Plan Review Details - Permit 14080339
Plan Review Stops For Permit 14080339
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-09-11 Cont ID  
Sent By jgomez Date 2014-09-11 Time 18:13 Rev Time 0.00
Received By jgomez Date 2014-09-11 Time 17:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-25 Cont ID  
Sent By dhayes Date 2014-09-25 Time 07:54 Rev Time 0.00
Received By dhayes Date 2014-09-25 Time 07:31 Sent To  
Notes
2014-09-25 09:47:12DATE: 9/25/2014
 PROJECT: KITCHEN AND BATH REMODEL
 PERMIT#: 14080339
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) LIGHTING OUTLETS SHALL BE INSTALLED WHERE SPECIFIED
 IN NEC 210.70(A)1,2,3
 (1) HABITABLE ROOMS. AT LEAST ONE WALL
 SWITCH?CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED IN
 EVERY HABITABLE ROOM AND BATHROOM.
 (2) ADDITIONAL LOCATIONS. ADDITIONAL LIGHTING OUTLETS
 SHALL BE INSTALLED IN ACCORDANCE WITH (A)(2)(A),
 (A)(2)(B), AND (A)(2)(C).
 (3) STORAGE OR EQUIPMENT SPACES. FOR ATTICS, UNDERFLOOR
 SPACES, UTILITY ROOMS, AND BASEMENTS, AT LEAST ONE
 LIGHTING OUTLET CONTAINING A SWITCH OR CONTROLLED BY A
 WALL SWITCH SHALL BE INSTALLED WHERE THESE SPACES ARE
 USED FOR STORAGE OR CONTAIN EQUIPMENT REQUIRING
 SERVICING.
  
 2) FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT
 GRADE LEVEL AND LOCATED NOT MORE THAN 2.0 M (61.2 FT)
 ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF
 THE DWELLING. NEC 210.52(E)(3)
  
 3) METAL FRAMING MEMBERS SHALL BE BONDED TO THE
 EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY
 ENERGIZE THE FRAMING AND BE SIZED IN ACCORDANCE WITH
 THE NEC TABLE 250.122. FOR THE PURPOSE OF THIS SECTION,
 A GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING
 SHALL BE PERMITTED.
  
 4) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
 FOR PERSONNEL. ALL OUTLETS IN THE GARAGE SHALL BE GFCI
 PROTECTED. NEC 210.8.
  
 5) FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT
 GRADE LEVEL AND LOCATED NOT MORE THAN 2.0 M (61.2 FT)
 ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF
 THE DWELLING. NEC 210.52(E)(3)
  
 6) OCCUPIABLE BALCONIES AND PORCHES OVER 20 SQ FT MUST
 NOW HAVE A RECEPTACLE OUTLET (GFCI PROTECTED)
 (210.52(E)(3).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-16 Cont ID  
Sent By dhayes Date 2014-09-16 Time 10:35 Rev Time 0.00
Received By dhayes Date 2014-09-16 Time 10:35 Sent To  
Notes
2014-09-16 11:02:38DATE: 9/16/2014
 PROJECT: BATHROOM AND KITCHEN RENNOVATION
 PERMIT#: 14080339
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) FLOOR PLAN TO BE REVISED TO SHOW ALL REQUIRED
 RECEPTACLE OUTLETS IN THE KITCHEN AND BATH. BATHROOM
 BRANCH CIRCUITS IN ADDITION TO THE NUMBER OF BRANCH
 CIRCUITS REQUIRED BY OTHER PARTS OF THIS SECTION, AT
 LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO
 SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS
 SHALL HAVE NO OTHER OUTLETS. PLEASE INDICATE COMPLIANCE
 WITH THE NEC ARTICLE 210.11(C)(3)
  
 2) KITCHEN COUNTER TOP RECEPTACLES SHALL BE SUPPLIED BY
 NO FEWER THAN TWO SMALL APPLIANCE BRANCH CIRCUITS. NEC
 210.52(B)(3) AT LEAST ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH ISLAND COUNTERTOP SPACE WITH A LONG
 DIMENSION OF 24" OR GREATER AND A SHORT DIMENSION OF
 12" OR GREATER. NEC 210.52(C)(2)
  
 3) INDICATE OR VERIFY THE INSTALLATION OF SMOKE AND CO
 DETECTORS AT ALL SLEEPING ROOMS. WHEN ALTERATIONS,
 REPAIRS, OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN
 ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN
 EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL
 BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR
 NEW DWELLINGS. FBC-RESIDENTIAL 314 AND 315. REVISE PLAN
 TO INDICATE OR VERIFY THE REQUIRED SMOKE AND CO
 DETECTORS.
  
 4) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12 REVISE ACCORDINGLY
  
 5) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 REVISE ACCORDINGLY
  
 6) OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE
 SUPPORT OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE
 LISTED, SHALL BE MARKED BY THEIR MANUFACTURER AS
 SUITABLE FOR THIS PURPOSE, AND SHALL NOT SUPPORT
 CEILING-SUSPENDED (PADDLE) FANS THAT WEIGH MORE THAN 32
 KG (70 LB). FOR OUTLET BOXES OR OUTLET BOX SYSTEMS
 DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) FANS
 THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED
 MARKING SHALL INCLUDE THE MAXIMUM WEIGHT TO BE
 SUPPORTED. NEC314.27(D) REVISE ACCORDINGLY
  
 7) CLAIRFICATION IS REQUIRED. THERE ARE NUMBER AND
 LLETTER DESIGNATIONS USED THROUGHOUT THE PLAN HOWEVER
 THERE IS NO SYMBOLS KEY USED FOR REFFERENCE. REVISE
 PLAN FOR CLAIRIFICATION. WPB AMENDMENTS TO THE FBC
 107.3.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-25 Cont ID  
Sent By dhayes Date 2014-09-25 Time 09:47 Rev Time 0.00
Received By dhayes Date 2014-09-24 Time 18:04 Sent To  
Notes
2014-09-24 18:04:49TO DAH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-16 Cont ID  
Sent By dhayes Date 2014-09-16 Time 11:02 Rev Time 0.00
Received By dhayes Date 2014-08-08 Time 14:35 Sent To  
Notes
2014-08-09 14:33:37R15

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-09-11 Cont ID  
Sent By jgomez Date 2014-09-01 Time 18:12 Rev Time 0.00
Received By tklarge Date 2014-09-01 Time 05:45 Sent To  
Notes
2014-09-11 18:13:33APPROVED BY TIM LARGE ON 9/1/14. SEE PLANS.