Plan Review Details - Permit 14080122
Plan Review Stops For Permit 14080122
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-09-03 Cont ID  
Sent By shill Date 2014-09-03 Time 16:37 Rev Time 0.00
Received By shill Date 2014-09-03 Time 16:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-16 Cont ID  
Sent By shill Date 2014-08-16 Time 18:15 Rev Time 0.00
Received By shill Date 2014-08-16 Time 18:15 Sent To  
Notes
2014-08-16 18:15:56****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE FLOOR PLAN TO PROVIDE THE FOLLOWING
 INFORMATION FOR BEDROOMS; FBC R310, FBC EB 604.1. THE
 CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%:
  
 REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW
 IN THE BEDROOMS - AWNING, CASEMENT, SINGLE HUNG?
  
 REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING
 DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH
 EXISTS WHEN THE WINDOW IS FULLY OPEN.
  
 REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING
 DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE
 MANUFACTURER
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-03 Cont ID  
Sent By shill Date 2014-09-03 Time 16:37 Rev Time 0.00
Received By shill Date 2014-09-03 Time 16:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-16 Cont ID  
Sent By shill Date 2014-08-16 Time 18:16 Rev Time 0.00
Received By shill Date 2014-08-04 Time 15:51 Sent To  
Notes
2014-08-04 15:52:14ROUTED TO MISC 1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved