Plan Review Details - Permit 14080903
Plan Review Stops For Permit 14080903
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-01-29 Cont ID  
Sent By shill Date 2015-01-29 Time 15:02 Rev Time 0.00
Received By shill Date 2015-01-21 Time 09:00 Sent To  
Notes
2015-01-29 15:24:064TH REVIEW: FBC 2010
  
 IN THIS RE-SUBMITTAL, THE APPLICANT HAS PROVIDED A DCA
 PLAN MDS007344. THE DCA COVER LETTER WAS NOT PROVIDED,
 AND THE PLANS DO NOT HAVE THE DCA STAMP ON THEM. I WAS
 UNABLE TO LOCATE THE PLAN ON FLORIDABUILDING.ORG. IT IS
 UNCLEAR HOW THIS PLAN RELATES TO THE INSIGNAI
 PREVIOUSLY PROVIDED.
  
 THE PLAN SUBMITTED IS FOR EDUCATIONAL OCCUPANCY;
 THEREFORE, THIS HAS BEEN REVIEWED FOR EDUCATIONAL USE
 ONLY. PLEASE ADDRESS. NO INFORMATION WAS PROVIDED
 REGARDING THE PROPOSED USE OF THIS STRUCTURE. ALTHOUGH
 APPLICATION STATES THIS IS "EXISTING" IT IS NOT
 CONSIDERED "EXISTING" IF A PERMIT WAS NOT OBTAINED. IT
 APPEARS THAT THIS WAS INSTALLED AFTER 2012.
  
 FROM PREVIOUS LISTS, BE ADVISED THAT THE FOUNDATION
 PLAN DOES NOT COMPLY WITH FBC R403.1.4 MINIMUM DEPTH.
 ALL EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12
 INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
 NO ADDITIONAL INFORMATION WAS PROVIDED.
  
 ELECTRICAL IS SHOWN ON THE MODULAR PLAN, AS WELL AS AN
 OPTIONAL BATHROOM, BUT NO INFORMATION PROVIDED
 REGARDING ELECTRICAL CONNECTION OR PLUMBING CONNECTION
 FOR REVIEW. PLANS WILL BE ROUTED FOR ELECTRICAL AND
 PLUMBING REVIEWS AFTER THIS INFORMATION IS SUBMITTED.
  
 FROM PREVIOUS THREE REVIEWS, FBC 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 NO IMPACT PROTECTION SHOWN FOR THE MODULAR, PLEASE
 ADDRESS FBC 2010 RESIDENTIAL 301.2.1.2, FBC 1609.1.4.
 (OCCUPANCY CLASSIFICATION HAS NOT BEEN DETERMINED.) IF
 REMOVABLE SHUTTERS ARE PROPOSED, PROVIDE PRODUCT
 APPROVALS AND THE SAMPLE INSTALLATION SCHEDULE (OR ALL
 INFORMATION IN ANOTHER FORMAT):
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 WHEN RESUBMITTING, PLEASE PROVIDE A RESPONSE LETTER
 STATING HOW EACH ITEM WAS ADDRESSED (THIS MAY BE DONE
 BY CONTRACTOR). ENGINEER IS TO ACKNOWLEDGE RECEIPT OF
 THE STRUCTURAL COMMENT.
  
 SAMANTHA M. HILL
 BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-12-30 Cont ID  
Sent By skennedy Date 2014-12-30 Time 08:02 Rev Time 0.00
Received By skennedy Date 2014-12-30 Time 08:02 Sent To  
Notes
2014-12-30 09:31:593RD REVIEW: FBC 2010
  
 IN THIS RE-SUBMITTAL, THE APPLICANT HAS PROVIDED ONLY A
 LEGACY DCA INSIGNIA # IVE-002378 FOR THE MODULAR
 BUILDING. I COULD NOT LOCATE THE PLAN ON
 FLORIDABUILDING.ORG. PLEASE UPDATE THE VALUE OF THE
 IMPROVEMENT AND PROVIDE THE PLAN. ADDITIONALLY, BE
 ADVISED THAT THE FOUNDATION PLAN DOES NOT COMPLY WITH
 FBC R403.1.4 MINIMUM DEPTH. ALL EXTERIOR FOOTINGS SHALL
 BE PLACED AT LEAST 12 INCHES (305 MM) BELOW THE
 UNDISTURBED GROUND SURFACE.
  
 THE BELOW COMMENTS FROM THE SECOND REVIEW ARE NOT
 ADDRESSED.
  
 THE SUBMITTED PLAN IS ONLY A FOUNDATION PLAN AND SURVEY
 SHOWING AN UNIDENTIFIED 36'X23.5 MODULAR BUILDING.
 PROVIDE A PLAN FOR THE BUILDING.PROVIDE ANY OTHER PLANS
 SUCH AS ELECTRICAL, PLUMBING, AIR CONDONDITIONING AS
 MAY BE NEEDED.
  
 PROVIDE PLANS PER FBC 107.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-10-05 Cont ID  
Sent By skennedy Date 2014-10-05 Time 12:11 Rev Time 0.00
Received By skennedy Date 2014-10-05 Time 12:11 Sent To  
Notes
2014-10-05 12:18:152ND REVIEW: FBC 2010
  
 THE SUBMITTED PLAN IS ONLY A FOUNDATION PLAN AND SURVEY
 SHOWING AN UNIDENTIFIED 36'X23.5 MODULAR BUILDING.
 PROVIDE A PLAN FOR THE BUILDING.PROVIDE ANY OTHER PLANS
 SUCH AS ELECTRICAL, PLUMBING, AIR CONDONDITIONING AS
 MAY BE NEEDED.
  
