Plan Review Details - Permit 14080918
Plan Review Stops For Permit 14080918
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-02 Cont ID  
Sent By jwitmer Date 2014-10-02 Time 07:32 Rev Time 0.00
Received By jwitmer Date 2014-10-02 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-28 Cont ID  
Sent By jwitmer Date 2014-08-28 Time 08:54 Rev Time 0.00
Received By jwitmer Date 2014-08-28 Time 06:45 Sent To  
Notes
2014-08-28 08:08:04BUILDING PLAN REVIEW
 PERMIT: 14080918
 ADD: 1016 CLARE AVE SUITE # 2
 CONT: FRED BLACK & ASSOC
 TEL: (561)547-4772
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUG. 28/2014
 ACTION: DENIED
  
 1) THE PLANS INDICATE THIS TO BE A LEVEL II ALTERATION.
 PLEASE REVIEW PERMIT # 13110818 THE AREA WHERE THE WORK
 IS OCCURRING WAS INDICATED AS STORAGE, THIS WILL BE
 CONSIDERED A CHANGE OF OCCUPANCY UNDER THE 2010 FL
 EXISTING BUILDING CODE AND REVIEWED TO CHAPTER 9,
 PLEASE UPDATE PLANS. 2010 EXISTING BUILDING CODE LEVEL
 II 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, :
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503)
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD : GROSS/ NET LIFE SAFETY PLAN
 MEANS OF EGRESS :EXITS
  
 2) SHEET A1.0 DOES NOT INDICATE WHERE THE 2ND MEANS OF
 EGRESS IS LOCATED. THERE IS A NEW DOORWAY CUT BACK INTO
 WHAT SHOWS AS A SMALL ROOM THEN INTO A STORAGE ROOM,
 PLEASE REVIEW EGRESS THROUGH MERCANTILE STORAGE ROOMS.
 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
 1. EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH
 ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE
 SUCH ADJOINING ROOMS OR AREAS AND THE AREA SERVED ARE
 ACCESSORY TO ONE OR THE OTHER, ARE NOT A GROUP H
 OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS
 TRAVEL TO AN EXIT.
 EXCEPTION: MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 ADJOINING OR INTERVENING ROOMS OR SPACES IN A GROUP H,
 S OR F OCCUPANCY WHEN THE ADJOINING OR INTERVENING
 ROOMS OR SPACES ARE THE SAME OR A LESSER HAZARD
 OCCUPANCY GROUP.
 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
 EXCEPTIONS:
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
  
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
  
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
  
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
  
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION
 THAT WILL MAINTAIN THE REQUIRED WIDTH AND LEAD DIRECTLY
 FROM THE RETAIL AREA TO THE EXIT WITHOUT OBSTRUCTIONS.
  
 3) SHEET A1.0 THE RAMP DOES NOT INDICATE HOW COMPLIANCE
 WITH RAMP EDGE PROTECTION WILL COMPLY. 2010 FL
 ACCESSIBILITY CODE 405.9.
  
 4) SHEET A1.0 PLEASE PROVIDE HOW COMPLIANCE WITH 2010
 FL ACCESSIBILITY CODE 243.1 GENERAL. WHERE SHOOTING
 FACILITIES WITH FIRING POSITIONS ARE DESIGNED AND
 CONSTRUCTED AT A SITE, AT LEAST 5 PERCENT, BUT NO FEWER
 THAN ONE, OF EACH TYPE OF FIRING POSITION SHALL COMPLY
 WITH 1010.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-10-02 Cont ID  
Sent By rlecky Date 2014-10-02 Time 12:06 Rev Time 0.00
Received By rlecky Date 2014-10-02 Time 11:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-11 Cont ID  
Sent By rlecky Date 2014-09-11 Time 10:32 Rev Time 0.00
Received By rlecky Date 2014-09-11 Time 10:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-08-25 Cont ID  
Sent By pleduc Date 2014-08-25 Time   Rev Time 0.00
Received By pleduc Date 2014-08-25 Time 13:20 Sent To  
Notes
2014-08-25 16:50:43THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE ADD EXIT SIGNS WHERE INDICATED ON THE FLOOR
 PLAN, A 1.0 AND ELECTRICAL PLAN, E 2.1.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-03 Cont ID  
Sent By hmoser Date 2014-10-03 Time 11:35 Rev Time 0.00
Received By hmoser Date 2014-09-26 Time 15:43 Sent To  
Notes
2014-09-26 15:43:21INCOMING SENT TO B-11.JW
 THE PLANS WERE SUBMITTED WITH THE VOIDED SHEETS
 INCLUDED INTHE SET. THEY HAD TO BE REMOVED FROM THE
 SET, AS REQUESTED IN THE PLAN REVIEW COMMENTS.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-25 Cont ID  
Sent By skennedy Date 2014-09-25 Time 15:59 Rev Time 0.00
Received By skennedy Date 2014-08-22 Time 14:21 Sent To  
Notes
2014-08-23 14:28:05INCOMING SENT TO B-02. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2014-10-03 Cont ID  
Sent By jwitmer Date 2014-10-03 Time 16:22 Rev Time 0.00
Received By jwitmer Date 2014-10-03 Time 16:22 Sent To  
Notes
2014-10-03 16:23:34THE PLANS WERE SUBMITTED TO P. B. C. IMPACT FEE OFFICE,
 PLANS STAMPED NO FEES DUE. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-10-02 Cont ID  
Sent By jwitmer Date 2014-10-02 Time 07:32 Rev Time 0.00
Received By jwitmer Date 2014-10-02 Time 07:32 Sent To  
Notes
2014-10-02 07:32:49BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-08-28 Cont ID  
Sent By jwitmer Date 2014-08-28 Time 07:07 Rev Time 0.00
Received By jwitmer Date 2014-08-28 Time 07:06 Sent To  
Notes
2014-08-28 07:06:57BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-10-03 Cont ID  
Sent By hmoser Date 2014-10-03 Time 11:35 Rev Time 0.00
Received By hmoser Date 2014-10-03 Time 11:29 Sent To  
Notes
2014-10-03 11:35:03PASS PROVISO
  
 REFER TO SECTION 602.2.1 SUPPLY AIR SYSTEMS
 606.3 INSTALLATION AND 606.4.1 SUPERVISION
 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX - 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-09-04 Cont ID  
Sent By hmoser Date 2014-09-04 Time 11:23 Rev Time 0.00
Received By hmoser Date 2014-09-04 Time 08:09 Sent To  
Notes
2014-09-04 11:23:50PASS PROVISO
  
 REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM, 606.3
 INSTALLATION, AND
 606.4.1 SUPERVISION 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-09-11 Cont ID  
Sent By tklarge Date 2014-09-11 Time 10:35 Rev Time 0.00
Received By tklarge Date 2014-09-06 Time 10:28 Sent To  
Notes
2014-09-06 10:33:111) EXISTING PLUMBING FIXTURES ARE ADEQUATE IN QUANTITY
 TO SATISFY THE REQUIREMENTS OF TABLE 403.1 OF THE 2010
 FLORIDA PLUMBING CODE. NO ADDITIONAL FIXTURES ARE
 REQUIRED. 9/6/14.
  
 PLUMBING PLAN REVIEW
 TIM LARGE-
 CHIEF PLUMBING INSPECTOR
 TEL:561-805-6692
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-25 Cont ID  
Sent By avann Date 2014-09-25 Time 15:52 Rev Time 0.00
Received By ajones Date 2014-09-25 Time 15:52 Sent To  
Notes
2014-09-11 15:07:239/11/14