Plan Review Details - Permit 14080108
Plan Review Stops For Permit 14080108
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2014-10-15 Cont ID  
Sent By mgonzale Date 2014-10-15 Time   Rev Time 0.50
Received By mgonzale Date 2014-10-15 Time   Sent To I
Notes
2014-10-15 15:05:47PROVISOS:
  
 #1 CALL 811 BEFORE DIGG, (FLORIDA ADMINISTRATIVE CODE
 CHAPTER 556, 553)
  
 #2 INSTALL ACCESSABLE CLEAN-OUT 5 FEET FROM GREASE
 SEPARATOR ON EFFLUENT LINE.
 (CLEAN-OUT WILL BE UTILIZED TO SAMPLE THE GREASE
 CONTENT UNDER THE CITY'S FOG PROGRAM
 AND TO COMPLY WITH TESTING AS REQUIRED BY STATE OF
 FLORIDA DEPARTMENT OF HEALTH)
 (FLORIDA ADMINISTRATIVE CODE CHAPTER 64E-6)
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2014-10-14 Cont ID  
Sent By wjolin Date 2014-10-14 Time 10:36 Rev Time 0.00
Received By wjolin Date 2014-10-14 Time 10:36 Sent To M
Notes
2014-10-14 10:37:17PASSED BY M. GONZALEZ (ENGINEERING). PASS RESULT
 ENTERED BY W. JOLIN (FIRE).

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2014-09-24 Cont ID  
Sent By hmoser Date 2014-10-21 Time 08:23 Rev Time 0.00
Received By wjolin Date 2014-09-24 Time 15:36 Sent To ENG
Notes
2014-09-24 15:46:15900 FLORIDA AVENUE - TRAILERS
 PERMIT #14080108
 MASTER #14060484
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 LOCATE FIRE DEPARTMENT CONNECTION ON THE OUTSIDE OF THE
 FENCE.
  
 POST WEATHERPROOF SIGNAGE INDICATING LOCAL ALARM ONLY.
 CALL 911 IF ALARM BELL SOUNDS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-09-09 Cont ID  
Sent By wjolin Date 2014-09-11 Time 17:41 Rev Time 0.00
Received By wjolin Date 2014-09-09 Time 17:14 Sent To M
Notes
2014-09-09 17:41:15900 FLORIDA AVENUE - TRAILERS
 PERMIT #14080108
 MASTER #14060484
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: PROVIDE WATER SUPPLY/HYDRANT FLOW TEST
 INFORMATION ON THE PLANS.
  
 REPEAT COMMENT: NO PRODUCT DATA SUBMITTED FOR PIPE,
 HANGERS, BACKFLOW PREVENTION DEVICES, FLOW SWITCHES,
 ETC.
  
 COVER SHEET AND FIRST SHEET ARE BOTH TITLED FP-1. COVER
 SHEET LABELED FP-1 IS NOT SIGNED OR SEALED BY THE
 ENGINEER OF RECORD.
  
 COVER SHEET INDICATES THE AHJ IS THE TOWN OF HIGHLAND
 BEACH.
  
 INDICATE UNDERGROUND PIPE MATERIAL. INDICATE THE
 UNDERGROUND RESTRAINING METHOD.
  
 COVER SHEET LAYOUT NEEDS TO BE COORDINATED WITH OTHER
 SHEETS. FOR EXAMPLE:
 1) COVER SHEET INDICATES A FREE STANDING FIRE
 DEPARTMENT CONNECTION, WHILE SHEETS FP-1 AND FP-2 SHOW
 FIRE DEPARTMENT CONNECTIONS ATTACHED TO THE SPRINKLER
 RISER. WHERE IS THE PERIMETER SECURITY FENCE LOCATED?
 2) COVER SHEET INDICATES THE WATER SUPPLY IS LOCATED TO
 THE NORTHWEST OF THE DOUBLE-WIDE TRAILER, WHILE SHEET
 FP-1 INDICATES THE WATER SUPPLY IS LOCATED TO THE
 SOUTHWEST OF THE DOUBLE-WIDE TRAILER.
 3) COVER SHEET INDICATES FIRE LINE BEGINS DOWNSTREAM OF
 DOMESTIC WATER, WHILE THE OTHER SHEETS INDICATE THE
 FIRE LINE BEGINS UPSTREAM OF THE DOMESTIC BACKFLOW
 PREVENTER.
  
