Plan Review Details - Permit 14090347
Plan Review Stops For Permit 14090347
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-11-13 Cont ID  
Sent By JWITMER Date 2014-11-13 Time 09:19 Rev Time 0.00
Received By jwitmer Date 2014-11-13 Time 09:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-24 Cont ID  
Sent By jwitmer Date 2014-09-24 Time 08:56 Rev Time 0.00
Received By jwitmer Date 2014-09-24 Time 08:10 Sent To  
Notes
2014-09-24 08:43:20BUILDING PLAN REVIEW
 PERMIT: 14090347
 ADD: 771 VILLAGE BLVD.
 CONT: GREY CONSTRUCTION
 TEL: (561)312-2766
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 24/ 2014
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS ARE PLANS THAT INDICATE THEY ARE
 1/4 INCH SCALE THAT WERE REDUCED TO FIT ON 8 1/2X 11
 1/4 PAPER. THEY ARE SMALLER THAN 1/8TH INCH SCALE. THEY
 COPIES ARE ALSO LIGHT AND WILL NOT BE VISIBLE WHEN
 SCANNED INTO RECORD RETENSION. THE 3RD ISSUE THE
 CONTRACTOR OF RECORD GREY CONSTRUCTION WILL NEED TO
 HAVE THE QUALIFIER PRINT THEIR NAME AND SIGN THEIR
 PLANS. NOTE A CGC CAN ONLY PREPARE PLANS FOR WHICH THEY
 ARE LICENSED AND UNDER THEIR SCOPE OF WORK COVERED BY
 THEIR LICENSE. EITHER PROVIDE THE PLUMBING LICENSE
 NUMBER OR A PLUMBING CONTRACTOR OR DESIGN PROFESSIONAL
 ARCHITECT OR ENGINEER FOR THE PLUMBING PLAN.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION:
  
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT.
  
 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE.
 107.3.4.1 GENERAL. WHEN IT IS REQUIRED THAT DOCUMENTS
 BE PREPARED BY A REGISTERED
 DESIGN PROFESSIONAL, THE BUILDING OFFICIAL SHALL BE
 AUTHORIZED TO REQUIRE THE OWNER TO ENGAGE AND DESIGNATE
 ON THE BUILDING PERMIT APPLICATION A REGISTERED DESIGN
 PROFESSIONAL WHO SHALL ACT AS THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE. IF THE
 CIRCUMSTANCES REQUIRE, THE OWNER SHALL DESIGNATE A
 SUBSTITUTE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL PERFORM THE DUTIES
 REQUIRED OF THE ORIGINAL
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE.
 THE BUILDING OFFICIAL SHALL BE NOTIFIED IN WRITING BY
 THE OWNER IF THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE IS CHANGED OR IS UNABLE TO CONTINUE
 TO PERFORM THE DUTIES. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-02 Cont ID  
Sent By dhayes Date 2014-12-02 Time 15:35 Rev Time 0.00
Received By dhayes Date 2014-12-02 Time 15:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-11-18 Cont ID  
Sent By PLEDUC Date 2014-11-18 Time 16:21 Rev Time 0.00
Received By scaldero Date 2014-11-18 Time 16:20 Sent To  
Notes
2014-11-18 16:22:44PERMIT #14090347
 FIRE REVIEW COMMENTS:
  
 1) EMERGENCY LIGHTING IS REQUIRED FOR EGRESS
 ILLUMINATION. THIS WILL BE REVIEWED AND APPROVAL GIVEN
 BY FIELD INSPECTOR.
  
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR/INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 (561) 644-7326

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-09-12 Cont ID  
Sent By pleduc Date 2014-09-12 Time   Rev Time 0.00
Received By pleduc Date 2014-09-12 Time 13:54 Sent To  
Notes
2014-09-12 16:07:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE SET OF PALNS WERE INCOMPLETE, ONE PROPOSED FLOOR
 WAS MISSING FROM SET.
  
 THE PLANS WERE CONFUSING AND HARD TO READ; TOO SMALL,
 LIGHT COLORED.
  
