2014-08-14 08:10:08 | DATE: 8/11/2014 |
| PROJECT: TESH RESIDENCE |
| PERMIT#: 14050296 REVISION#14080058 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW ON REVISION |
| ACTION: DENIED |
| |
| 1) PROVIDE A PANEL SCHEDULE TO INDICATE NEW AND |
| EXISTING LOADS. |
| 2) PROVIDE A LOAD CALCULATION TO INDICATE EXISTING |
| ELECTRICAL PANEL AND SERVICE ARE ADAQUATE TO SERVE |
| ADDITIONAL LOADS. |
| 3) INDICATE CIRCUITRY ON PLANS. IDENTIFY NEW AND |
| EXISTING CIRCUITS AND DEVICES. FBC 107.2.1. |
| 4) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE |
| BATHROOMS. NEC 210.11 (C)(3) |
| 5) INDICATE STAIRWAY AND LANDINGS FROM 1ST TO 2ND FL. |
| 6) INCATE FAN BOXES WHERE REQUIRED FOR SUPPORT OF A |
| CEILING FAN. NEC 314.27(A) |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT |
| /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| ITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |