Plan Review Details - Permit 14080109
Plan Review Stops For Permit 14080109
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-09-05 Cont ID  
Sent By skennedy Date 2014-09-05 Time 10:30 Rev Time 0.00
Received By skennedy Date 2014-09-05 Time 10:30 Sent To  
Notes
2014-09-05 10:30:55DISCUSSED W/ REB.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-08 Cont ID  
Sent By jwitmer Date 2014-08-08 Time 16:16 Rev Time 0.00
Received By jwitmer Date 2014-08-08 Time 15:32 Sent To  
Notes
2014-08-08 16:16:25BUILDING PLAN REVIEW
 PERMIT: 14080109
 ADD: 1045 CHARLOTTE
 CONT: THE CARPENTER'S SON
 TEL: ()452-2191
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY AUG. 08/2014
 ACTION: DENIED
  
 1) THE SUBMITTED PLAN IS A STATE APPROVED PLANS FOR A
 RESIDENTIAL STORAGE SHED (BUILDING CATEGORY I) , 180
 VALT / EXP. D, PLEASE REVIEW ISSUES AT HAND:
 1A) THE OCCUPANCY CLASSIFICATION IS BEING CHANGED TO A
 BUSINESS OCCUPANCY, A GUARD SHACK, THE BUILDING
 CATEGORY II HAS CHANGED, THIS WILL INCREASE THE
 REQUIRED PRESSURES.
 1B) WITH THE OCCUPANCY CHANGE REQUIRING THE BUILDING TO
 BE A BUILDING CATEGORY LL THIS MAY AFFECT THE ANCHORING
 OF THE STRUCTURE, THE ANCHORING ENGINEERING WILL ALSO
 NEED TO BE REVIEWED.
 1C) PLEASE NOTE ALSO THE REQUIREMENT FOR COMPONENTS AND
 CLADDING WINDOWS AND DOORS WILL NEED TO HAVE EITHER
 LARGE MISSILE IMPACT GLAZING OR STORM SHUTTERS. 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING.FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 1D) THE STATE PLANS SHEET 1 NOTE # 11 INDICATE FOR A
 RESIDENTIAL USE A ACCESORY SRUCTURE THE DOOR MAY BE 72
 INCHES, NOTE # 12 FOR COMMERCIAL USE THE DOOR MUST BE
 6'-8" TALL. FBC-B 1008.1.1.
 1E) THE STATE APPROVED PLANS DO INDICATE THAT THE NOTE
 # 4 THE GUTTER SYSTEM IS A SITE INSTALLED SYSTEM AND
 THE CONTRACTOR WILL NEED TO SUBMIT THE GUTTER AND DOWN
 SPOUT TO BE INSTALLED. 2010 FBC-B 1503.7 PROTECTION
 AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 2) IT WOULD APPEAR THE MANUFACTURER OF THE BUILDING
 SHOULD MAKE A REVISION TO THE STATE APPROVED PLANS FOR
 THE BUSINESS USE OCCUPANCY, THEN THE STATE APPROVED
 PLANS WOULD ADDRESS THE COMMENTS 1A-1D.
 1E) GUTTERS WILL STILL BE A SITE INSTALLED BY THE
 CONTRACTOR.
  
 3) PLEASE IDENTIFY WHICH TYPE OF BUILDING TO BE
 INSTALLED, GABLE END, HIP OR SHED TYPE ROOF.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-03 Cont ID  
Sent By rlecky Date 2014-09-03 Time 15:11 Rev Time 0.00
Received By rlecky Date 2014-09-03 Time 14:44 Sent To  
Notes
2014-09-03 15:21:32SEE NOTES ON PLAN. RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-08-11 Cont ID  
Sent By scaldero Date 2014-08-11 Time 16:13 Rev Time 0.00
Received By scaldero Date 2014-08-11 Time 16:13 Sent To  
Notes
2014-08-11 16:15:06PERMIT # 14080109
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 A CERTIFIED AND APPROVED FIRE EXTINGUISHER (2A-10BC)
 MUST BE PROVIDED.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-03 Cont ID  
Sent By rlecky Date 2014-09-03 Time 15:21 Rev Time 0.00
Received By rlecky Date 2014-08-04 Time 16:57 Sent To  
Notes
2014-08-04 17:00:14ROUTE TO B16

Review Stop P PLUMBING
Rev No 2 Status N Date 2014-09-05 Cont ID  
Sent By skennedy Date 2014-09-05 Time 10:30 Rev Time 0.00
Received By skennedy Date 2014-09-05 Time 10:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-08-08 Cont ID  
Sent By jwitmer Date 2014-08-08 Time 16:21 Rev Time 0.00
Received By jwitmer Date 2014-08-08 Time 15:32 Sent To  
Notes
2014-08-08 16:21:12PLUMBING PLAN REVIEW
 PERMIT: 14080109
 ADD: 1045 CHARLOTTE
 CONT: THE CARPENTER'S SON
 TEL: ()452-2191
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY AUG. 08/2014
 ACTION: DENIED
  
 1) PLEASE PROVIDE THE DISTANCE IN FEET TO THE NEAREST
 RESTROOMS? 2010 FBC-P 403.3.2.
  
 2) NO DRINKING FOUNTAIN WILL BE REQUIRED SINCE THE
 OCCUPANT LOAD IS 15 OR FEWER 2010 FBC-P TABLE 403.1
 FOOTNOTE F.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2014-08-18 Cont ID  
Sent By jroach Date 2014-08-18 Time 15:28 Rev Time 0.00
Received By sgraham Date 2014-08-18 Time 15:28 Sent To B
Notes
2014-08-05 17:33:058/5/14