Plan Review Details - Permit 14081199
Plan Review Stops For Permit 14081199
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status N Date 2015-04-30 Cont ID  
Sent By skennedy Date 2015-04-30 Time 10:32 Rev Time 0.00
Received By skennedy Date 2015-04-30 Time 10:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2014-11-18 Cont ID  
Sent By skennedy Date 2014-11-18 Time 08:13 Rev Time 0.00
Received By skennedy Date 2014-11-18 Time 08:12 Sent To  
Notes
2014-11-18 08:16:59SEE PREVIOUS REVIEWS: AT THIS POINT, WE ARE DOWN TO
 SHUTTER INSTALLATION SCHEDULE, WINDOW AND DOOR PRODUCT
 APPROVALS. ADDITIONALLY, THIS WORK (CARPORT ENCLOSURE)
 IS COMPLETE WITH NO INSPECTIONS, SO AN ENGINEERS
 CERTIFICATION LETTER IS REQUIRED FOR THIS WORK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2014-11-04 Cont ID  
Sent By skennedy Date 2014-11-04 Time 16:27 Rev Time 0.00
Received By skennedy Date 2014-11-04 Time 16:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2014-10-10 Cont ID  
Sent By skennedy Date 2014-10-10 Time 11:33 Rev Time 0.00
Received By skennedy Date 2014-10-10 Time 11:33 Sent To  
Notes
2014-10-10 11:34:34SEE PREVIOUS COMMENTS, APPLICANT HAS CHECKED OUT A SET
 TO REGROUP WITH DESIGNER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-09-14 Cont ID  
Sent By skennedy Date 2014-09-14 Time 14:35 Rev Time 0.00
Received By skennedy Date 2014-09-14 Time 14:35 Sent To  
Notes
2014-09-14 14:40:02FBC 2010 3RD REVIEW:
 SEE COMMENTS BELOW FROM PREVIOUS REVIEWS: ALTHOUGH YOU
 HAVE NOW 2 FULL SIZE SETS, THE COMMENTS BELOW STILL
 APPLY.
 SEE THE COMMENTS ON PLUMBING AND ELECTRICAL REVIEW.
  
 FBC 2010, 2ND REVIEW:
  
 THE SUBMITTAL IS INSUFFICIENT IN TERMS OF SETS, FORMS,
 SUBMITTAL DOCUMENTS AND DEFINED SCOPE OF WORK.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
 NO SHUTTER INFOFRMATION HAS BEEN PROVIDED.
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
 YOU HAVE SUBMITTED PHOTO COPIES OF AN OLD PLAN BEARING
 THE TITLE BLOCK OF THE ORIGINAL ENGINEER. IS THIS
 ENGINEER INVOLVED WITH THIS PROJECT? IF NOT, REMOVE THE
 INFOMATION OR INDICATE WHY THIS IS BEING PROVIDED.
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
 THE SMALL SET OF PLANS IS NOT ACCEPTABLE. IT IS A
 REDUCED PHTO COPY.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD AS
 MAY BE APPLICABLE.
 THE PRODUCT INFORMATION IS STILL NOT PROVIDED..
  
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16 OR UTILIZE THE
 SHUTTER INSTALLATION SCHEDULE FORM AVAILABLE AT
 WPB.ORG.
 THIS INFORMATION IS STILL NOT PROVIDED.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-09-10 Cont ID  
Sent By skennedy Date 2014-09-10 Time 10:26 Rev Time 0.00
Received By skennedy Date 2014-09-10 Time 09:01 Sent To  
Notes
2014-09-10 10:31:48FBC 2010, 2ND REVIEW:
  
 THE SUBMITTAL IS INSUFFICIENT IN TERMS OF SETS, FORMS,
 SUBMITTAL DOCUMENTS AND DEFINED SCOPE OF WORK.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
 ONE SET IS A SMALL PHOTO COPY, NO SHUTTER INFOFRMATION
 HAS BEEN PROVIDED.
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
 YOU HAVE SUBMITTED PHOTO COPIES OF AN OLD PLAN BEARING
 THE TITLE BLOCK OF THE ORIGINAL ENGINEER. IS THIS
 ENGINEER INVOLVED WITH THIS PROJECT, IF NOT, REMOVE THE
 INFOMATION OR INDICATE WHY THIS IS BEING PROVIDED.
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
 THE SMALL SET OF PLANS IS NOT ACCEPTABLE. IT IS A
 REDUCED PHTO COPY.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD AS
 MAY BE APPLICABLE.
 THE PRODUCT INFORMATION IS STILL NOT PROVIDED..
  
