2014-08-08 15:22:43 | DATE: 8/6/2014 | | PROJECT: TENANT IMPROVEMENT 313 DATURA ST. | | PERMIT#: 13050713 REVISION #14080295 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: PROVISO | | | | THE SINGLE LINE DIAGRAM IS MISSING THE LINE BETWEEN THE | | METER AND THE MAIN IN THE THREE 400AMP METER/MAIN | | SYMBOLS. PROVIDE SAME SIZE CONDUIT NIPPLE AND WIRE AS | | INDICATED AT THE LINE SIDE OF THE METER. | | | | THE MAIN BONDING JUMPERS NEED TO BE SIZED ACCORDING TO | | THE APPROPRIATE SIZE BASED ON NEC 250.28(D)(1) | | | | BOND LINE GUTTER. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|
|