 UNABLE TO DETERMINE WHAT WALLS WERE COMING DOWN, OR
 GOING UP.
  
 UNABLE TO DETERMINE IF ANY LIFE SAFETY EQUIPMENT WILL
 BE IMPACTED, NOT DOCUMENTED ON PLANS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-12-06 Cont ID  
Sent By tklarge Date 2014-12-06 Time 03:23 Rev Time 0.00
Received By tklarge Date 2014-12-03 Time 10:38 Sent To  
Notes
2014-12-04 10:38:28RE-SUBMITTAL SENT TO TIM LARGE FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-02 Cont ID  
Sent By dhayes Date 2014-12-02 Time 15:35 Rev Time 0.00
Received By dhayes Date 2014-10-17 Time 17:43 Sent To  
Notes
2014-10-17 17:45:43B06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-29 Cont ID  
Sent By tklarge Date 2014-09-29 Time 11:32 Rev Time 0.00
Received By tklarge Date 2014-09-10 Time 10:00 Sent To  
Notes
2014-09-11 10:00:36B06
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-09-24 Cont ID  
Sent By jwitmer Date 2014-09-24 Time 08:56 Rev Time 0.00
Received By jwitmer Date 2014-09-24 Time 08:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2014-12-01 Cont ID  
Sent By HMOSER Date 2014-12-01 Time   Rev Time 0.33
Received By rbergsma Date 2014-12-01 Time   Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2014-09-25 Time   Rev Time 0.50
Received By   Date   Time   Sent To P
Notes
2014-09-25 14:02:08STATE THE PURPOSE OF THE NEWLY CREATED AREA, DOES THIS
 SPACE INCREASE THE OCCUPANT LOAD, O/A REQUIREMENT, NAIL
 OR PEDICURE AREA FOR VENTILATION ?

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-12-06 Cont ID  
Sent By tklarge Date 2014-12-04 Time 14:50 Rev Time 0.00
Received By tklarge Date 2014-12-06 Time 03:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-10-30 Cont ID  
Sent By TKLARGE Date 2014-10-30 Time 13:14 Rev Time 0.00
Received By tklarge Date 2014-10-30 Time 13:05 Sent To  
Notes
2014-10-30 13:13:59WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 1) SUBMIT TWO COMPLETE COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS/INSTALLATION MANUALS. THE INFORMATION
 YOU HAVE SUBMITTED IS INCOMPLETE.
 2) THE EXISTING PLUMBING RISER HAS A FLAT DRY VENT FOR
 THE MOST UPSTREAM CHAIR. THE VENT CONNECTION OF A DRY
 VENT TO A HORIZONTAL DRAIN SHALL CONNECT ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE. 2010 FPC
 SEC.905.3.
 3) THE PLUMBING INSTALLATION FOR THE ADDED CHAIRS
 CANNOT BE INSTALLED AS DESIGNED. CONSIDER A CIRCUIT
 VENT SYSTEM IN ACCORDANCE W/ 2010 FPC SEC.911.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-29 Cont ID  
Sent By tklarge Date 2014-09-29 Time 11:17 Rev Time 0.00
Received By tklarge Date 2014-09-29 Time 11:17 Sent To  
Notes
2014-09-29 11:31:171) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE PEDICURE CHAIRS.
 2) SUBMIT TWO COPIES OF CLEAR AND LEGIBLE PLANS FOR
 REVIEW. PLANS SHALL BE DRAWN ON A MIN. OF 1/8 " SCALE
 AND SHALL CLEARLY SHOW THE SCOPE OF WORK TO BE DONE.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1. THE PLANS ARE FROM
 A PREVIOUS PERMIT FROM 2007 AND HAVE THE PERMIT NUMBER
 STAMP ON THEM AND DIFFICULT TO READ. WPB AMEND. TO 2010
 FBC SEC. 107.2.1.4.
 3) SUBMIT TWO COPIES OF SANITARY AND WATER PIPING
 RISERS FOR REVIEW PER WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 4) CLEARLY IDENTIFY ALL NEW AND EXISTING WORK ON THE
 PLAN.