Plan Review Details - Permit 14080059
Plan Review Stops For Permit 14080059
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-03-10 Cont ID  
Sent By jwitmer Date 2015-03-10 Time 08:13 Rev Time 0.00
Received By jwitmer Date 2015-03-10 Time 06:30 Sent To  
Notes
2015-03-10 07:40:31BUILDING PLAN REVIEW
 PERMIT: 14080059
 ADD: 5660 N MILITARY TRL.
 CONT: TBD
 TEL: (901)495-8701
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: TUES. MARCH 10/ 2015
 ACTION: BUILDING PROVISO
  
 1) THIS PROJECT WILL REQUIRE A RESIDENT INSPECTOR
 BEFORE PERMIT ISSUANCE;
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION BOLTED CONNECTIONS, WELDS &
 WELDED DECKS
  
 FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME'
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO
 KEN CONRAD BY E-MAIL. KEN CONRAD: [email protected]
  
 NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE REQUIRED.
 FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE PERMIT
 LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND BATCH
 STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF
 PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE
 RESIDENT INSPECTOR, THE OTHER FOR THE MEP INSPECTORS.
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
  
 2A) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.3.4.2
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE
 BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND
 FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF THE
 BUILDING. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE
 INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN APPROVED BY THE BUILDING OFFICIAL.
  
 2B) DEFERRED SUBMITTALS: FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOOR/ STOREFRONT
 (B) WINDOWS/ STOREFRONT
 (D) ROOFING PRODUCTS AND ASSEMBLIES , 3 FT. PARAPET,
 MAY REQUIRE ENHANCED FASTENING IN ROOF ZONES 2 & 3/
 -63.8 PSF @ 15 FT.
  
 2C) DEFERRED SUBMITTAL: 107.2.1.2 FOR ROOF ASSEMBLIES
 REQUIRED BY THE CODE, THE CONSTRUCTION DOCUMENTS SHALL
 ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING
 SYSTEM, MATERIALS, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT
 BY AN ARCHITECT OR ENGINEER FOR THE SPECIFIC SITE MUST
 BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-11-24 Cont ID  
Sent By jwitmer Date 2014-11-24 Time 11:37 Rev Time 0.00
Received By jwitmer Date 2014-11-22 Time 10:45 Sent To  
Notes
2014-11-22 11:22:28BUILDING PLAN REVIEW
 PERMIT: 14080059
 ADD: 5660 N MILITARY TRL.
 CONT: TBD
 TEL: (901)495-8701
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 NOTE: PLANS WERE SUBMITTED BY MAIL "NO PERMIT
 APPLICATION WAS PROVIDED", SUBMITTED AS A TBD" TO BE
 DETERMINED" BEFORE PERMIT ISSUANCE A QUALIFIED
 CONTRACTOR WILL NEED TO SUBMIT A SIGNED AND NOTIRIZED
 PERMIT APPLICATION BY THE OWNER AS WELL AS THE
 CONTRACTOR.
  
 2ND REVIEW
 DATE: SAT. NOV. 22/2014
 ACTION: DENIED
  
  
 NOTICE:!!!!!!!!!!!!!!!!
 CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A
 LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE
 FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE TIMES
 FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
 1)COMPLIED. SITE PLAN.
  
 2) 2ND REQUEST. THE SUBMITTED SOILS REPORTS ARE COPIES
 OF ORIGINAL SOILS REPORTS. THE REPORT HAS A COPIED
 ENGINEERS SIGNATURE, & NO SEAL.
  
 61G15-23.002(1) SEAL, SIGNATURE AND DATE SHALL BE
 AFFIXED. A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME
 AND AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS,
 REPORTS, FINAL BID DOCUMENTS PROVIDED TO THE OWNER OR
 THE OWNER?S REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED
 OR ISSUED BY SAID REGISTRANT AND BEING FILED FOR PUBLIC
 RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED
 AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS,
 SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER.
  
