Plan Review Details - Permit 14081093
Plan Review Stops For Permit 14081093
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-09-03 Cont ID  
Sent By jwitmer Date 2014-09-03 Time 15:19 Rev Time 0.00
Received By jwitmer Date 2014-09-03 Time 15:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-18 Cont ID  
Sent By rlecky Date 2014-09-18 Time 13:40 Rev Time 0.00
Received By rlecky Date 2014-09-18 Time 10:43 Sent To  
Notes
2014-09-18 13:42:1014081093
 4847 FRED GLADSTONE DRIVE
 GENERATOR PROJECT. ATS BUILDING
  
 REVIEWED WITH THE FOLLOWING COMMENTS NOTED ON THE PLAN.
  
 VERIFY A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE ELECTRIC SERVICE, PANEL BOARDS, TRANSFER
 SWITCHES AND MAIN DISCONNECTING MEANS HAS BEEN
 PROVIDED. NEC 110.16, 110.22
  
 VERIFY THAT THE REQUIRED DEDICATED EQUIPMENT SPACES
 WITH SAFE WORKING CLEARANCE FOR THE ELECTRICAL
 EQUIPMENT, DISCONNECTS AND TRANSFER SWITCHES HAVE BEEN
 PROVIDED. NEC 110.26
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-18 Cont ID  
Sent By cpuell Date 2014-09-18 Time 13:58 Rev Time 0.00
Received By cpuell Date 2014-08-26 Time 12:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-09-14 Cont ID  
Sent By skennedy Date 2014-09-14 Time 15:35 Rev Time 0.00
Received By skennedy Date 2014-09-14 Time 15:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-09-19 Cont ID  
Sent By skennedy Date 2014-09-19 Time 08:12 Rev Time 0.00
Received By skennedy Date 2014-09-18 Time 16:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2014-09-18 Cont ID  
Sent By eschneid Date 2014-09-18 Time 16:22 Rev Time 0.25
Received By eschneid Date 2014-09-18 Time 16:22 Sent To  
Notes
2014-09-18 16:28:24PASSED W/PROVISOS:
  
 1) A PODOCARPUS HEDGE, FIVE (5) FOOT TALL AT INSTALL
 AND GROWN TO THE HEIGHT OF THE GENERATOR, IS REQUIRED
 TO SCREEN THE SOUTH AND WEST SIDES OF THE PROPOSED
 UNDERGROUND TANK PAD AND THE PROPOSED GENERATOR. THE
 OPENING IN THE HEDGE TO PERMIT ACCESS TO THE GENERATOR
 SHALL BE ON THE WEST SIDE. THE EXISTING ARECA PALMS
 SHALL SCREEN THE NORTH SIDE AND THE EXISTING SHED SHALL
 SCREEN THE EAST SIDE. AN OPAQUE FENCE IS NOT REQUIRED
 SO LONG AS THE PREVIOUSLY STATED SCREENING REQUIREMENTS
 REMAIN.
  
 2) THE NEW LANDSCAPE TO SCREEN THE GENERATOR AREA AND
 THE PRE-MANUFACTURED METAL ELECTRICAL EQUIPMENT
 BUILDING SHALL BE INSTALLED AS PART OF PERMIT NO.
 13110778, AS REVISED BY PERMIT REVISION NO. 14090292,
 AND PRIOR TO THE ISSUANCE OF A FINAL (104) INSPECTION
 APPROVAL.
  
 3) SHEET C-101 DOES NOT SHOW THE PAVEMENT BEING REMOVED
 FOR THE SCREEN HEDGE PLANTING AT THE GENERATOR AREA,
 NOR DOES IT SHOW THE D CURB REQUIRED TO PROTECT THE
 LANDSCAPE FROM VEHICULAR ENCROACHMENT. THIS INFORMATION
 IS SHOWN ON PERMIT REVISION NO. 14090292 AND SHALL BE
 INSTALLED IN ACCORDANCE WITH THE APPROVED PERMIT
 REVISION PLANS.
  
 4) THE REVISED LAYOUT SHALL BE SUBMITTED AS PART OF THE
 CURRENT OPEN MINOR PLANNED DEVELOPMENT AMENDMENT TO THE
 PLANNING DIVISION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-09-18 Cont ID  
Sent By eschneid Date 2014-09-18 Time 14:25 Rev Time 0.50
Received By eschneid Date 2014-09-18 Time 14:09 Sent To  
Notes
2014-09-18 14:13:35FAILED
  
 1) A PODOCARPUS HEDGE, FIVE (5) FOOT TALL AT INSTALL
 AND GROWN TO THE HEIGHT OF THE GENERATOR, IS REQUIRED
 TO SCREEN THE SOUTH AND WEST SIDES OF THE PROPOSED
 UNDERGROUND TANK PAD AND THE PROPOSED GENERATOR. THE
 OPENING IN THE HEDGE TO PERMIT ACCESS TO THE GENERATOR
 SHALL BE ON THE WEST SIDE. THE EXISTING ARECA PALMS
 SHALL SCREEN THE NORTH SIDE AND THE EXISTING SHED SHALL
 SCREEN THE EAST SIDE. AN OPAQUE FENCE IS NOT REQUIRED
 SO LONG AS THE PREVIOUSLY STATED SCREENING REQUIREMENTS
 REMAIN.
  
 2) THE NEW LANDSCAPE TO SCREEN THE GENERATOR AREA AND
 THE PRE-MANUFACTURED METAL ELECTRICAL EQUIPMENT
 BUILDING SHALL BE INSTALLED AS PART OF THIS PERMIT AND
 PRIOR TO THE ISSUANCE OF A FINAL (104) INSPECTION
 APPROVAL.
  
 3) SHEET C-101 DOES NOT THE PAVEMENT BEING REMOVED FOR
 THE SCREEN HEDGE PLANTING AT THE GENERATOR AREA, NOR
 DOES IT SHOW THE D CURB REQUIRED TO PROTECT THE
 LANDSCAPE FROM VEHICULAR ENCROACHMENT.
  
 4) STAFF DOES NOT OBJECT TO THE REORIENTATION OF THE
 GENERATOR PAD AND FUEL TANK AREA.
  
 5) THE REVISED LAYOUT SHALL BE SUBMITTED AS PART OF THE
 CURRENT OPEN MINOR PLANNED DEVELOPMENT AMENDMENT TO THE
 PLANNING DIVISION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  