Plan Review Details - Permit 14081103
Plan Review Stops For Permit 14081103
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-02 Cont ID  
Sent By dhayes Date 2014-09-02 Time 11:37 Rev Time 0.00
Received By dhayes Date 2014-09-02 Time 11:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-08-29 Cont ID  
Sent By dhayes Date 2014-08-29 Time 11:49 Rev Time 0.00
Received By dhayes Date 2014-08-29 Time 11:49 Sent To  
Notes
2014-08-29 11:54:19DATE: 8/29/2014
 PROJECT: CAMPBELL JOB
 PERMIT#: 14060500, REVISION #14081103
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE A THE OCPD AT THE GENERATOR.
 2) PROVIDE A LOAD CALCULATION FOR THE NEUTRAL CONDUCTOR
 FROM THE GENERATOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-02 Cont ID  
Sent By dhayes Date 2014-09-02 Time 11:37 Rev Time 0.00
Received By dhayes Date 2014-09-02 Time 11:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-29 Cont ID  
Sent By dhayes Date 2014-08-29 Time 11:54 Rev Time 0.00
Received By dhayes Date 2014-08-26 Time 17:37 Sent To  
Notes
2014-08-26 17:38:05TO ELEC
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved