2014-09-04 16:26:41 | 1665 PALM BEACH LAKES BOULEVARD | | PERMIT #14081268 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | TYPE I HOOD SYSTEMS SHALL BE DESIGNED TO AUTOMATICALLY | | ACTIVATE THE EXHAUST FAN WHENEVER COOKING OPERATIONS | | OCCUR. THE ACTIVATION OF THE EXHAUST FAN SHALL OCCUR | | THROUGH AN INTERLOCK WITH THE COOKING APPLIANCES, BY | | MEANS OF A HEAT SENSOR. | | | | HOOD SUPPRESSION ACTIVATION SHALL BE TIED INTO THE | | BUILDINGS FIRE ALARM SYSTEM. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | FIRE INVESTIGATOR & INSPECTOR | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | | | | | |
|
|