Plan Review Details - Permit 14090254
Plan Review Stops For Permit 14090254
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-14 Cont ID  
Sent By rmcdouga Date 2014-10-14 Time 19:07 Rev Time 0.00
Received By rmcdouga Date 2014-10-14 Time 16:02 Sent To  
Notes
2014-10-14 19:04:36 
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) SHEETS A1.1 SITE PLAN AND D2.1 DEMOLITION PLAN ARE
 MISSING FROM THE PACKAGE. THERE IS A SEPARATE PERMIT
 FOR THE DEMOLITION WITH THESE SHEETS, HOWEVER, IT WOULD
 HELP CLARIFY THE WORK IF THESE PLAN SHEETS ARE INCLUDED
 IN THIS SUBMITTAL. THEY ARE ALSO LISTED IN THE LIST OF
 DRAWINGS ON SHEET A0.1. FBC 107.2.1
  
 2) FBC 107.3.4 - THE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 ARE
 REQUIRED TO REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
  
 3) FBC 107.3.4 & DCA RULE 9N-3 - SUBMIT TWO SETS OF
 PRODUCTS APPROVALS FOR THE IMPACT RATED EXTERIOR ARCHED
 TOP IN-SWING ENTRY DOOR #101 AND THE IMPACT RATED
 EXTERIOR DOUBLE OUT-SWING FOYER DOOR #102.
  
 4) FBC 107.2.1 - CLARIFY THE EXTERIOR DOOR #105 AT THE
 FAMILY ROOM. ON SHEET A3.2 IT IS SPECIFIED AS CASEMENT
 WINDOWS. THE PRODUCT APPROVAL FOR CASEMENT WINDOWS THAT
 WAS SUBMITTED HAS MAXIMUM UNIT HEIGHT OF 71-7/8". THE
 UNIT HEIGHT FOR THIS OPENING IS 85" ON THE PLANS.
  
 5) INSTALLATION DRAWINGS FOR KML FIXED WINDOWS WERE
 SUBMITTED. THE FL NUMBER IS NOT LISTED ON THE DRAWINGS.
 SUBMIT TWO COPIES OF THE COVERSHEET WITH THE FL# THAT
 LISTS THESE DRAWINGS. ALSO INDICATE WHERE THIS WINDOW
 WILL BE INSTALLED. NOTE: PRODUCT APPROVALS FOR AN
 ANDERSON FIXED WINDOW WERE ALSO SUBMITTED. ARE THESE
 BOTH FOR THE ARCHED FIXED GLASS WINDOWS ABOVE THE GAME
 ROOM DOORS. FBC 107.2.1
  
 6) SUBMIT THE PRODUCT APPROVALS FOR THE EXTERIOR DOORS
 AND WIND THAT ARE TO BE RE-INSTALLED IN DIFFERENT
 LOCATIONS FBC 107.3.4 & DCA RULE 9N-3
  
 7) IN ORDER TO SPEED PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW THE REVIEW COMMENTS HAVE BEEN ADDRESSED.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-16 Cont ID  
Sent By dhayes Date 2014-10-16 Time 07:25 Rev Time 0.00
Received By dhayes Date 2014-10-15 Time 15:26 Sent To  
Notes
2014-10-16 11:24:0910/16/2014
 PROJECT: COLEMAN RESIDENCE
 PERMIT#: 14090254
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) NEC 210.70 LIGHTING OUTLETS SHALL BE INSTALLED WHERE
 SPECIFIED IN 210.70(A), (B), AND (C).
 (B) FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH?CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED TO
 PROVIDE ILLUMINATION ON THE EXTERIOR SIDE OF OUTDOOR
 ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS. INDICATE
 ALL REQUIRED SWITCHED LIGHTING OUTLETS AFFECTED BY THE
 INSTALLATION OR MODIFICATION OF EXTERIOR DOOR OPENINGS.
  
 2) NEC 406.3 RECEPTACLE OUTLETS SHALL BE LOCATED IN
 BRANCH CIRCUITS IN ACCORDANCE WITH PART III OF ARTICLE
 210. GENERAL INSTALLATION REQUIREMENTS SHALL BE IN
 ACCORDANCE WITH 406.3(A) THROUGH (F).
 (D) REPLACEMENT OF RECEPTACLES SHALL COMPLY WITH
 406.3(D)(1),(2), AND (3) AS APPLICABLE.
  
 (D)(2) GFCI PROTECTED RECEPTACLES SHALL BE PROVIDED
 WHERE REPLACEMENTS ARE MADE AT RECEPTACLE OUTLETS THAT
 ARE REQUIRED TO BE SO PROTECTED ELSEWHERE IN THIS CODE.
 SEE NEC 210.8
  
 NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION
 FOR PERSONNEL.
 (A) DWELLING UNITS. ALL 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN THE LOCATIONS
 SPECIFIED IN (1) THROUGH (8) SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
 (1) BATHROOMS.
 (2) GARAGES, AND ALSO ACCESSORY BUILDINGS THAT HAVE A
 FLOOR LOCATED AT OR BELOW GRADE LEVEL NOT INTENDED AS
 HABITABLE ROOMS AND LIMITED TO STORAGE AREAS, WORK
 AREAS, AND AREAS OF SIMILAR USE
 (3) OUTDOORS
  
 4) REVISED PLANS TO INDICATE ALL SWITCHES, RECEPTACLE
 OUTLETS, AND LIGHTS AFFECTED BY THE INSTALLATION OR
 MODIFICATION OF THE EXTERIOR DOORS AND WHERE AFFECTED
 BY THE OVERALL SCOPE OF DEMOLITION AND RENNOVATION WORK
 OF AS REQUIRED. WPB AMENDMENTS TO FBC 107.3.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-16 Cont ID  
Sent By dhayes Date 2014-10-16 Time 11:30 Rev Time 0.00
Received By dhayes Date 2014-09-09 Time 13:47 Sent To  
Notes
2014-09-09 13:48:01R06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-09-26 Cont ID  
Sent By rbergsma Date 2014-09-26 Time   Rev Time 0.50
Received By rbergsma Date   Time   Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-09-26 Cont ID  
Sent By tklarge Date 2014-09-26 Time 06:30 Rev Time 0.00
Received By tklarge Date 2014-09-26 Time 06:30 Sent To  
Notes
2014-09-26 06:31:33PLUMBING SUB- PERMIT REQUIRED BY LICENSED PLUMBING
 CONTRACTOR.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-09-11 Cont ID  
Sent By sgraham Date 2014-09-11 Time 15:40 Rev Time 0.00
Received By sgraham Date 2014-09-11 Time 15:40 Sent To  
Notes
2014-09-11 15:42:439/10/14 ZONING FAILED
  
 1. SUBMIT 2 COPIES OF AN UP TO DATE SURVEY OF THE
 PROPERTY, SHOWING THE LOCATION OF NEW ENTRY AND LOGGIA
2014-09-11 15:19:469/11/14