Plan Review Details - Permit 14080111
Plan Review Stops For Permit 14080111
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-08-19 Cont ID  
Sent By rmcdouga Date 2014-08-19 Time 15:42 Rev Time 0.00
Received By rmcdouga Date 2014-08-19 Time 15:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-08-15 Cont ID  
Sent By rmcdouga Date 2014-08-15 Time 07:49 Rev Time 0.00
Received By rmcdouga Date 2014-08-15 Time 07:40 Sent To  
Notes
2014-08-15 08:11:252010 FBC
  
 1) VALUATION FROM PREVIOUS REVIEW HAS NOT BEEN
 ADEQUATELY ADDRESSED. APPLICATION HAS 5,300 SQFT AND
 $16,000.00. SUBMIT A SIGNED COPY OF THE CONTRACT FOR
 THE RE-ROOF TO BE FILED FOR PUBLIC RECORD. CITY
 AMENDMENTS 109.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-04 Cont ID  
Sent By rmcdouga Date 2014-08-04 Time 17:55 Rev Time 0.00
Received By rmcdouga Date 2014-08-04 Time 16:53 Sent To  
Notes
2014-08-04 17:55:482010 FBC
  
 DENIED BY BUILDING
  
 1) THE MEAN ROOF HEIGHT (MRH) IS SPECIFIED AS 12' ON
 THE RAS 117 CALCULATIONS AND 30' ON THE APPLICATION.
 PLEASE CORRECT. CITY AMENDMENTS 107.2.1 AND FBCR
 301.2.1
  
 2) THE DESIGN WIND PRESSURES ARE INCORRECT FOR 170 MPH
 (132 MPH VASD) EXPOSURE C WITH A 30' MRH AND A 0 TO 7
 DEGREE ROOF SLOPE. THE UPLIFT PRESSURES ARE -43.8 PSF
 FOR ROOF ZONE 1, -73.5 PSF FOR ROOF ZONE 2 AND -110.7
 PSF FOR ROOF ZONE 3. PLEASE CORRECT. FBCR 301.2.1
  
 3) PLEASE REVISE THE FASTENER SPACING CALCULATIONS
 USING THE CORRECTED PRESSURES. CITY AMENDMENTS 107.2.1
 AND FBCR 301.2.1
  
 4) THE VALUATION FOR THE WORK IS TOO LOW FOR A 5,300
 SQFT MODIFIED BITUMEN ROOF SYSTEM. BASED ON THE
 MARSHALL AND SWIFT VALUATION GUIDE, THE AVERAGE
 VALUATION IS $5.30 PER SQUARE FOOT. BASED ON THIS, THE
 VALUATION FOR THIS PROJECT IS $28,090.00 AND WILL BE
 ADJUSTED ACCORDINGLY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2014-08-04 Cont ID  
Sent By rmcdouga Date 2014-08-04 Time 17:56 Rev Time 0.00
Received By rmcdouga Date 2014-08-04 Time   Sent To  
Notes
2014-08-04 14:37:48PER CONV WITH F MITTNER..NO REVIEW NECSSARY AS CONTR
 SAID THIS IS FOR FLAT DECK ONLY..NO TILE WORK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-15 Cont ID  
Sent By rmcdouga Date 2014-08-15 Time 07:49 Rev Time 0.00
Received By rmcdouga Date 2014-08-14 Time 07:40 Sent To  
Notes
***NONE***