2014-08-28 07:55:23 | DATE: 8/28/2014 |
| PROJECT: HOSPICE OF PALM BEACH |
| PERMIT#: 14080809 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: PROVISO |
| |
| 1) FBC-ENERGY |
| 505.2 LIGHTING CONTROLS (MANDATORY). |
| LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS |
| REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND |
| 505.2.4. |
| |
| 2) NEC 600.5 |
| EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY |
| A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT |
| SUPPLIES NO OTHER LOAD. |
| |
| 3) ALL EXTERIOR LIGHTING ( INCLUDING SIGNS AND LED |
| ACCENT LIGHTING) NOT EXEMPTED BY FBC 505.1 SHALL HAVE |
| AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN NOT |
| REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME CLOCK OR |
| ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES SHALL BE |
| CAPABLE OF RETAINING PROGRAMING DURING A LOSS OF POWER |
| FOR A MINIMUM OF 10 HOURS. FBC-E 505.2.4 |
| |
| 4) PROVIDE A PANEL SCHEDULE INDICATING THE AVAILABLE |
| CIRCUITS FOR THE PROJECT. INDICATE THE CIRCUITING ON |
| THE SITE PLAN. WPB FBC 107.2.1 |
| |
| 5) INDICATE LOCATIONS AND PROVIDE ACCESS FOR REMOTE |
| DRIVERS. |
| |
| 6) LISTING AND LABELING OF EQUIPMENT IS REQUIRED BY AN |
| APPROVED TESTING LAB. IN JUDGING EQUIPMENT, |
| CONSIDERATION SUCH AS THE FOLLOWING SHALL BE EVALUATED: |
| SUITABILITY FOR INSTALLATION AND USE IN CONFORMITY WITH |
| THE PROVISIONS OF THIS CODE. NEC 110.3(A)(1 THRU 8) |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |