Plan Review Details - Permit 14081009
Plan Review Stops For Permit 14081009
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-09-26 Cont ID  
Sent By rmcdouga Date 2014-09-26 Time 15:13 Rev Time 0.00
Received By rmcdouga Date 2014-09-26 Time 15:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-09-23 Cont ID  
Sent By rmcdouga Date 2014-09-23 Time 08:11 Rev Time 0.00
Received By rmcdouga Date 2014-09-23 Time 07:27 Sent To E
Notes
2014-09-23 07:54:132010 FBC
  
 DENIED BY BUILDING
  
 1) THE GENERAC MODEL QT 27 - 27KW GENERATOR IS NOT
 LISTED ON THE SIGNED AND SEALED ENGINEERED DRAWINGS AS
 ONE OF THE GENERATORS THAT THE AMERICAST PAD CAN BE
 USED WITH. SUBMIT SIGNED AND SEALED DRAWINGS FOR THE
 AMERICAST PAD THAT IS FOR THE GENERAC MODEL QT 27
 GENERATOR. FBC 107.2.1 AND FAC61G15-23.002.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-04 Cont ID  
Sent By rmcdouga Date 2014-09-04 Time 07:06 Rev Time 0.00
Received By rmcdouga Date 2014-09-04 Time 07:06 Sent To E
Notes
2014-09-04 07:31:562010 FBC
  
 DENIED BY BUILDING
  
 1) IF THERE IS A MIAMI-DADE OR STATE OF FLORIDA PRODUCT
 APPROVAL FOR THE AMERICAST GENERATOR PAD AS REQUIRED BY
 DCA RULE 9N-3, PLEASE SUBMIT IT. OTHERWISE, THE
 DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S
 HANDWRITTEN SIGNATURE AND SEAL AFFIXED PER
 FAC61G15-23.002.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-24 Cont ID  
Sent By dhayes Date 2014-09-24 Time 13:09 Rev Time 0.00
Received By dhayes Date 2014-09-24 Time 13:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-09 Cont ID  
Sent By dhayes Date 2014-09-09 Time 09:41 Rev Time 0.00
Received By dhayes Date 2014-09-09 Time 09:32 Sent To  
Notes
2014-09-09 11:28:04DATE: 9/9/2014
 PROJECT: GENERATOR
 PERMIT#: 14081009
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE ELECTRICAL RESER DIAGRAM INDICATES TWO SEPARATE
 200AMP SERVICE ENTRANCE FEEDERS TO TO SEPARATE 200 AMP
 PANELS. NEC 310.16 CALLS FOR A MINIMUM 3/0CU FEEDER FOR
 200AMP.
 NEC 310.15(B)(6) IS ONLY FOR A SINGLE SERVICE ENTRANCE.
 REVISE PLAN TO INDICATE FULL SIZE SERVICE ENTRANCE
 CONDUCTOR SETS.
  
 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1.
 REVISE THE PLANS WITH THE SIGNATURE OF THE QUALIFIER OR
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-24 Cont ID  
Sent By dhayes Date 2014-09-24 Time 13:09 Rev Time 0.00
Received By dhayes Date 2014-09-20 Time 09:38 Sent To  
Notes
2014-09-20 09:38:56INCOMING SENT TO R. MCDOUGALS DESK . JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-09 Cont ID  
Sent By dhayes Date 2014-09-09 Time 09:41 Rev Time 0.00
Received By dhayes Date 2014-08-22 Time 13:15 Sent To  
Notes
2014-08-22 13:15:15ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2014-08-25 Cont ID  
Sent By sgraham Date 2014-08-25 Time 11:51 Rev Time 0.00
Received By sgraham Date 2014-08-25 Time 11:51 Sent To E
Notes
***NONE***