2014-09-18 08:13:50 | BUILDING PLAN REVIEW |
| REVISION: 14090037 |
| PERMIT: 13030782 |
| ADD: 326 FERN ST |
| CONT: STRATICON |
| TEL: (561)436-4733 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: THURS. SEPT. 18/2014 |
| ACTION: DENIED |
| |
| 1) COMPLIED. THRESHOLD BUILDING (3) SETS OF DOCUMENTS. |
| |
| 2) THE HAND DRAWN SKETCH FOR UNIT # 12331 HAS A PARTIAL |
| SHOP DRAWING STAMP, IT DOES NOT INDICATE IF APPROVED OR |
| NOT.2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING |
| |
| |
| 3) NOA # 11-1031.06 CGI WINDOWS SERIES 130 SENTENEL. |
| SHEET 2 OF 6 HAS HIGHLIGHTED 60 X 60 INCH WINDOWS WITH |
| GLASS TYPE "C" & "C1" WITH A +/- 48.8. THE VASD |
| PRESSURES ZONE # 4 ARE =/- 50.1 AND FOR ZONE # 5 ARE |
| +50.1 & -91.3. THE VASD PRESSURES ARE LOW FOR THIS |
| WINDOW SIZE.2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING |
| |
| |
| 4A) NOA # 12-0706.03 CGI DOOR SERIES "450" OUTSWING |
| GLAZED W/WO SIDELITES. WINDOW NOA # 11-1031.06 |
| INDICATES HAND WRITTEN 1ST FLOOR ONLY SECTION OF |
| STOREFRONT WITHIN 8.2 FT OF EDGE OF BUILDING (ZONE # 5) |
| PRESSURES +50.1/ -91.3 VASD. NOTE THIS SHEET |
| INDICATESTHE STANDARD HARDWARE IS ONLY GOOD FOR +/- |
| 70.2. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING |
| |
| |
| 4B) NOA # 12-0706.03 CGI DOOR SERIES "450" OUTSWING |
| GLAZED W/WO SIDELITES. SHEET 1.1 OF 7 INDICATES |
| (HIGHLIGHTED BOTH 10A & 10AA DOOR HEIGHT OF 96 3/4 IN. |
| THE PRESSURES FOR 10A ARE +/- 90.0. LOW REQUIRED 91.3 |
| VASD. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING |
| |
| |
| 4C) NOA # 12-0706.03 CGI DOOR SERIES "450" OUTSWING |
| GLAZED W/WO SIDELITES. SHEET 7 OF 7 MULLION ANCHORS NOT |
| PROVIDED (HIGHLIGHTED) ON |
| THE PLANS. |
| |
| 5) NOA # 12-0203.13 CGI WINDOW & DOOR, CLIPPED EXTRUDED |
| ALUMINUM MULLION. MULLION SIZES, RE-INFORCED OR NOT, |
| NOR ANCHORS ARE IDENTIFIED NOR THE PRESSURES. 2010 |
| FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING. |
| |
| NOTE THE 1ST HISTORIC REVIEW NOT SHOWN AS REVIEWED WILL |
| NEED TO SEND THE 2ND PACKAGE TO HISTORICS FOR REVIEW. |
| NOTE THE NOA # 11-1031.06 CGI WINDOWS SERIES 130 |
| SENTENEL SHOWS THE MUTTINS AS A OPTION, THIS MAY BE A |
| ISSUE WITH HISTORICS, TO KEEP THE HISTORICAL FEATURES |
| OF THE BUILDING, HISTORIC REVIEW IS REQUIRED. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |