Plan Review Details - Permit 14090204
Plan Review Stops For Permit 14090204
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-10-14 Cont ID  
Sent By dhayes Date 2014-10-14 Time 11:23 Rev Time 0.00
Received By dhayes Date 2014-10-14 Time 11:16 Sent To  
Notes
2014-10-14 11:26:55THE DEDICATED 120V ELETRICAL CIRCUIT FEEDING THE
 CONTROL PANEL SHAL BE INSTALLED BY A CERTIFIED
 ELECTRICAL CONTRACTOR LICENSED AND INSURED FOR THE
 SCOPE OF WORK INVOLVED.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-15 Cont ID  
Sent By dhayes Date 2014-09-15 Time 16:28 Rev Time 0.00
Received By dhayes Date 2014-09-15 Time 16:28 Sent To  
Notes
2014-09-15 16:33:06DATE: 9/15/2014
 PROJECT: OLD NAVY
 PERMIT#: 14090204
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) FOR THE SAME REASON AS THE FIR INSPECTOR. REVISE
 PLANS FOR OPERATION TO COMPLY WITH ORIGINAL DESIGN.
 ADDITIONALLY, ONCE COMPLETE AND OPERATIONAL IN ADDITION
 TO THE SYSTEM OPERATING AS STATED IN THE FIRE
 INSPECTORS COMMENTS THE PANEL IN THE TENANT SPACE MUST
 BE ABLE TO BE SILENCED AND OR RESET FROM THE MASTER
 CONTROL PANEL.
  
 2) THE DEDICATED 120V ELETRICAL CIRCUIT FEEDING THE
 CONTROL PANEL SHAL BE INSTALLED BY A CERTIFIED
 ELECTRICAL CONTRACTOR LICENSED AND INSURED FOR THE
 SCOPE OF WORK INVOLVED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-10-06 Cont ID  
Sent By scaldero Date 2014-10-06 Time 13:00 Rev Time 0.00
Received By scaldero Date 2014-10-06 Time 12:52 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-09-09 Cont ID  
Sent By scaldero Date 2014-09-09 Time 18:49 Rev Time 0.00
Received By scaldero Date 2014-09-09 Time 18:49 Sent To E
Notes
2014-09-09 18:57:18PERMIT # 14090204
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLAN REVIEW FAILED:
 1) INSUFFICIENT COVERAGE FOR STORE AREA. DEVICES NEED
 TO BE RAISED TO 110CD. ADDITIONAL DEVICES ARE NEEDED
 FOR FITTING ROOM AREA AND FOR STOCK AREA.
  
 2) PER APPROVED MASTER PLANS: MAIN FACP FOR THIS
 BUILDING IS TO BE THE ONLY PANEL TO NOTIFY THE FIRE
 DEPARMENT. NOTIFICATION WILL DESIGNATE SPECIFIC ADDRESS
 OF TENANT WHERE TROUBLE IS LOCATED. EACH BUILDING SHALL
 ALARM/EVACUATE ONLY THE SPACES IN THAT BUILDING (IE AN
 ALARM IN "B" WILL NOT EVACUATE ANY SPACE IN "A", "BII",
 OR "C". EACH TENANT SPACE FACP SHALL BE CONNECTED TO
 MAIN FACP FOR THIS BUILDING VIA MODULES. TENANT SYSTEM
 SHALL BE COMPATIBLE WITH NOTIFIER OR EQUAL APPROVED
 MAIN FACP/HARDWARE EACH FLOW/TAMPER SHALL BE ZONED SO
 THAT AN ALARM WILL SOUND FOR EACH BUILDING SEPARATELY.
  
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-14 Cont ID  
Sent By dhayes Date 2014-10-14 Time 11:27 Rev Time 0.00
Received By dhayes Date 2014-10-02 Time 14:07 Sent To  
Notes
2014-10-02 14:07:30RE-SUBMITTAL SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-15 Cont ID  
Sent By dhayes Date 2014-09-15 Time 16:33 Rev Time  
Received By dhayes Date   Time   Sent To  
Notes
2014-09-08 09:57:06ROUTED TO FIRE