Plan Review Details - Permit 14090214
Plan Review Stops For Permit 14090214
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-09-29 Cont ID  
Sent By jgomez Date 2014-09-29 Time 17:40 Rev Time 0.00
Received By jgomez Date 2014-09-29 Time 17:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-09 Cont ID  
Sent By rmcdouga Date 2014-09-09 Time 11:11 Rev Time 0.00
Received By rmcdouga Date 2014-09-09 Time 11:11 Sent To  
Notes
2014-09-09 11:53:41REVISION TO CHANGE FROM SYSTEM W-9 TO SYSTEM W-7 OF THE
 MULE-HIDE MODIFIED BITUMEN ROOF SYSTEM FL10497.
  
 2010 FBC
  
 DENIED BY BUILDING
  
 1) THE W-7 SYSTEM HAS PRELIMINARY ATTACHED INSULATION
 AND A BASE SHEET FASTENED WITH OMG, DEKFAST OR TRUFAST
 FASTENERS. 12" OC IN THE 4" LAP AND 12" OC IN TWO
 STAGGERED CENTER ROWS. THIS SYSTEM DOES NOT CORRESPOND
 WITH THE INFORMATION IS THE ENGINEERING THAT WAS
 SUBMITTED FOR ENHANCED FASTENING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-29 Cont ID  
Sent By jgomez Date 2014-09-29 Time 17:31 Rev Time 0.00
Received By jgomez Date 2014-09-29 Time 17:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-09 Cont ID  
Sent By rmcdouga Date 2014-09-09 Time 11:11 Rev Time 0.00
Received By rmcdouga Date 2014-09-08 Time 14:35 Sent To  
Notes
2014-09-08 14:35:58REVISION SENT TO ROBERT MCDOUGAL'S DESK FOR REVIEW. JG.