 MISSING SOILS REPORT 2010 FBC-B 1803.2 INVESTIGATIONS
 REQUIRED. GEOTECHNICAL INVESTIGATIONS SHALL BE
 CONDUCTED IN ACCORDANCE WITH SECTIONS 1803.3 THROUGH
 1803.5.
 1803.3 BASIS OF INVESTIGATION. SOIL CLASSIFICATION
 SHALL BE BASED ON OBSERVATION AND ANY NECESSARY TESTS
 OF THE MATERIALS DISCLOSED BY BORINGS, TEST PITS OR
 OTHER SUBSURFACE EXPLORATION MADE IN APPROPRIATE
 LOCATIONS. ADDITIONAL STUDIES SHALL BE MADE AS
 NECESSARY TO EVALUATE SLOPE STABILITY, SOIL STRENGTH,
 POSITION AND ADEQUACY OF LOAD-BEARING SOILS, THE EFFECT
 OF MOISTURE VARIATION ON SOIL-BEARING CAPACITY,
 COMPRESSIBILITY, LIQUEFACTION AND EXPANSIVENESS.
  
 3) PARTIAL APPROVED. THE DESIGNER OF RECORD HAS
 REQUESTED THE MISSING PRODUCT APPROVALS TO COME IN
 AFTER PERMIT ISSUANCE AS DEFERRED SUBMITTALS. THE
 COVERSHEET A0 LIST THE PRODUCT APPROVALS, WE REQUIRE
 THE PRODUCT APPROVALS 2 COPIES OF EACH ON E FOR RECORD
 RETENION THE OTHER FOR THE FIELD INSPECTORS.
 WINDOWS AND DOORS WITH GLAZING, IDENTIFY WHICH MODEL IF
 MORETHAN ONE TYPE IS LISTED (FL REPORTS), IDENTIFY THE
 TYPE OF GLAZING TO BE INSTALLED, INDENTIFY WIDTH &
 LENGTH OF GLAZING UNITS, MULLIONS, AND ASSOCIATED
 PRESSURES. ETC. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. MISSING YKK FL 16554-R2
 (B) WINDOWS FIXED FL. 16314-R1 / STOREFRONT FL 14218-R2
 (D) ROOFING PRODUCTS AND ASSEMBLIES GAF NOA 12-1218.04
 TO BE SUBMITTED AS A DERRED SUBMITTAL
  
 4) DEFERRED SUBMITTALS. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 5) DEFERRED SUBMITTAL: 107.2.1.2 FOR ROOF ASSEMBLIES
 REQUIRED BY THE CODE, THE CONSTRUCTION DOCUMENTS SHALL
 ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING
 SYSTEM, MATERIALS, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT
 BY AN ARCHITECT OR ENGINEER FOR THE SPECIFIC SITE MUST
 BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS.
  
 6) DEFERRED SUBMITTAL. PLEASE PROVIDE THE EFIS
 MANUAFACTURERS SPECIFICATIONS FOR INSTALATION. 107.2.4
 EXTERIOR WALL ENVELOPE. CONSTRUCTION DOCUMENTS FOR ALL
 BUILDINGS SHALL DESCRIBE THE EXTERIOR WALL ENVELOPE IN
 SUFFICIENT DETAIL TO DETERMINE COMPLIANCE WITH THIS
 CODE. THE CONSTRUCTION DOCUMENTS SHALL PROVIDE DETAILS
 OF THE EXTERIOR WALL ENVELOPE AS REQUIRED, INCLUDING
 FLASHING, INTERSECTIONS WITH DISSIMILAR MATERIALS,
 CORNERS, END DETAILS, CONTROL JOINTS, INTERSECTIONS AT
 ROOF, EAVES OR PARAPETS, MEANS OF DRAINAGE,
 WATER-RESISTIVE MEMBRANE AND DETAILS AROUND OPENINGS.
 THE CONSTRUCTION DOCUMENTS SHALL INCLUDE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS THAT PROVIDE SUPPORTING
 DOCUMENTATION THAT THE PROPOSED PENETRATION AND OPENING
 DETAILS DESCRIBED IN THE CONSTRUCTION DOCUMENTS
 MAINTAIN THE WEATHER RESISTANCE OF THE EXTERIOR WALL
 ENVELOPE. THE SUPPORTING DOCUMENTATION SHALL FULLY
 DESCRIBE THE WALL SYSTEM WHICH WAS TESTED, WHERE
 APPLICABLE, AS WELL AS THE TEST PROCEDURE USED.
  
