Plan Review Details - Permit 14090353
Plan Review Stops For Permit 14090353
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-12-30 Cont ID  
Sent By shill Date 2014-12-30 Time 08:13 Rev Time 0.00
Received By shill Date 2014-12-30 Time 08:13 Sent To  
Notes
2014-12-30 08:15:36****PROVISO****
 ****REVISION REQUIRED PRIOR TO FIRST INSPECTION****
  
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SAME PLAN (SIGNED & SEALED ON 9/5/14) WAS SUBMITTED;
 THEREFORE, REVIEW PASSED WITH PROVISO, REVISION
 REQUIRED TO ADDRESS PREVIOUS COMMENT:
  
 1. FASTENING PROPOSED SHOULD BE SPECIFIC: FASTENER
 TYPE, LENGTH OR MINIMUM EMBEDMENT, DIAMETER, MINIMUM
 NUMBER, FBC 1609. REVISE PLAN TO BE LESS VAGUE -
 "1/4-20 THROUGH BOLT APPROPRIATE FOR WEIGHT AND
 SURFACE."
  
 ALTHOUGH A THROUGH BOLT WAS SPECIFIED, GRAPHICALLY IT
 WAS NOT SHOWN AS EXTENDING THROUGH THE ENTIRE
 SUBSTRATE, SO THE BOLT WOULD THEREFORE REQUIRE A
 LENGTH.
  
 ALTERNATES (SCREWS, TOGGLE BOLTS) DID NOT INCLUDE
 LENGTH.
  
 REVISE PLAN TO INCLUDE FASTENER INFORMATION.
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-14 Cont ID  
Sent By shill Date 2014-10-14 Time 18:29 Rev Time 0.00
Received By shill Date 2014-10-14 Time 18:29 Sent To  
Notes
2014-10-14 18:30:20****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FASTENING PROPOSED SHOULD BE SPECIFIC: FASTENER
 TYPE, LENGTH OR MINIMUM EMBEDMENT, DIAMETER, MINIMUM
 NUMBER, FBC 1609. REVISE PLAN TO BE LESS VAGUE -
 "1/4-20 THROUGH BOLT APPROPRIATE FOR WEIGHT AND
 SURFACE."
  
 ALTHOUGH A THROUGH BOLT WAS SPECIFIED, GRAPHICALLY IT
 WAS NOT SHOWN AS EXTENDING THROUGH THE ENTIRE
 SUBSTRATE, SO THE BOLT WOULD THEREFORE REQUIRE A
 LENGTH.
  
 WHAT DOES "APPROPRIATE FOR WEIGHT AND SURFACE" MEAN?
 SHOULDN'T THE ENGINEER SPECIFY THE FASTENER BASED ON
 JOB CONDITIONS? THIS ENGINEER'S PLANS ARE NOT NORMALLY
 THIS VAGUE.
  
 ALTERNATES (SCREWS, TOGGLE BOLTS) DID NOT INCLUDE
 LENGTH.
  
 REVISE PLAN TO INCLUDE REQUESTED INFORMATION.
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-10-14 Cont ID  
Sent By sciard Date 2014-10-14 Time 13:01 Rev Time 0.00
Received By sciard Date 2014-10-14 Time 13:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-30 Cont ID  
Sent By shill Date 2014-12-30 Time 08:15 Rev Time 0.00
Received By shill Date 2014-12-01 Time 18:24 Sent To  
Notes
2014-12-01 18:24:51SENT TO ZONING.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-14 Cont ID  
Sent By shill Date 2014-10-14 Time 18:31 Rev Time 0.00
Received By shill Date 2014-09-10 Time 17:52 Sent To  
Notes
2014-09-10 17:52:13ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2014-12-29 Cont ID  
Sent By eschneid Date 2014-12-29 Time 17:21 Rev Time 0.25
Received By eschneid Date 2014-12-29 Time 17:21 Sent To B
Notes
2014-12-29 17:26:55PERMITTED - 33.75 SQ. FT (27 SQ. FT. + 25% CITYPLACE
 ADMINISTRATIVE VARIANCE)
 PROPOSED - 29.1 SQ. FT.
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-10-06 Cont ID  
Sent By eschneid Date 2014-10-06 Time 10:28 Rev Time 0.25
Received By eschneid Date 2014-10-06 Time 10:28 Sent To E
Notes
2014-10-06 10:48:34FAILED
  
 1) THE TWO INTERIOR ARCADE WALL SIGNS REQUESTED FOR
 THIS BAY EXCEED THE PERMITTED SIGN AREA PERMITTED BY
 THE CITYPLACE MASTER SIGN PLAN.
  
 PERMITTED - 27 SQ. FT.
 PROPOSED - 29.1 SQ. FT.
  
 PLEASE NOTE THAT CITYPLACE MAY APPROVE, IN WRITING, A
 VARIANCE TO INCREASE IN THE SIGN SQUARE FOOTAGE BY UP
 TO 25 PERCENT (TO 33.75 SQ. FT), WHICH WOULD PERMIT
 29.1 SQ. FT. OF INTERIOR ARCADE WALL SIGNAGE.
  
 2) A COPY OF THE REVIEW HAS BEEN SENT TO CARLOS BERNAL
 AT CITYPLACE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  