Plan Review Details - Permit 14081171
Plan Review Stops For Permit 14081171
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-01-20 Cont ID  
Sent By shill Date 2015-01-20 Time 08:35 Rev Time 0.00
Received By shill Date 2015-01-20 Time 08:35 Sent To  
Notes
2015-01-20 08:54:29****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 INSTALLATION SCHEDULE DID NOT INCLUDE THE FOLLOWING
 INFORMATION:
  
 SHUTTER CONNECTION MOUNTING TYPE (SHOULD CORRELATE WITH
 THE ANCHOR CHARTS ON PAGE 4 OF THE NOA; EITHER C1, C2,
 C3, C4, OR C5)
 ANCHOR SPACING
  
 THEREFORE, INSTALLATION SCHEDULE HAS BEEN REDLINED FOR
 WORST CASE (C5, 5" ANCHOR SPACING)
  
 IF THIS IS NOT ACCEPTABLE, SUBMIT A REVISION WHICH
 INCLUDES A REVISED INSTALLATION SCHEDULE WITH SHUTTER
 CONNECTION MOUNTING TYPE AND ANCHOR SPACING PROPOSED;
 OR, DO NOT PICK UP THIS PERMIT AND RESUBMIT WITH A
 REVISED INSTALLATION SCHEDULE.
  
 LOCATION FOR INFILL DETAIL 2-A1 IS NOT SHOWN ON THE
 FLOOR PLAN. IF THIS IS TO BE USED, SUBMIT A REVISED
 PLAN SHOWING PROPOSED LOCATION.
  
 INFILL DETAIL 2-A1 LACKS A BOND BREAK, FBC 2010
 RESIDENTIAL 703.6.3. IF THIS IS TO BE USED, REVISE
 DETAIL ANS SUBMIT.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-11-20 Cont ID  
Sent By jwitmer Date 2014-11-20 Time 09:32 Rev Time 0.00
Received By jwitmer Date 2014-11-20 Time 08:15 Sent To  
Notes
2014-11-20 09:32:15BUILDING PLAN REVIEW
 PERMIT: 14081171
 ADD: 739 43RD ST.
 CONT: T. H. MOTTLEY
 TEL: (561)502-1986
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: THURS. NOV. 20/2014
 ACTION: DENIED
  
 NOTICE:!!!!!!!!!!
 CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A
 LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE
 FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE
 TIMES FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
 1) IF THE CONTRACTOR IS TAKING RESPONSIBILITY FOR THE
 DESIGN AND DRAFTING OF THE SUBMITTED PLANS, PLEASE
 PRINT NAME, SIGN NAME AND LICENSE NUMBER ON THE PLANS.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2) REPEAT COMMENT, REVISE PLANS TO STATE WHAT SIZE OF
 THE EXISTING WINDOW, TYPE OF WINDOW, (AWNING, CASEMENT,
 DOUBLE HUNG OR SINGLE HUNG WINDOW.
 NOTE THESE DIMENSIONS ARE NOT ONLY REQUIRED TO
 DETERMINE EGRESS REQUIREMENTS FOR SLEEPING ROOMS BUT
 ALSO FOR THE SHUTTER SCHEDULE.
 FBC-R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED. /
 FBC-RFBC-R R308.3.1 IMPACT TEST.
  
 3) REPEAT COMMENT. THE QUESTION HAS BEEN ASKED FOR THE
 EGRESS WINDOWS PROVIDED DIMENSIONS OF 36 X63 IN. PLEASE
 PROVIDE WHAT THE CLEAR OPENING OR VENT SIZE IS OF THE
 EGRESS WINDOWS, THIS HAS NOT BEEN PROVIDED, SHOW
 COMPLIANCE WITH 2010 FBC-R R310.1.1 MINIMUM OPENING
 AREA.
 GRADE FLOOR OPENINGS SHALL HAVE A MINIMUM NET CLEAR
 OPENING OF 5 SQUARE FEET (0.465 M2).
 R310.1.2 MINIMUM OPENING HEIGHT.
 THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES
 (610 MM).
 R310.1.3 MINIMUM OPENING WIDTH.
 THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20 INCHES
 (508 MM).
 2010 FBC-EXISTING BLDG. CODE 604.1 GENERAL.
 MEANS OF EGRESS FOR BUILDINGS UNDERGOING ALTERATION
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 601.1 AND
 THE SCOPING PROVISIONS OF CHAPTER 1 WHERE APPLICABLE.
 EXCEPTION: DOOR AND WINDOW DIMENSIONS. IN RESIDENTIAL
 DWELLINGS AND DWELLING UNITS, A MAXIMUM OF 5 PERCENT
 REDUCTION IN THE CLEAR OPENING DIMENSIONS OF
 REPLACEMENT DOORS AND WINDOWS SHALL BE ALLOWED.
  
