Plan Review Details - Permit 14090028
Plan Review Stops For Permit 14090028
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-07 Cont ID  
Sent By jwitmer Date 2014-10-07 Time 06:41 Rev Time 0.00
Received By jwitmer Date 2014-10-07 Time 05:57 Sent To  
Notes
2014-10-07 06:41:08BUILDING PLAN REVIEW
 PERMIT: 14090028
 ADD: 525 S FLAGLER DR, COMMON FLOOR AREA
 CONT: URBAN DESIGN CONCEPTS
 TEL: (561)301-9506
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. OCT. 07/2014
 ACTION: APPROVED

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-04 Cont ID  
Sent By jwitmer Date 2014-09-04 Time 09:09 Rev Time 0.00
Received By jwitmer Date 2014-09-04 Time 06:30 Sent To  
Notes
2014-09-04 08:06:42BUILDING PLAN REVIEW
 PERMIT: 14090028
 ADD: 525 S FLAGLER DR, COMMON FLOOR AREA
 CONT: URBAN DESIGN CONCEPTS
 TEL: (561)301-9506
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. SEPT. 04/2014
 ACTION: DENIED
  
 1) SHEET A1-1 SHOWS NEW RESTROOMS, SHOWER FACILITIES
 AND A SAUNA, UNDER THE 2010 FL. EXISTING BUILDING CODE
 LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1A) THE NEW SINGLE USE TOLIET ROOMS NEED TO BE
 ACCESSIBILE SEE THE 2010 FL ACCESSIBILITY CODE 213.2
 TOILET ROOMS AND BATHING ROOMS.
 WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL
 COMPLY WITH 603. WHERE BATHING ROOMS ARE PROVIDED, EACH
 BATHING ROOM SHALL COMPLY WITH 603.
 EXCEPTIONS: (4.) WHERE MULTIPLE SINGLE USER TOILET
 ROOMS ARE CLUSTERED AT A SINGLE LOCATION, NO MORE THAN
 50 PERCENT OF THE SINGLE USER TOILET ROOMS FOR EACH USE
 (GENDER) AT EACH CLUSTER SHALL BE REQUIRED TO COMPLY
 WITH 603. THE NEW TOLIET ROOMS WILL NEED TO COMPLY WITH
 FIGURE 604.8.1.6 WHEELCHAIR ACCESSIBLE TOLIET
 COMPARTMENT FOR NEW CONSTRUCTION.
  
 ADVISORY 213.2 TOILET ROOMS AND BATHING ROOMS
 EXCEPTIONS 3 AND 4.
 A ?CLUSTER? IS A GROUP OF TOILET ROOMS PROXIMATE TO ONE
 ANOTHER. GENERALLY, TOILET ROOMS IN A CLUSTER ARE
 WITHIN SIGHT OF, OR ADJACENT TO, ONE ANOTHER.
  
 1B) SHOWER ROOM AND COMPARTMENT WILL ALSO NEED TO
 COMPLY WITH 213.2 TOILET ROOMS AND BATHING ROOMS. WHERE
 TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL
 COMPLY WITH 603. WHERE BATHING ROOMS ARE PROVIDED, EACH
 BATHING ROOM SHALL COMPLY WITH 603.
  
 2010 FL ACC CODE 603.1 GENERAL. TOILET AND BATHING
 ROOMS SHALL COMPLY WITH 603.
  
 603.2 CLEARANCES. CLEARANCES SHALL COMPLY WITH 603.2.
  
 603.2.1 TURNING SPACE. TURNING SPACE COMPLYING WITH 304
 SHALL BE PROVIDED WITHIN THE ROOM.
  
 1C) SEE THE 2010 FL ACC CODE FOR ACCESSIBLE SHOWER
 STALLS:
 608.3.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 WHERE A SEAT IS PROVIDED IN STANDARD ROLL-IN TYPE
 SHOWER COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THE
 BACK WALL AND THE SIDE WALL OPPOSITE THE SEAT. GRAB
 BARS SHALL NOT BE PROVIDED ABOVE THE SEAT. WHERE A SEAT
 IS NOT PROVIDED IN STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THREE
 WALLS. GRAB BARS SHALL BE INSTALLED 6 INCHES (150 MM)
 MAXIMUM FROM ADJACENT WALLS.
 OR
 608.3.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, GRAB
 BARS SHALL BE PROVIDED ON THE BACK WALL AND THE SIDE
 WALL FARTHEST FROM THE COMPARTMENT ENTRY. GRAB BARS
 SHALL NOT BE PROVIDED ABOVE THE SEAT. GRAB BARS SHALL
 BE INSTALLED 6 INCHES (150 MM) MAXIMUM FROM ADJACENT
 WALLS.
  