 7) DEFERRED SUBMITTAL. SHEET A3 DETAIL # 1 AS WELL AS
 THE ENERGY CALCS INDICATE THE USE OF R-30 INSULATION,
 PLEASE PROVIDE A CROSS SECTION OF ROOF WITH THE THE
 R-30 INSULATION, THE TYPE OF MATERIAIL ANAD HOW IT WILL
 BE ATTACHED TO THE ROOF DECK. ENERGY CODE WHOLE
 BUILDING METHOD 506.3.1./ COMPONENTS & CLADDING
 1609.1.2.
  
 8) COMPLIED. SHEET S2 DETAIL #4.
  
 9) COMPLIED.
  
 10) COMPLIED.
  
 11) COMPLIED. P. B. C. IMPACT FEE ASSESSMANT.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-25 Cont ID  
Sent By jwitmer Date 2014-08-25 Time 06:46 Rev Time 0.00
Received By jwitmer Date 2014-08-24 Time 15:01 Sent To  
Notes
2014-08-25 06:46:04BUILDING PLAN REVIEW
 PERMIT: 14080059
 ADD: 5660 N MILITARY TRL.
 CONT: TBD
 TEL: (901)495-8701
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUG. 25/2014
 ACTION: DENIED
  
 1) MISSING DOCUMENTS:
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND DOCUMENTS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 1. SITE REQUIREMENTS:
 PARKING
 FIRE ACCESS
 VEHICLE LOADING
 DRIVING/TURNING RADIUS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV)
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
 LOCATION OF SPECIFIC TANKS, WATER LINES AND SEWER LINES
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
  
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 THE PROPOSED FINISHED GRADES AND, AS APPLICABLE, FLOOD
 HAZARD AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS;
 AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE
 BOUNDARY LINE SURVEY.
 IN THE CASE OF DEMOLITION, THE SITE PLAN SHALL SHOW
 CONSTRUCTION TO BE DEMOLISHED AND THE LOCATION AND SIZE
 OF EXISTING STRUCTURES AND CONSTRUCTION THAT ARE TO
 REMAIN ON THE SITE OR PLOT. THE BUILDING OFFICIAL IS
 AUTHORIZED TO WAIVE OR MODIFY THE REQUIREMENT FOR A
 SITE PLAN WHEN THE APPLICATION FOR PERMIT IS FOR
 ALTERATION OR REPAIR OR WHEN OTHERWISE WARRANTED.
  
 2) MISSING SOILS REPORT 2010 FBC-B 1803.2
 INVESTIGATIONS REQUIRED. GEOTECHNICAL INVESTIGATIONS
 SHALL BE CONDUCTED IN ACCORDANCE WITH SECTIONS 1803.3
 THROUGH 1803.5.
 1803.3 BASIS OF INVESTIGATION. SOIL CLASSIFICATION
 SHALL BE BASED ON OBSERVATION AND ANY NECESSARY TESTS
 OF THE MATERIALS DISCLOSED BY BORINGS, TEST PITS OR
 OTHER SUBSURFACE EXPLORATION MADE IN APPROPRIATE
 LOCATIONS. ADDITIONAL STUDIES SHALL BE MADE AS
 NECESSARY TO EVALUATE SLOPE STABILITY, SOIL STRENGTH,
 POSITION AND ADEQUACY OF LOAD-BEARING SOILS, THE EFFECT
 OF MOISTURE VARIATION ON SOIL-BEARING CAPACITY,
 COMPRESSIBILITY, LIQUEFACTION AND EXPANSIVENESS.
  
