Plan Review Details - Permit 14081009
Plan Review Stops For Permit 14081009 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2014-09-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-09-26 |
Time |
15:13 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-09-26 |
Time |
15:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2014-09-23 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-09-23 |
Time |
08:11 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-09-23 |
Time |
07:27 |
Sent To |
E |
|
Notes |
2014-09-23 07:54:13 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE GENERAC MODEL QT 27 - 27KW GENERATOR IS NOT | | LISTED ON THE SIGNED AND SEALED ENGINEERED DRAWINGS AS | | ONE OF THE GENERATORS THAT THE AMERICAST PAD CAN BE | | USED WITH. SUBMIT SIGNED AND SEALED DRAWINGS FOR THE | | AMERICAST PAD THAT IS FOR THE GENERAC MODEL QT 27 | | GENERATOR. FBC 107.2.1 AND FAC61G15-23.002. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-09-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-09-04 |
Time |
07:06 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-09-04 |
Time |
07:06 |
Sent To |
E |
|
Notes |
2014-09-04 07:31:56 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) IF THERE IS A MIAMI-DADE OR STATE OF FLORIDA PRODUCT | | APPROVAL FOR THE AMERICAST GENERATOR PAD AS REQUIRED BY | | DCA RULE 9N-3, PLEASE SUBMIT IT. OTHERWISE, THE | | DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S | | HANDWRITTEN SIGNATURE AND SEAL AFFIXED PER | | FAC61G15-23.002. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2014-09-24 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-09-24 |
Time |
13:09 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-09-24 |
Time |
13:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2014-09-09 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-09-09 |
Time |
09:41 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-09-09 |
Time |
09:32 |
Sent To |
|
|
Notes |
2014-09-09 11:28:04 | DATE: 9/9/2014 | | PROJECT: GENERATOR | | PERMIT#: 14081009 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) THE ELECTRICAL RESER DIAGRAM INDICATES TWO SEPARATE | | 200AMP SERVICE ENTRANCE FEEDERS TO TO SEPARATE 200 AMP | | PANELS. NEC 310.16 CALLS FOR A MINIMUM 3/0CU FEEDER FOR | | 200AMP. | | NEC 310.15(B)(6) IS ONLY FOR A SINGLE SERVICE ENTRANCE. | | REVISE PLAN TO INDICATE FULL SIZE SERVICE ENTRANCE | | CONDUCTOR SETS. | | | | 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS | | TO FBC 107.2.1. | | REVISE THE PLANS WITH THE SIGNATURE OF THE QUALIFIER OR | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-09-24 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-09-24 |
Time |
13:09 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-09-20 |
Time |
09:38 |
Sent To |
|
|
Notes |
2014-09-20 09:38:56 | INCOMING SENT TO R. MCDOUGALS DESK . JW |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-09-09 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-09-09 |
Time |
09:41 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-08-22 |
Time |
13:15 |
Sent To |
|
|
Notes |
2014-08-22 13:15:15 | ROUTED TO ZONING |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2014-08-25 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2014-08-25 |
Time |
11:51 |
Rev Time |
0.00 |
Received By |
sgraham |
Date |
2014-08-25 |
Time |
11:51 |
Sent To |
E |
|
Notes |
|
|
|