Plan Review Details - Permit 14081219
Plan Review Stops For Permit 14081219
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-09 Cont ID  
Sent By rlecky Date 2014-09-09 Time 14:57 Rev Time 0.00
Received By rlecky Date 2014-09-09 Time 14:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-09-05 Cont ID  
Sent By scaldero Date 2014-09-05 Time 13:43 Rev Time 0.00
Received By scaldero Date 2014-09-05 Time 13:43 Sent To E
Notes
2014-09-05 13:49:14PERMIT # 14081219
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO: ALL TENANT SPACES IN BUILDING 1855 MUST BE
 TIED INTO THE MASTER FIRE ALARM PANEL FOR THE BUILDING.
 EACH TENANT SPACE WILL BE INTERCONNECTED AND UPON
 ACTIVATION OF AN ALARM IN ANY ONE SPACE, ALL SPACES
 WILL HAVE THEIR NOTIFICATION DEVICES ACTIVATE. AN FACP
 IN A TENANT SPACES WILL HAVE THE "RESET" AND "SILENCE"
 FUNCTIONS DEACTIVED. RESET AND SILENCE OF AN ALARM IS
 LIMITED TO THE MASTER PANEL FOR THE BUILDING AND MAY
 ONLY BE DONE BY A LICENSED FIRE ALARM TECHNICIAN.
 SHOULD IT BE FOUND THAT TENANTS ARE ACCESSING THE
 PANELS IN THE TENANT SPACES AND/OR USING THE "RESET" OR
 "SILENCE" FUNCTIONS, THE OFFICE OF THE FIRE MARSHAL MAY
 REQUIRE THAT THE TENANT FACP BE REMOVED.
  
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-09 Cont ID  
Sent By rlecky Date 2014-09-09 Time 14:57 Rev Time 0.00
Received By rlecky Date 2014-08-28 Time 12:28 Sent To  
Notes
2014-08-28 12:28:59ROUTED TO FIRE