 3) THE COVERSHEET A0 LIST THE PRODUCT APPROVALS, WE
 REQUIRE THE PRODUCT APPROVALS 2 COPIES OF EACH ON E FOR
 RECORD RETENION THE OTHER FOR THE FIELD INSPECTORS.
 WINDOWS AND DOORS WITH GLAZING, IDENTIFY WHICH MODEL IF
 MORETHAN ONE TYPE IS LISTED (FL REPORTS), IDENTIFY THE
 TYPE OF GLAZING TO BE INSTALLED, INDENTIFY WIDTH &
 LENGTH OF GLAZING UNITS, MULLIONS, AND ASSOCIATED
 PRESSURES. ETC. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. ROOF HATCHES
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE,
 THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE
 AND DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 6) 107.2.4 EXTERIOR WALL ENVELOPE. CONSTRUCTION
 DOCUMENTS FOR ALL BUILDINGS SHALL DESCRIBE THE EXTERIOR
 WALL ENVELOPE IN SUFFICIENT DETAIL TO DETERMINE
 COMPLIANCE WITH THIS CODE. THE CONSTRUCTION DOCUMENTS
 SHALL PROVIDE DETAILS OF THE EXTERIOR WALL ENVELOPE AS
 REQUIRED, INCLUDING FLASHING, INTERSECTIONS WITH
 DISSIMILAR MATERIALS, CORNERS, END DETAILS, CONTROL
 JOINTS, INTERSECTIONS AT ROOF, EAVES OR PARAPETS, MEANS
 OF DRAINAGE, WATER-RESISTIVE MEMBRANE AND DETAILS
 AROUND OPENINGS. THE CONSTRUCTION DOCUMENTS SHALL
 INCLUDE MANUFACTURER?S INSTALLATION INSTRUCTIONS THAT
 PROVIDE SUPPORTING DOCUMENTATION THAT THE PROPOSED
 PENETRATION AND OPENING DETAILS DESCRIBED IN THE
 CONSTRUCTION DOCUMENTS MAINTAIN THE WEATHER RESISTANCE
 OF THE EXTERIOR WALL ENVELOPE. THE SUPPORTING
 DOCUMENTATION SHALL FULLY DESCRIBE THE WALL SYSTEM
 WHICH WAS TESTED, WHERE APPLICABLE, AS WELL AS THE TEST
 PROCEDURE USED.
  
 7) SHEET A3 DETAIL # 1 AS WELL AS THE ENERGY CALCS
 INDICATE THE USE OF R-30 INSULATION, PLEASE PROVIDE A
 CROSS SECTION OF ROOF WITH THE THE R-30 INSULATION, THE
 TYPE OF MATERIAIL ANAD HOW IT WILL BE ATTACHED TO THE
 ROOF DECK. ENERGY CODE WHOLE BUILDING METHOD 506.3.1./
 COMPONENTS & CLADDING 1609.1.2.
  
 8) SHEET A6 & S2 DETAIL # 4 SHOW THE USE OF ROOF TOP
 A/C CURBS BUT THE PLANS DO NOT PROVIDE HOW THE ROF OP
 PACKAGE UNIT WILL BE TIED TO THE A/C CURB, PART OF
 COMPONENTS AND CLADDING. , 1609.6.4.41 COMPONENTS &
 CLADDING.
  
 9) SHEET S2 THE ROOF TOP HATCH IS LOCATED WITHIN 10FT
 OF THE PARAPET, PLEASE SHOW COMPLIANCE WITH 2010 FBC-B
 1013.6 ROOF ACCESS.
 GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING
 IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR
 OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN
 SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE
 FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER.
  