 1D) 2010 FL ACC CODE 608.4 SEATS. A FOLDING OR
 NON-FOLDING SEAT SHALL BE PROVIDED IN TRANSFER TYPE
 SHOWER COMPARTMENTS. A FOLDING SEAT SHALL BE PROVIDED
 IN ROLL-IN TYPE SHOWERS REQUIRED IN TRANSIENT LODGING
 GUEST ROOMS WITH MOBILITY FEATURES COMPLYING WITH
 806.2. SEATS SHALL COMPLY WITH 610.
 EXCEPTION: IN RESIDENTIAL DWELLING UNITS, SEATS SHALL
 NOT BE REQUIRED IN TRANSFER TYPE SHOWER COMPARTMENTS
 PROVIDED THAT REINFORCEMENT HAS BEEN INSTALLED IN WALLS
 SO AS TO PERMIT THE INSTALLATION OF SEATS COMPLYING
 WITH 608.4.
  
 1E) 2010 FL ACC CODE 608.5 CONTROLS. CONTROLS, FAUCETS,
 AND SHOWER SPRAY UNITS SHALL COMPLY WITH 309.4.
  
 1F) FOR SAUNAS PLEASE REVIEW 2010 FL ACC CODE: 612
 SAUNAS AND STEAM ROOMS
 612.1 GENERAL. SAUNAS AND STEAM ROOMS SHALL COMPLY WITH
 612.
 612.2 BENCH. WHERE SEATING IS PROVIDED IN SAUNAS AND
 STEAM ROOMS, AT LEAST ONE BENCH SHALL COMPLY WITH 903.
 DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE REQUIRED BY 903.2.
 EXCEPTION: A READILY REMOVABLE BENCH SHALL BE PERMITTED
 TO OBSTRUCT THE TURNING SPACE REQUIRED BY 612.3 AND THE
 CLEAR FLOOR OR
 GROUND SPACE REQUIRED BY 903.2.
 612.3 TURNING SPACE. A TURNING SPACE COMPLYING WITH 304
 SHALL BE PROVIDED WITHIN SAUNAS AND STEAM ROOMS.
  
 2) SHEET A1-1SHOWS THE NEW ENTRY DOORS AS INSWING DOORS
 PLEASE PROVIDE THE OCCUPANT LOAD FOR THIS SUITE, THE
 2010 FL BUILDING CODE
 1008.1.2 DOOR SWING.
 EGRESS DOORS SHALL BE OF THE PIVOTED OR SIDE-HINGED
 SWINGING TYPE. DOORS SHALL SWING IN THE DIRECTION OF
 EGRESS TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50 OR
 MORE PERSONS OR A GROUP H OCCUPANCY.
  
 3) SHEET A1-1 DOES NOT SHOW ANY RATED WALLS WITHIN THE
 EXIT ACCESS CORRIDOR/ TENANT SEPERATION WALL, IS THE
 DESIGNER OF RECORD CLAIMING THE
 EXCEPTION 4 FROM 709.1.6.?
  
 4) SHEET A1-1 SHOWS WORK WITHIN THE ELEVATOR LOBBY AND
 WILL NEED TO SHOW COMPLIANCE WITH THE 2010 FL EXISTING
 BUILDING CODE 703.1 SCOPE. THE REQUIREMENTS OF THIS
 SECTION ARE LIMITED TO WORK AREAS IN WHICH LEVEL 2
 ALTERATIONS ARE BEING PERFORMED, AND SHALL APPLY BEYOND
 THE WORK AREA WHERE SPECIFIED.
 703.2.1 EXISTING VERTICAL OPENINGS.
 ALL EXISTING INTERIOR VERTICAL OPENINGS CONNECTING TWO
 OR MORE FLOORS SHALL COMPLY WITH THE APPROPRIATE
 SECTIONS OF THE FLORIDA FIRE PREVENTION CODE.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-10-03 Cont ID  
Sent By dhayes Date 2014-10-03 Time   Rev Time 0.00
Received By pleduc Date 2014-10-03 Time 12:32 Sent To  
Notes
2014-10-03 12:33:26THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-02 Cont ID  
Sent By dhayes Date 2014-09-02 Time 15:31 Rev Time 0.00
Received By dhayes Date 2014-09-02 Time 15:31 Sent To  
Notes
2014-09-02 15:31:51DATE: 9/2/2014
 PROJECT: TRUMP PLAZA BATHROOM REMODEL
 PERMIT#: 14090028
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE A FLOOR PLAN INDICATING THE LOCATION OF
 PANEL "A" WPB, FBC 107.2.1
  
 2) PROVIDE A PANEL SCHEDULE AND LOAD CALCULATION FOR
 PANEL "A" MAKING CLEAR ANY EXISTING LOADS TO BE
 RELOCATED OR REMOVED. INDICATE CLEARLY IS IT A MAIN
 BREAKER PANEL OR A MLO. THE PANEL ON THE PLAN INDICATES
 BOTH.
  
 3) PROVIDE A RISER DIAGRAM INDICATING THE "EXISTING
 PANEL A" AND WHERE IT IS FED FROM INDICATING THE
 CAPACITY TO FEED THE ADDITIONAL LOAD.
  
