Plan Review Details - Permit 14080088
Plan Review Stops For Permit 14080088
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-08-28 Cont ID  
Sent By dhayes Date 2014-08-28 Time 12:59 Rev Time 0.00
Received By dhayes Date 2014-08-28 Time 12:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-08-11 Cont ID  
Sent By dhayes Date 2014-08-11 Time 11:50 Rev Time 0.00
Received By dhayes Date 2014-08-11 Time 11:40 Sent To  
Notes
2014-08-11 13:04:20DATE: 8/6/2014
 PROJECT: GENERATR 3263 RUSSLYNN DR.
 PERMIT#: 14080088
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) IT IS ILLEGAL TO REPRODUCE COPYRIGHTED MATERIAL
 UNDER FEDERAL LAW.
 A) PROVIDE A WRITTEN SCOPE OF WORK.
 B) PROVIDE A LOAD CALCULATION, PANEL SCHEDULE AND RISER
 DIAGRAM TO SUPPORT THE SCOPE OF WORK.
 C) PROVIDE MAUFACTURER DATA SHEETS ON THE ATS.
  
 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-28 Cont ID  
Sent By dhayes Date 2014-08-28 Time 12:59 Rev Time 0.00
Received By dhayes Date 2014-08-27 Time 19:01 Sent To  
Notes
2014-08-27 19:01:40SENT TO D HAYES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-11 Cont ID  
Sent By dhayes Date 2014-08-11 Time 13:04 Rev Time 0.00
Received By dhayes Date 2014-08-04 Time 12:00 Sent To  
Notes
2014-08-04 12:00:41ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2014-08-04 Cont ID  
Sent By sgraham Date 2014-08-04 Time 15:10 Rev Time 0.00
Received By sgraham Date 2014-08-04 Time 15:10 Sent To E
Notes
***NONE***