 4) REPEAT COMMENT; SHUTTER SCHEDULE, THE SHUTTER
 SCHEDULE SUBMITTED IS ONLY FOR THE SLEEPING ROOM
 WINDOWS. ALL WINDOWS BEING REPLACED WILL REQUIRE
 STORM SHUTTERS SINCE THE PRODUCT APPROVALS SUBMITTED
 ARE NON- IMPACT REATED GLASS. FBC-RFBC-R R308.3.1
 IMPACT TEST.
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4.
  
 FL BLD CODE 2010 SECTION 107.2.4, 1609.1.4, 1715.2 &
 EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A COMPLETE
 INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING
 SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS,
 WALL PRESSURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION TO FACILITATE
 PLAN REVIEW AND PERMIT ISSUANCE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-10-21 Cont ID  
Sent By shill Date 2014-10-21 Time 16:22 Rev Time 0.00
Received By shill Date 2014-10-21 Time 16:22 Sent To  
Notes
2014-10-21 16:24:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE FLOOR PLAN TO INCLUDE ROOM DESIGNATIONS, FBC
 2010 R310, FBC 2010 EXISTING BUILDING 604.1.
  
 2. REVISE FLOOR PLAN TO PROVIDE THE FOLLOWING
 INFORMATION FOR BEDROOMS; FBC R310, FBC EB 604.1. THE
 CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%:
  
 REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW
 IN THE BEDROOMS - AWNING, CASEMENT, SINGLE HUNG?
  
 REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING
 DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH
 EXISTS WHEN THE WINDOW IS FULLY OPEN.
  
 REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING
 DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE
 MANUFACTURER
  
 3. THE NEW FLOOR PLAN DOES NOT INCLUDE OVERALL WINDOW
 SIZES, FBC 2010 RESIDENTIAL 301. PLEASE REVISE.
  
 4. FOR THE SHUTTERS: COMPLETE THE SAMPLE INSTALLATION
 SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE
 COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC R301,
 FBC1609. TWO SETS REQUIRED. THIS FORM IS AVAILABLE IN
 THE LOBBY OR ON THE INTERNET AT
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-10 Cont ID  
Sent By shill Date 2014-09-10 Time 13:21 Rev Time 0.00
Received By shill Date 2014-09-10 Time 13:21 Sent To  
Notes
2014-09-10 13:22:00****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE FLOOR PLAN TO INCLUDE ROOM DESIGNATIONS, FBC
 2010 R310, FBC 2010 EXISTING BUILDING 604.1.
  
 2. REVISE FLOOR PLAN TO PROVIDE THE FOLLOWING
 INFORMATION FOR BEDROOMS; FBC R310, FBC EB 604.1. THE
 CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%:
  
 REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW
 IN THE BEDROOMS - AWNING, CASEMENT, SINGLE HUNG?
  
 REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING
 DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH
 EXISTS WHEN THE WINDOW IS FULLY OPEN.
  
 REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING
 DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE
 MANUFACTURER
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-01-20 Cont ID  
Sent By shill Date 2015-01-20 Time 08:54 Rev Time 0.00
Received By shill Date 2015-01-13 Time 17:50 Sent To  
Notes
2015-01-13 17:50:42TO SHILL DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-11-20 Cont ID  
Sent By jwitmer Date 2014-11-20 Time 09:32 Rev Time 0.00
Received By jwitmer Date 2014-11-20 Time 08:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-21 Cont ID  
Sent By shill Date 2014-10-21 Time 16:24 Rev Time 0.00
Received By shill Date 2014-10-14 Time 14:02 Sent To  
Notes
2014-10-15 14:03:22SENT TO SAMANTHA HILL FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-10 Cont ID  
Sent By shill Date 2014-09-10 Time 13:22 Rev Time 0.00
Received By shill Date 2014-09-10 Time 13:22 Sent To  
Notes
2014-08-27 09:03:20ROUTED TO MISC 1