 4) INDICATE ON THE PLANS ANY EXISTING AND/OR NEW
 EMERGENCY LIGHTING PROVIDING A SAFE AND ILLUMINATED
 MEANS OF EGRESS. NFPA 101 SECTION 7.9
  
 5) PROVIDE MANUFACTURER PRODUCT SPECIFICATIONS AND
 INSTALLATION DETAILS FOR SAUNA. INDICATE ACCESS FOR
 RECEPTACLE FEED FOR SAUNA AFTER THE INSTALLATION OF THE
 SAUNA. NEC 110.3, 110.26
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2014-10-03 Cont ID  
Sent By pleduc Date 2014-10-03 Time 12:31 Rev Time 0.00
Received By pleduc Date 2014-10-03 Time 12:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-16 Cont ID  
Sent By tklarge Date 2014-10-16 Time 13:20 Rev Time 0.00
Received By tklarge Date 2014-10-01 Time 10:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-09 Cont ID  
Sent By hmoser Date 2014-09-09 Time 15:21 Rev Time 0.00
Received By hmoser Date 2014-09-02 Time 15:33 Sent To  
Notes
2014-09-02 15:32:06B10

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-10-06 Cont ID  
Sent By hmoser Date 2014-10-06 Time   Rev Time 0.33
Received By rbergsma Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-09-09 Cont ID  
Sent By hmoser Date 2014-09-09 Time 15:21 Rev Time 0.00
Received By hmoser Date 2014-09-09 Time 14:57 Sent To  
Notes
2014-09-09 15:21:00NO MECHANICAL PLANS SUBMITTED AT THIS TIME
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-10-16 Cont ID  
Sent By tklarge Date 2014-10-16 Time 13:20 Rev Time 0.00
Received By tklarge Date 2014-10-16 Time 13:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-06 Cont ID  
Sent By tklarge Date 2014-09-06 Time 07:03 Rev Time 0.00
Received By tklarge Date 2014-09-06 Time 07:01 Sent To  
Notes
2014-09-06 07:08:501) SHT.G0-1 - ACCESSIBILITY NOTE #2 - THE SIDE REACH
 RANGES SHALL COMPLY W/ THE FLORIDA ACCESSIBILITY CODE
 SEC.308.3 THRU 308.3.2.
 2) CLOTHES RODS SHALL COMPLY W/THE REACH RANGES IN
 SECS.308.1 & 803.5 2010 FAC.
 3) SHT. A1-1 - THE NEW SAUNA, RESTROOMS AND SHOWES
 SHALL COMPLY W/ THE 2010 FAC SEC.213.2 & SEC. 603,
 SEC.612, 903, 903.2, AND 304.
 4) SHOW THE FIXTURE CLEARANCES FOR THE WATER CLOSETS IN
 ACCORDANCE W/ THE 2010 FAC SEC. 604.2.
 5) SHT.A1-1 - HOW CAN THE RESTROOMS # 101 & 102 BE
 EXISTING WHEN THESE ROOMS ARE NOT SHOWN ON G1-1 & THE
 PARTITIONS ARE SHOWN AS NEW? WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 6) SUBMIT ACCESSIBILITY DETAILS (ELEVATIONS) FOR THE
 PLUMBING FIXTURES, GRAB BARS,SHOWER SEAT, ETC. WPB
 ADMIN. AMEND. TO 2010 FBC SEC.107.2.1.
 7) DOORS SHALL NOT SWING INTO THE REQUIRED FLOOR SPACE
 REQUIRED FOR ANY FIXTURE OER 2010 FAC SEC.603.2.3. (
 SEE EXCEPTIONS). SHOW THE REQUIRED CLEAR FLOOR SPACE
 FOR THE WATER CLOSETS AND THE LAVATORIES AND THE SHOWER
 AND SAUNA.
 8) THE SEAT AND CONTROLS IN THE SHOWER SHALL COMPLY W/
 FAC SEC.608.2.3, 608.5.3. 608.6 , 610.1., 610.3.
 9) SUBMIT A WATER RISER DIAGRAM FOR THE
 CHANGES/ADDITTIONS BEING MADE TO THE POTABLE WATER
 SYSTEM.
 10) SHT. P1-1 - SIZE ALL SECTIONS OF THE SANITARY RISER
 INCLUDING THE EXISTING.
 11) THE MINIMUM SLOPE ON THE DRAINAGE PIPING SHALL
 COMPLY W/ TABLE 704.1 OF THE 2010 FLORIDA PLUMBING CODE
 DEPENDING ON THE PIPE SIZE. SEE NOTE #4 ON P1-1 UNDER
 "PLUMBING NOTES".
 12) FLORIDA PLUMBING CODE SEC. 909.2.1.- NOT MORE THAN
 ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM
 OF THE DRY-VENTED FIXTURE DRAIN CONNECTION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE-
 CHIEF PLUMBING INSPECTOR
 TEL:561-805-6692
 FAX: 561-805-6676
 E-MAIL: [email protected]
  