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16 OR UTILIZE THE
 SHUTTER INSTALLATION SCHEDULE FORM AVAILABLE AT
 WPB.ORG.
 THIS INFORMATION IS STILL NOT PROVIDED.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-02 Cont ID  
Sent By skennedy Date 2014-09-02 Time 11:06 Rev Time 0.00
Received By skennedy Date 2014-09-02 Time 11:06 Sent To  
Notes
2014-09-02 11:32:24FBC 2010, 1ST REVIEW:
  
 THE SUBMITTAL IS INSUFFICIENT IN TERMS OF SETS, FORMS,
 SUBMITTAL DOCUMENTS AND DEFINED SCOPE OF WORK.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD AS
 MAY BE APPLICABLE.
  
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16 OR UTILIZE THE
 SHUTTER INSTALLATION SCHEDULE FORM AVAILABLE AT
 WPB.ORG.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2014-11-17 Cont ID  
Sent By skennedy Date 2014-11-17 Time 08:46 Rev Time 0.00
Received By skennedy Date 2014-11-17 Time 08:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2014-11-05 Cont ID  
Sent By skennedy Date 2014-11-05 Time 11:28 Rev Time 0.00
Received By skennedy Date 2014-11-05 Time 11:28 Sent To  
Notes
2014-11-05 11:29:304TH REVIEW: FBC 2010
  
 SEE PREVIOUS COMMENTS AND MOST RECENT COMMENTS FOR
 BUILDING PLAN REVIEW.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2014-10-10 Cont ID  
Sent By skennedy Date 2014-10-10 Time 11:34 Rev Time 0.00
Received By skennedy Date 2014-10-10 Time 11:34 Sent To  
Notes
2014-10-10 11:34:57SEE PREVIOUS COMMENTS, APPLICANT HAS CHECKED OUT A SET
 TO REGROUP WITH DESIGNER.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-09-14 Cont ID  
Sent By skennedy Date 2014-09-14 Time 14:15 Rev Time 0.00
Received By skennedy Date 2014-09-14 Time 13:46 Sent To  
Notes
2014-09-14 14:21:522ND REVIEW: FBC 2010
  
 SEE IST REVIEW COMMENS BELOW, ADDITIONALLY PLEASE
 PROVIDE A CLEAR DESIGN AND SCOPE OF WORK, THE
 APPLICATION STATES "REPLACE EXISTING WIRE AND ELECTRIC
 BOX. "PANEL 125 AMP 24 LTS RELOCATE." THIS IS UNCLEAR
 AS THE INCLUDED PLANS DO NOT INDICATE THIS SCOPE OF
 WORK. PLEASE PROVIDE CLEAR PLANS AND SCOPE OF WORK.
  
 1ST REVIEW: FBC 2010
  
 THE ELECTRICAL SUBMITTAL IS UNCLEAR. SEE BUILDING
 REVIEW COMMENTS. THE ELECTRICAL DESCRIPTION ON THE
 ATTACHED SUB ELECTRICAL APPLICATION AND THE SEPARATE
 ELECTRICAL PLAN ATTTACHED THERETO ARE NOT COMPATABLE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-10 Cont ID  
Sent By skennedy Date 2014-09-10 Time 10:38 Rev Time 0.00
Received By skennedy Date 2014-09-10 Time 10:26 Sent To  
Notes
2014-09-10 10:42:291ST REVIEW: FBC 2010
  
 THE ELECTRICAL SUBMITTAL IS UNCLEAR. SEE BUILDING
 REVIEW COMMENTS. THE ELECTRICAL DESCRIPTION ON THE
 ATTACHED SUB ELECTRICAL APPLICATION AND THE SEPARATE
 ELECTRICAL PLAN ATTTACHED THERETO ARE NOT COMPATABLE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2015-04-30 Cont ID  
Sent By skennedy Date 2015-04-30 Time 10:32 Rev Time 0.00
Received By skennedy Date 2015-04-30 Time 10:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2014-11-18 Cont ID  
Sent By skennedy Date 2014-11-18 Time 08:17 Rev Time 0.00
Received By skennedy Date 2014-11-13 Time 12:51 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-11-05 Cont ID  
Sent By skennedy Date 2014-11-05 Time 13:03 Rev Time 0.00
Received By skennedy Date 2014-10-14 Time 14:56 Sent To  
Notes
2014-11-05 13:03:035TH REVIEW: FBC 2010
  
 PLEASE SEE PREVIOUS REVIEWS.
  
 ADDITIONAL COMMENTS:
  
 FBC 107 PROVIDE A SITE PLAN. DEMONSTRATE SETBACKS AND
 FIRE SEPARATION.
  