 SUPPLYING A FIRE MAIN DIRECTLY FROM A FIRE HYDRANT WILL
 NOT BE ACCEPTED AS THIS CONFIGURATION IS NOT SECURED
 FROM DISASSEMBLY AND COULD AFFECT FIRE RESCUE
 SUPPRESSION TACTICS. PROVIDE AN UNDERGROUND TAP TO THE
 CITY WATER MAIN OR PROVIDE A LISTED WATER TANK. CITY
 WATER MAIN INFORMATION (LOOP/DEAD-END, SIZE, ETC.) NOT
 PROVIDED ON THE PLANS. ADDITIONALLY, THIS PROPOSED
 INSTALLATION DOES NOT ALLOW THE PIPING TO BE
 HYDROSTATICALLY PRESSURE TESTED BETWEEN THE BACKFLOW
 PREVENTER AND HYDRANT CONNECTION PER NFPA 13 AND NFPA
 24.
  
 PER NFPA 24 SECTION 8.7 DOMESTIC SERVICE USE
 PROHIBITED. THE USE OF HYDRANTS FOR PURPOSES OTHER THAN
 FIRE-RELATED SERVICES SHALL BE PROHIBITED.
  
 IF A SINGLE FIRE/DOMESTIC WATER MAIN TAP IS UTILIZED,
 THE DOMESTIC WATER DEMAND WILL NEED TO BE ADDED TO THE
 HYDRAULIC CALCULATIONS FOR PIPING SMALLER THAN
 4-INCHES.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-08-13 Cont ID  
Sent By wjolin Date 2014-08-13 Time 11:41 Rev Time 0.00
Received By wjolin Date 2014-08-13 Time 11:34 Sent To ENG
Notes
2014-08-13 11:41:40900 FLORIDA AVENUE - TRAILERS
 PERMIT #14080108
 MASTER #14060484
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO NFPA 24 AND NFPA 13 IN LIEU OF
 THE PROPOSED NFPA 13D SYSTEMS.
  
 PROVIDE WATER SUPPLY/HYDRANT FLOW TEST INFORMATION ON
 THE PLANS.
  
 PROVIDE A SITE PLAN DETAILING TRAILER LOCATIONS, NORTH
 DIRECTION, FIRE HYDRANT LOCATIONS, FDCS, WATER MAIN TAP
 SIZE, ETC.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME.
  
 NO PRODUCT DATA SUBMITTED FOR PIPE, HANGERS, BACKFLOW
 PREVENTION DEVICES, FLOW SWITCHES, ETC.
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-10-21 Cont ID  
Sent By hmoser Date 2014-10-21 Time 08:23 Rev Time 0.00
Received By hmoser Date 2014-09-23 Time 09:07 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-24 Cont ID  
Sent By skennedy Date 2014-09-22 Time 09:06 Rev Time 0.00
Received By skennedy Date 2014-08-28 Time 09:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-22 Cont ID  
Sent By skennedy Date 2014-08-22 Time 14:36 Rev Time 0.00
Received By skennedy Date 2014-08-13 Time 11:34 Sent To  
Notes
2014-08-04 14:10:53ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-10-21 Cont ID  
Sent By hmoser Date 2014-10-21 Time 08:23 Rev Time 0.00
Received By hmoser Date 2014-10-21 Time 08:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-09-22 Cont ID  
Sent By rbergsma Date 2014-09-22 Time   Rev Time 0.00
Received By rbergsma Date   Time   Sent To  
Notes
2014-09-22 14:46:11SEE FIRE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-08-22 Cont ID  
Sent By skennedy Date 2014-08-22 Time 14:35 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
2014-08-22 14:36:21SEE FIRE COMMENTS.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  