 10) PLEASE PROVIDE WHERE THE STRUCURAL PLANS INDICATE
 THE USE OF LONGITUDINAL (HORIZONTAL) WALL
 REINFORCEMENT, AND ON WHAT CENTERS? 2010 FBC-B 2108.2/
 ASCE 530.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-12-15 Cont ID  
Sent By rlecky Date 2014-12-15 Time 11:46 Rev Time 0.00
Received By dhayes Date 2014-12-15 Time 10:53 Sent To  
Notes
2014-12-15 11:46:0212/15/2014
 PROJECT: AUTOZONE #4938
 PERMIT#: 14080059
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) VERIFY THAT THE INTERIOR AND EXTERIOR LIGHTING
 CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH THE
 FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL
 BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME
 SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST
 10 HOURS. FBC ENERGY CONSERVATION 505.2
  
 2) VERIFY SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN
 DISCONNECTING MEANS. NEC 110.16, 110.22
  
 3) VERIFY THE ELECTRICAL DISCONNECTING MEANS AND PANEL
 BOARDS HAVE A FAULT CURRENT RATING THAT IS SUFFICIENT
 AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. INDICATE THE MAXIMUM AVAILABLE FAULT
 CURRENT AT THE SERVICE POINT OF THE ELECTRICAL UTILITY.
 NEC 110.9, 110.10
  
 4) VERIFY DIMENSIONS AND LISTING FOR THE ELECTRICAL
 SERVICE WIREWAY. NEC 110-26, 314.28
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-08-26 Cont ID  
Sent By rlecky Date 2014-08-26 Time 11:46 Rev Time 0.00
Received By rlecky Date 2014-08-26 Time 10:09 Sent To  
Notes
2014-08-26 11:49:0714080059
 5660 N. MILITARY TRAIL
 AUTO ZONE
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 CONFIRM THAT THE INTERIOR AND EXTERIOR LIGHTING
 CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH THE
 FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL
 BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME
 SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST
 10 HOURS. FBC ENERGY CONSERVATION 505.2
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN
 DISCONNECTING MEANS. NEC 110.16, 110.22
  
 SHOW THE PROPOSED LOCATION OF THE ELECTRICAL SERVICE.
 VERIFY SAFE WORKING CLEARANCE HAS BEEN PROVIDED AT THE
 SERVICE, PANEL BOARDS AND DISCONNECTS. NEC 110.26,
 240.24(D)
  
 VERIFY THE ELECTRICAL DISCONNECTING MEANS AND PANEL
 BOARDS HAVE A FAULT CURRENT RATING THAT IS SUFFICIENT
 AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. INDICATE THE MAXIMUM AVAILABLE FAULT
 CURRENT AT THE SERVICE POINT OF THE ELECTRICAL UTILITY.
 NEC 110.9, 110.10
  
 PROVIDE DIMENSIONS AND LISTING FOR THE ELECTRICAL
 SERVICE WIREWAY. NEC 110-26, 314.28
  
 THE ELECTRIC WATER COOLER REQUIRES GFCI PROTECTION. NEC
 422.52
  
 THE DRINK MACHINE REQUIRES GFCI PROTECTION. NEC 422.51
  
  
 NOTE: A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR FIRE
 ALARM SYSTEMS, VIDEO, SECURITY, VOICE, POS, SITE
 LIGHTING, SIGNS AND DATA SYSTEMS
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2014-12-18 Cont ID  
Sent By cranford Date 2014-12-18 Time 10:41 Rev Time 0.00
Received By cranford Date 2014-12-18 Time 10:40 Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2014-08-19 Cont ID  
Sent By cranford Date 2014-08-19 Time 08:28 Rev Time 1.00
Received By cranford Date 2014-08-14 Time 15:17 Sent To B
Notes
2014-08-15 08:36:05ENGINEERING/PULBLIX WORKS DEPT. COMMENTS
  
 1. ENGINEERING DEPARTMENT DEVELOPMENT APPROVAL WILL BE
 REQUIRED PRIOR TO START OF CONSTRUCTION. THE
 APPLICATION FORM IS AVAILABLE ON OUR WEBSITE AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 2. THE WATER METER WILL NEED TO BE LOCATED WITHIN THE
 RIGHT-OF-WAY OR WITHIN AN EASEMENT.
  