 ALTHOUGH IT IS UNCLEAR FROM THE APPLICATION, THE INTENT
 OF THIS SUBMITTAL IS TO LEGALIZE AN ACCESSORY BUILDING
 THAT WAS APPARENTLY CONSTRUCTED WITHOUT PERMITS. THE
 BUILDING IN QUESTION IS APPROXIMATELY 18.5 X 18.75 FEET
 SQUARE AND IS DIPICTED AS EXISTING ON SHEET 2 OF
 DRAWINGS SUBMITTED ON OCTOBER 10. A SEARCH OF PERMIT
 RECORDS INDICATES SUCH A BUILDING DID NOT EXIST
 ACCORDING TO A SURVEY ON FILE DATED 1998 AND THAT THERE
 IS NO PERMIT RECORD FOR CONSTRUCTING THE BUILDING ANY
 TIME ON FILE. THERE IS NO ASSURANCE THAT THE STRUCTURE
 MEETS ZONING SETBACKS OR REQUIRED SEPARATION FROM OTHER
 STRUCTURES. THE APPLICATION IS ON HOLD BASED ON
 DISCUSSION WITH THE ENGINEER OF RECORD, RIZA ALTAN.
  
 RE SUBMITTAL IS ANTICIPATED TO BE FOR DEMOLITION OF
 THIS STRUCTURE AND FOR IMPROVEMENT OF THE ITEMS SHOWN
 ON SHEET 1 OF THE DRAWINGS.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-10-10 Cont ID  
Sent By skennedy Date 2014-10-10 Time 11:35 Rev Time 0.00
Received By skennedy Date 2014-09-18 Time 18:51 Sent To  
Notes
2014-09-18 18:52:07SENT TO S KENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-09-14 Cont ID  
Sent By skennedy Date 2014-09-14 Time 14:40 Rev Time 0.00
Received By skennedy Date 2014-09-10 Time 11:46 Sent To  
Notes
2014-09-11 11:47:05TO SAK DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-10 Cont ID  
Sent By skennedy Date 2014-09-10 Time 10:42 Rev Time 0.00
Received By skennedy Date 2014-09-08 Time 14:44 Sent To  
Notes
2014-09-08 14:44:59RE-SUBMITTAL SENT TO STEVE KENNEDY'S DESK FOR REVIEW.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-02 Cont ID  
Sent By skennedy Date 2014-09-02 Time 11:11 Rev Time 0.00
Received By skennedy Date 2014-08-27 Time 11:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2014-11-17 Cont ID  
Sent By skennedy Date 2014-11-17 Time 08:46 Rev Time 0.00
Received By skennedy Date 2014-11-17 Time 08:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2014-11-05 Cont ID  
Sent By skennedy Date 2014-11-05 Time 10:12 Rev Time 0.00
Received By skennedy Date 2014-11-05 Time 10:12 Sent To  
Notes
2014-11-05 10:13:193RD REVIEW: FBC 2010
  
 SEE COMMENTS FROM PREVIOUS REVIEWS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-10-10 Cont ID  
Sent By skennedy Date 2014-10-10 Time 11:35 Rev Time 0.00
Received By skennedy Date 2014-10-10 Time 11:35 Sent To  
Notes
2014-10-10 11:35:20SEE PREVIOUS COMMENTS, APPLICANT HAS CHECKED OUT A SET
 TO REGROUP WITH DESIGNER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-14 Cont ID  
Sent By skennedy Date 2014-09-14 Time 14:26 Rev Time 0.00
Received By skennedy Date 2014-09-14 Time 14:22 Sent To  
Notes
2014-09-14 14:34:591ST REVIEW: FBC 2010
  
 A PLUMBING PLAN HAS BEEN ADDED TO THE SUBMITTAL. THE
 DESCRIPTION ON THE PLUMBING PERMIT APPLICATION IS NOT
 CONSISTENT WITH PLANS SUBMITTED. IT SEEMS THE INTENT OF
 THE APPLICATION IS TO DEMOLISH SOME PART OF THE
 ACCESSORY BUILDING, BUT THERE IS NO PLAN INDICATING SO.
 ADDITIONALLY, IT APPEARS THE INTENT IS TO REMODEL THE
 KITCHEN IN THE PRIMARY STRUCTURE. THE PLUMBNG PLAN
 SUBMITTED FOR THIS PART OF THE WORK IS ACCETABLE IN
 DETAIL, BUT NEEDS TO BE SIGNED THE THE PLUMBER IF HE IS
 TAKING RESPONSIBILITY FOR THAT PART OF THE DESIGN PER
 THE SECTION BELOW:
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-11-17 Cont ID  
Sent By skennedy Date 2014-11-18 Time 08:17 Rev Time 0.00
Received By sgraham Date 2014-11-17 Time 16:08 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-11-05 Cont ID  
Sent By sgraham Date 2014-11-05 Time 08:59 Rev Time 0.00
Received By sgraham Date 2014-11-05 Time 08:59 Sent To B
Notes
2014-11-05 09:00:1911/5/14 ZONING FAILED
  
 1. PROVIDE TWO UP TO DATE SURVEYS SHOWING THE LOCATION
 OF THE BUILDING.


Account Summary | Usage Policy | Privacy Policy