 PROVIDE PLANS PER FBC 107.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-22 Cont ID  
Sent By skennedy Date 2014-08-22 Time 14:30 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
2014-08-22 14:33:101ST REVIEW: FBC 2010
  
 PROVIDE PLANS PER FBC 107.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date 2015-02-06 Time   Sent To  
Notes
2015-02-24 08:38:27R22
  
2015-02-07 06:33:49INCOMING SENT TO S. HILLS' DESK.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-01-29 Cont ID  
Sent By shill Date 2015-01-29 Time 15:24 Rev Time 0.00
Received By shill Date 2015-01-09 Time 08:45 Sent To  
Notes
2015-01-21 09:00:421/21 TO SH DESK FOR BUILDING REVIEW
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-12-30 Cont ID  
Sent By skennedy Date 2014-12-30 Time 09:34 Rev Time 0.00
Received By skennedy Date 2014-12-29 Time 09:37 Sent To  
Notes
2014-12-29 09:38:03TO SAK DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-05 Cont ID  
Sent By skennedy Date 2014-10-05 Time 12:11 Rev Time 0.00
Received By skennedy Date 2014-09-24 Time   Sent To  
Notes
2014-09-26 15:42:53TO MISC 2 BOX.
2014-09-24 14:03:23ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-22 Cont ID  
Sent By skennedy Date 2014-08-22 Time 14:33 Rev Time 0.00
Received By skennedy Date 2014-08-22 Time 07:26 Sent To  
Notes
2014-08-22 07:26:28INCOMING SENT TO ZONING. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-03-01 Cont ID  
Sent By tklarge Date 2015-03-01 Time 08:15 Rev Time 0.00
Received By tklarge Date 2015-02-28 Time 11:24 Sent To  
Notes
2015-03-01 08:14:551)THE OCCUPANCY NOTED ON THE PLANS IS SHOWN AS
 EDUCATIONAL. TABLE 403.1 OF THE FL. PLUMBING CODE
 REQUIRES SEPARATE FACILITIES FOR THE MALES AND FEMALES.
 A MINIMUM OF ONE WATER CLOSET AND ONE LAVATORY SHALL BE
 PROVIDED FOR THE MALES AND ALSO THE FEMALES. A SERVICE
 SINK IS ALSO REQUIRED AND A DRINKING FOUNTAIN.
 2) A MINIMUM OF TWO DRINKING FOUNTAINS SHALL BE
 SUPPLIED IN ACCORDANCE WITH THE 2010 FL. ACCESSIBILITY
 CODE SEC. 211.2
 3) THE BUILDING SHALL COMPLY WITH FL. STATUTE 553.415
 AND SECTION 428 OF THE 2010 FL. BUILDING CODE. APPROVED
 PLANS AND SPECIFICATIONS SHALL BE EVIDENCED BY A LETTER
 OF CERTIFICATION FROM THE AGENCY AUTHORIZED TO PERFORM
 INSPECTIONS OF OR REVIEW PLANS FOR MANUFACTURED
 BUILDINGS AS PROVIDED IN FL. ADMIN. RULE 9B-1 PER THE
 2010 FBC SEC.428.2, 428.4.2.
 4) SHT. A1 SHOWS A CITY WATER CONNECTION TO THE TRAILER
 AND THERE IS ALSO AN 8 1/2' X 11' DRAWING STAPLED TO
 THE PLAN SHOWING THE SOURCE OF WATER BEING A RAIN
 BARREL. CLARIFY. IF A RAIN BARREL WILL BE THE WATER
 SOURCE, SUBMIT A COMPLETE PIPNG PLAN INCLUDING THE PUMP
 SHOWING HOW THE WATER WILL BE PIPED TO THE TRAILER AND
 HOW THE PRESSURE WILL BE MAINTAINED. WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 5) ONLY POTABLE WATER SHALL BE SUPPLIED TO PLUMBING
 FIXTURES THAT PROVIDE WATER FOR DRINKING , BATHING, OR
 CULINARY PURPOSES PER THE 2010 FPC SEC. 602.2. SIGNS
 SHALL BE POSTED AT ANY FIXTURE UTILIZING NON-POTABLE
 WATER THAT THE WATER IS NON-POTABLE AND NOT FOR DRINING
 PURPOSES.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2014-12-22 Cont ID  
Sent By aaponte Date 2014-12-22 Time 16:09 Rev Time 0.00
Received By aaponte Date 2014-12-22 Time 16:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2014-09-26 Cont ID  
Sent By aaponte Date 2014-09-26 Time 15:38 Rev Time 0.00
Received By aaponte Date 2014-09-26 Time 15:38 Sent To  
Notes
2014-09-26 15:42:211. PLEASE SUBMIT DRAWINGS WITH NEW STRUCTURE ON SITE.
 IS THE USE A RESIDENTIAL UNIT?
 2. A NEW PARKING SPACE SHALL BE PROVIDED FOR THE NEW
 UNIT.
 3. WHAT IS THE VALUE OF THE NEW STRUCTURE ON SITE?
 4. LANDSCAPE REQUIREMENTS MAY BE TRIGGERED BY THE NEW
 STRUCTURE ON SITE. TO BE DETERMINED BY VALUE
 INFORMATION.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-08-22 Cont ID  
Sent By sgraham Date 2014-08-22 Time 09:18 Rev Time 0.00
Received By sgraham Date 2014-08-22 Time 09:18 Sent To B
Notes
2014-08-22 09:19:148/22/14 ZONING FAILED
  
 1.NO PLANS INCLUDED WITH PERMIT APPLICATION.