 3. HOW WILL THE 3:1 SLOPE PROPOSED BETWEEN THE REAR OF
 THE DUMPSTER ENCLOSURE AND THE PROPERTY LINE BE
 MAINTAINED.
  
 4. PLEASE ALSO PROVIDE A CROSS-SECTION BETWEEN THE
 NORTH SIDE OF THE BUILDING AND THE PROPERTY LINE.
  
 5. THE SIDEWALK CONNECTING THE DOOR ON THE EAST SIDE OF
 THE BUILDING TO THE REMAINED OF THE ON-SITE SIDEWALK
 WAS INCLUDED IN THE PLAN SUBMITTED UNDER PLANNING
 APPLICATION Z13120013 BUT IS NOT INCLUDED IN THE SITE
 PLAN SUBMITTED WITH THIS APPLICATION (BUILDING APP
 14080059). THE PLANS NEED TO MATCH.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 ENGINEERING & PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-08-06 Cont ID  
Sent By pleduc Date 2014-08-06 Time   Rev Time 0.00
Received By pleduc Date 2014-08-06 Time 12:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2015-03-12 Cont ID  
Sent By skennedy Date 2015-03-12 Time 13:52 Rev Time 0.00
Received By skennedy Date 2015-03-03 Time 18:32 Sent To  
Notes
2015-03-03 18:33:43C26

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-18 Cont ID  
Sent By cranford Date 2014-12-18 Time 10:44 Rev Time 0.00
Received By cranford Date 2014-11-17 Time 18:08 Sent To  
Notes
2014-11-17 18:12:07C05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-03 Cont ID  
Sent By skennedy Date 2014-09-03 Time 07:27 Rev Time 0.00
Received By skennedy Date 2014-08-01 Time 11:38 Sent To  
Notes
2014-08-05 11:38:24SENT TO C27 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2014-11-22 Cont ID  
Sent By jwitmer Date 2014-11-22 Time 10:44 Rev Time 0.00
Received By jwitmer Date 2014-11-22 Time 10:44 Sent To  
Notes
2014-11-22 10:44:59PALM BEACH COUNTY IMPACT FEE ASSESSMENT;
 OCT. 13/ 2014
 PR RECEIPT: MU-2014-021859-0000
 EXISTING USE CREDIT; NO FEES DUE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-08-24 Cont ID  
Sent By jwitmer Date 2014-08-24 Time 15:26 Rev Time 0.00
Received By jwitmer Date 2014-08-24 Time 15:26 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2015-04-07 Cont ID  
Sent By llouie Date 2015-04-07 Time   Rev Time 0.00
Received By llouie Date 2015-04-07 Time   Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2014-12-17 Cont ID  
Sent By llouie Date 2014-12-17 Time   Rev Time 0.00
Received By llouie Date 2014-12-17 Time   Sent To  
Notes
2014-12-17 12:58:16** LANDSCAPE FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) CONDITIONS OF ISPR #13-12/Z13120013 HAVE NOT BEEN
 ADDRESSED. CONDITIONS NEED TO BE ADDRESSED PRIOR TO
 SUBMITTING FOR BUILDING PERMITS. (8/15/14 REPEAT
 COMMENT: APPLICANT IS AWARE OF CONDITION)
  
 PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE
 ARE QUESTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-12-01 Cont ID  
Sent By hmoser Date 2014-12-01 Time   Rev Time 0.50
Received By rbergsma Date 2014-12-01 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-08-16 Cont ID  
Sent By hmoser Date 2014-08-16 Time 08:57 Rev Time 0.00
Received By hmoser Date 2014-08-16 Time 08:47 Sent To  
Notes
2014-08-16 08:57:24PLAN DENIED
  
