTRICAL PLAN REVIEW | | ACTION: PROVISO | | | | 1) ACCESS TO EXITS SHALL BE MARKED BY APPROVED, READILY | | VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO | | REACH THE EXIT IS NOT READILY APPARENT TO THE | | OCCUPANTS. NFPA 101 SECTION 7.10.1.5.1 | | | | 2) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED | | MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND | | ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE | | REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL | | BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY | | INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF | | A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT | | REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 | | | | 3) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL | | BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL | | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL | | SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT | | SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL. | | EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT | | EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL | | BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND | | BY ONE OF THE WIRING METHODS OF NEC CHAPTER 3. NEC | | 700.12(F) | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2014-09-22 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-09-22 |
Time |
11:34 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-09-22 |
Time |
11:34 |
Sent To |
|
|
Notes |
2014-11-01 15:30:02 | 09/22/2014 | | PROJECT: SKY 309 | | PERMIT#: 14090389 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: PROVISO | | | | 1) ACCESS TO EXITS SHALL BE MARKED BY APPROVED, READILY | | VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO | | REACH THE EXIT IS NOT READILY APPARENT TO THE | | OCCUPANTS. NFPA 101 SECTION 7.10.1.5.1 | | | | 2) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED | | MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND | | ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE | | REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL | | BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY | | INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF | | A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT | | REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 | | | | 3) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL | | BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL | | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL | | SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT | | SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL. | | EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT | | EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL | | BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND | | BY ONE OF THE WIRING METHODS OF NEC CHAPTER 3. NEC | | 700.12(F) | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2014-12-01 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-12-01 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-12-01 |
Time |
11:20 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2014-11-18 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-11-18 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-11-18 |
Time |
12:10 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2014-10-14 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-10-14 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-10-14 |
Time |
11:47 |
Sent To |
|
|
Notes |
2014-10-14 12:35:54 | THIS PLAN WAS REVIEWED AND TENTATTIVELY APPROVED BY | | PETER LEDUC, FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PROVISO: | | | | THE OCCUPANY LOAD AS PROPOSED COULD NOT BE VERIFIED. | | | | THE STAIRWAYS AND DOORS ASH SHOWN IS ACCEPTABLE AND | | WILL BE FIELD VERIFIED. | | | | DIMENSIONS OF THE OCCUPIED SPACE OR OCCUPANCY LOAD | | CALCULATIONS WERE NOT PROVIDED OR DID NOT MATCH | | DRAWINGS TO VERIFY THE OCCUPANCY LOADS PROPOSED. | | | | PROVIDE OCCUPANCY LOAD CALCULATIONS INCLUDING | | DIMENSIONS AND OTHER PERTINANT INFORMATION JUSTIFYING | | THE PROPOSED OCCUPANY LOADS THAT MATCH EXISTING OR | | PROPOSED FLOOR LAYOUTS. | | | | PROVIDE THE ABOVE INFORMATION TO THE FIRE INSPECTOR FOR | | VERIFICATION AT THE TIME OF FIRE INSPECTION. THE | | OCCUPANCY LOADS WILL BE POSTED BASED ON THOSE | | CALCULATIONS WITH VERIFICATION OF THE FIRE INSPECTOR. | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2014-09-15 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-09-15 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-09-15 |
Time |
11:59 |
Sent To |
|
|
Notes |
2014-11-18 12:11:52 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE SEE BUILDING COMMENTS, WILL STAMPED APPROVED | | WHEN CORRECTED IF NO ADDTIONAL CHANGES. | 2014-09-15 15:23:37 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | ALL EXIT PATHS AND CAPACITIES FROM ALL FLOOR LEVELS | | SHALL BE CLEARLY IDENTIFIED AND INDICATED. | | | | SHEET A-O SHOWS OCCUPANCY LOADS THAT CAN'T BE CONFIRMED | | WITH THE INFORMATION PROVIDED. A LIFE SAFETY PLAN SHALL | | BE SUBMITTED SHOWING ALL EXIT PATHWAYS, FROM ALL | | FLOORS, WITH OCCUPANT LOADS, LEADING TO A PUBLIC WAY. | | THE EXITS DISCHARGES ON THE 1ST FLOOR SHALL BE | | IDENTIFIED (WITH DIMENSIONS) AND SHALL LEAD TO A PUBLIC | | WAY. | | | | SHEET A-3 SHOWS AN EXIT DOOR WITH AN EXIT CAPACITY OF | | 165 AND THE STAIR EXIT CAPACITY OF 200. THE EXIT | | CAPCITY CAN ONLY BE MEASURED AT THE NARROWEST POINT, | | 165. IT IS UNCLEAR WHAT THE PROPOSED TOTAL IS USING. | | | | SHEET A-3 DOES NOT SHOW THE SECOND EXIT FROM THE THIRD | | OR SECOND FLOOR AND THE EXIT CAPACITIES CALCULATIONS. | | | | OCCUPANT LOADS CAN NOT BE VERIFIED OR APPROVED AT THIS | | TIME WITHOUT FLOOR AND SEATING PLANS AND EXIT CAPACITY | | APPROVAL. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2014-12-01 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-12-01 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-11-19 |
Time |
16:12 |
Sent To |
|
|
Notes |
2014-11-24 16:13:03 | RE-SUBMITTAL SENT TO JIM WITMER FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2014-11-18 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-11-18 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-11-04 |
Time |
10:22 |
Sent To |
|
|
Notes |
2014-11-05 10:23:05 | TO JW DESK | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-11-01 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-11-01 |
Time |
15:10 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-10-03 |
Time |
17:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-09-25 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-09-25 |
Time |
09:48 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-09-12 |
Time |
08:24 |
Sent To |
|
|
Notes |
|
|
|