Plan Review Details - Permit 14090191
Plan Review Stops For Permit 14090191
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-09-08 Cont ID  
Sent By jgomez Date 2014-09-08 Time 10:59 Rev Time 0.00
Received By jgomez Date 2014-09-08 Time 10:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-08 Cont ID  
Sent By jgomez Date 2014-09-08 Time 09:22 Rev Time 0.00
Received By jgomez Date 2014-09-08 Time 09:09 Sent To  
Notes
2014-09-08 09:28:07RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- RAS 117 CALCULATIONS SUBMITTED: FLAT ROOF APPROVED
 ASSEMBLY SPECIFIED BY THE ENGINEER DOESN'T MATCH FLAT
 ROOF APPROVED ASSEMBLY SELECTED BY THE CONTRACTOR.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-09-05 Cont ID  
Sent By fmittner Date 2014-09-05 Time 15:45 Rev Time 0.00
Received By fmittner Date 2014-09-05 Time 15:45 Sent To  
Notes
***NONE***