 1) REFER TO SECTION 606.2.1 SUPPLY AIR
 AND SECTION 606.4.1 SUPERVISION.2010
 FBC (M)
 2) REFER TO SECTION 606.3 INSTALLATION.
 2010 FBC (M)
 3) PROVIDE A DETAIL FROM THE ENGINEER
 ON THE CURB TO ROOF TIE DOWN AND RTU
 TO CURB TIE DOWN. PER SECTION
 301.12 WIND RESISTANCE 2010 FBC (M)
 4) REFER TO SECTION 1509.7 MECHANICAL UNIT'S
 2010 FBC.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-11-26 Cont ID  
Sent By tklarge Date 2014-11-26 Time 10:34 Rev Time 0.00
Received By tklarge Date 2014-11-26 Time 10:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-08-30 Cont ID  
Sent By tklarge Date 2014-08-30 Time 09:02 Rev Time 0.00
Received By tklarge Date 2014-08-30 Time 08:41 Sent To  
Notes
2014-08-30 09:02:232010 WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1.
 1) SHT. A-4-THE GUARDRAILS AT THE DRINKING FOUNTAINS
 SHALL NOT IMPINGE ON THE REQUIRED CLEAR FLOOR SPACE FOR
 THE FIXTURE. THE REQUIRED 30" X 48" CLEAR FLOOR SPACE
 SHALL BE CENTERED ON THE FIXTURE PER THE 2010 FAC
 SEC.602.2.. SHOW THE REQUIRED CLEAR FLOOR SPACE ON THE
 FLOOR PLAN.
 2) SHT. A-4- DETIAL #6 (INTERIOR BATHROOM ELEVATIONS)
 ACCESSORY #7- A VERTICALLY MOUNTED GRAB BAR IS SHOWN.
 THIS IS NOT PERMITTED PER THE FAC SEC.609.4.
 3) SHT.A-4-DETAIL #4- THE TOILET PAPER DISPENSER SHALL
 BE LOCATED 9 INCHES MAXIMUMTO THE CENTER LINE OF THE
 DISPENSER PER SEC. 604.7 OF THE 2010 FAC.
 4) SHT. M-2- THE HOT AND COLD WATER LINES ARE REVERSED
 AT THE LAVS ON THE WATER RISER. THE HOT WATER SHALL BE
 ON THE LEFT SIDE PER THE 2010 FPC SEC.607.4.
 5)A SEPARATE SHUTOFF VALVE IS REQD. FOR THE ROOFTOP
 HOSE BIBB PER THE 2010 FPC SEC.606.2.(2).
 6) A CLEANOUT IS REQD. IN THE BASE OF THE STACK FOR THE
 MOP SINK PER 2010 FPC SEC.708.3.4.
 REVIEWED BY:
 TIM LARGE-
 CHIEF PLUMBING INSPECTOR
 TEL:561-805-6692
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-03-11 Cont ID  
Sent By llouie Date 2015-03-11 Time 16:37 Rev Time 0.00
Received By llouie Date 2015-03-11 Time 16:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2014-12-01 Cont ID  
Sent By llouie Date 2014-12-01 Time 17:11 Rev Time 0.00
Received By llouie Date 2014-12-01 Time 17:11 Sent To  
Notes
2014-12-01 17:13:03** ZONING FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) CONDITIONS OF ISPR #13-12/Z13120013 HAVE NOT BEEN
 ADDRESSED. CONDITIONS NEED TO BE ADDRESSED PRIOR TO
 SUBMITTING FOR BUILDING PERMITS. (8/15/14 REPEAT
 COMMENT: APPLICANT IS AWARE OF CONDITION)
  
 PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE
 ARE QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-08-15 Cont ID  
Sent By llouie Date 2014-08-15 Time 14:09 Rev Time 0.00
Received By llouie Date 2014-08-15 Time 14:09 Sent To  
Notes
2014-08-15 14:11:54** ZONING FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) CONDITIONS OF ISPR #13-12/Z13120013 HAVE NOT BEEN
 ADDRESSED. CONDITIONS NEED TO BE ADDRESSED PRIOR TO
 SUBMITTING FOR BUILDING PERMITS.
  
 2.) ENGINEERING PERMIT REQUIRED.
  
 PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE
 ARE QUESTIONS.