Plan Review Details - Permit 14080344
Plan Review Stops For Permit 14080344
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-09-08 Cont ID  
Sent By   Date 2014-09-08 Time   Rev Time 0.00
Received By tklarge Date 2014-09-08 Time 09:21 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-08-20 Cont ID  
Sent By tklarge Date 2014-08-20 Time 11:57 Rev Time 0.00
Received By tklarge Date 2014-08-20 Time 12:04 Sent To  
Notes
2014-08-20 12:13:191ST REVIEW 2010 FBC-
 1) SUBMITTED GAS TABLE IS FROM THE 2004 FBC. SUBMIT
 APPLICABLE GAS TABLE FROM THE 2010 FBC GAS CODE.
 2) SUBMIT ADDITIONAL SPECS FOR THE GENERATOR. GENERATOR
 SHALL COMPLY W/ UL 2200 & NFPA 37.
 3) GENERATOR SHALL BE 5 FT. FROM THE BUILDING WALL PER
 NFPA 37.
 4)SHOW THE LOCATION OF ALL BUILDING OPENINGS IN
 RELATION TO THE GENERATOR EXHAUST. EXHAUST SHALL BE
 MIN. 10 FT. FROM BUILDING OPENINGS.
  
 T. LARGE
 561-805-6692

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-20 Cont ID  
Sent By   Date 2014-09-08 Time 12:13 Rev Time 0.00
Received By tklarge Date 2014-08-08 Time 14:35 Sent To  
Notes
2014-08-08 14:35:15ROUTED TO PLUMBING $5000 & UNDER